2007-03-02 09:16:36 | *** UNSAT *** | | | | 1) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES AND | | THE LIGHTING FIXTURES ON PLANS AND FIXTURE LEGEND DO | | NOT CORRELATE. | | PLEASE SEE THERE ARE SEVERAL AREAS/ROOMS WHICH THE | | LIGHTING WATTAGE EXCEEDS THAT OF THE TABLES AND | | ALLOWANCES PERMITTED BY THE TABLES AND THE FBC ENERGY | | CODE. | | 13-415.2. | | PLEASE SEE 13-415.1AB.1.1 AND SEE ENERGY CALCULATIONS | | FOR USE. | | PLEASE SEE THE TABLES FOR MAX LIGHTING ALLOWANCES. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-03-01 17:53:14 | IN ELEC FOR REVIEW |
|