Date |
Text |
2007-01-10 07:23:35 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE FLORIDA |
| STATUTES |
| NFPA 99C 2002 |
| |
| FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| |
| 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE |
| W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE |
| FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION |
| 11-4.22.3. |
| ****RESPONSE NOTED, BUT THE DOOR SWING SHALL SWING OUT |
| OF THE TOILET ROOM FOR THE ROOM TO BE ADAPTABLE. |
| |
| 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB |
| MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT |
| SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS |
| 104 & 111. |
| ****RESPONSE NOTED, BUT EPOXY PAINT DOES NOT COMPLY |
| WITH THE REQUIREMENT FOR A HARD SURFACE. |
| |
| 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE |
| CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY |
| ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW |
| COMPLIANCE WITH THE FOLLOWING: |
| A. OK |
| B. OK |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES - NOT |
| ADDRESSED. |
| D. OK |
| |
| 7. OK |
| 8. OK |
| |
| 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER |
| FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT |
| MANUF. SPECIFICATION. SECTION 611.1. |
| ****NO RESPONSE - NOT ADDRESSED. |
| |
| 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE |
| WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER |
| HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM |
| SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE |
| COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES |
| ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR |
| 4.5.2.1.3(B) FOR THE VACUUM SYSTEM. |
| ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES |
| REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER |
| RISER ISOMETRIC. |
| |
| 11. OK |
| 12. OK |
| 13. OK |
| 14. OK |
| 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE |
| VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR |
| THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE |
| IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION. |
| (INFORMATIONAL ONLY). |
| |
| *************NEW COMMENT************* |
| |
| 1B. THE PERSONAL SIGNATURE OF THE ARCHITECT SHALL |
| APPEAR ON ALL ARCHITECTURAL DOCUMENTS. 61G1-16.003 & FS |
| 481.2055. THE SEAL IS STAMPED WITH A SIGNATURE STAMP. |
| THIS IS NOT APPROVED. PLEASE SIGN EACH SHEET. |
| |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |