Plan Review Notes
Plan Review Notes For Permit 06090449
Permit Number 06090449
Review Stop P
Sequence Number 2
Notes
Date Text
2007-01-10 07:23:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE FLORIDA
 STATUTES
 NFPA 99C 2002
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE
 W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION
 11-4.22.3.
 ****RESPONSE NOTED, BUT THE DOOR SWING SHALL SWING OUT
 OF THE TOILET ROOM FOR THE ROOM TO BE ADAPTABLE.
  
 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB
 MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT
 SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS
 104 & 111.
 ****RESPONSE NOTED, BUT EPOXY PAINT DOES NOT COMPLY
 WITH THE REQUIREMENT FOR A HARD SURFACE.
  
 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE
 CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY
 ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. OK
 B. OK
 C. 11-4.24.6 EXPOSED PIPES & SURFACES - NOT
 ADDRESSED.
 D. OK
  
 7. OK
 8. OK
  
 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER
 FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT
 MANUF. SPECIFICATION. SECTION 611.1.
 ****NO RESPONSE - NOT ADDRESSED.
  
 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE
 WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER
 HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM
 SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE
 COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES
 ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR
 4.5.2.1.3(B) FOR THE VACUUM SYSTEM.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES
 REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER
 RISER ISOMETRIC.
  
 11. OK
 12. OK
 13. OK
 14. OK
 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE
 VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR
 THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE
 IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION.
 (INFORMATIONAL ONLY).
  
 *************NEW COMMENT*************
  
 1B. THE PERSONAL SIGNATURE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS. 61G1-16.003 & FS
 481.2055. THE SEAL IS STAMPED WITH A SIGNATURE STAMP.
 THIS IS NOT APPROVED. PLEASE SIGN EACH SHEET.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved