Date |
Text |
2006-12-03 20:15:03 | ATTACHED SHEET WITH REFERENCE TO FS 553.80(2)B), ONLY A |
| NOTICE FOR INFORMATIONAL PURPOSE AT THIS TIME. |
2006-10-16 18:48:33 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| NFPA 99C 2002 |
| |
| 1. SHT T.1 CODE NOTES #8 ACCESSIBILITY TO BE PER |
| FBC-2004 CHAPTER 11. CORRECT REFERENCE. |
| |
| 2. ALL SHEETS. SEAL SHALL IMPRESS INFORMATION REQUIRED |
| BY FAC 61G1-16.002(1) & FS 481.221. PRINTED NAME OF THE |
| PERSON SEALING THE DOCUMENT REQUIRED IN THE TITLE |
| BLOCK. FAC 61G1-16.004(6) & FS 481.2055. |
| |
| 3. SHT A.0 SHOW COMPLIANCE WITH THE FOLLOWING:FOR |
| W/C'S |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.5 FLUSH CONTROLS |
| |
| 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE |
| W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE |
| FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION |
| 11-4.22.3. |
| |
| 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB |
| MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT |
| SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS |
| 104 & 111. |
| |
| 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE |
| CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY |
| ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW |
| COMPLIANCE WITH THE FOLLOWING: |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE (CABINET DOORS ARE NOT |
| APPROVED IN THE CLEAR FLOOR SPACE. DELETE FROM |
| DETAIL). |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| |
| 7. SHT P.1 PLUMBING FIXTURE LEGEND SK-2 SINK MODEL NOT |
| APPROVED. (SEE ATTACHED MANUF. SHEET). MAXIMUM DEPTH |
| FOR AN ACCESSIBLE SINK IS 6-1/2" PER SECTION 11-4.24.4. |
| 8" IS INDICATED ON MANUF. SPECIFICATION SHEET. |
| |
| 8. SHT P.1 EWH & REC. PUMP DIAG. SHOWS PVC PIPE FOR P/T |
| DISCHARGE LINE & EMERGENCY PAN DRAIN LINE. THIS IS NOT |
| APPROVED. SECTION 504.6.2 AND TABLE 605.4. - PAN DRAIN |
| LINE AND P/T DISCHARGE LINE ARE SHOWN AS AIR BREAKS TO |
| THE FLOOR SINK. AIR GAPS ARE REQUIRED. SECTION 802.2 |
| AND DEFINITIONS.- A NOTE INDICATES "TO JAN. SINK BELOW" |
| BUT DETAIL SHOW PIPING TO FLOOR SINK. PLEASE CLARIFY. |
| SECTION 106.1.1. |
| |
| 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER |
| FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT |
| MANUF. SPECIFICATION. SECTION 611.1. |
| |
| 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE |
| WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER |
| HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM |
| SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE |
| COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES |
| ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR |
| 4.5.2.1.3(B) FOR THE VACUUM SYSTEM. |
| |
| 11. SHT P.2 THE COMPRESSOR AIR INTAKE SHALL COMPLY WITH |
| NFPA 99C SECTION 5.1.3.5.13.2. THE MATERIALS FOR THE |
| COMPRESSOR INTAKE PIPING SHALL COMPLY WITH NFPA 99C |
| SECTIONS 5.1.3.5.13.4 & 5.1.10.2.1. |
| |
| 12. SHTS P.1 & P.2 MORE INFORMATION IS REQUIRED FOR |
| ROOM 117. SUBMIT AN ELEVATION FOR THE SOUTH AND EAST |
| WALLS. IT APPEARS THAT THE WATER HEATER AND THE AIR |
| COMPRESSOR ARE LOCATED IN THE SAME SPACE. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| |
| 13. SHT P.2 DETAIL #6 VACUUM TUBES SHALL BE HARD-DRAWN |
| SEAMLESS COPPER PER NFPA 99C SECTION 5.1.10.2.1. DELETE |
| FROM REFERENCE THE OTHER MATERIALS. |
| |
| 14. SHT P.2 DETAIL #1 MORE INFORMATION IS REQUIRED. |
| SUBMIT INFORMATION ON THE DETAIL FOR THE AIR COMPRESSOR |
| INDICATING IF THE AIR INTAKE WILL BE CONNECTED TO THE |
| COMPRESSOR. IF NOT THE FLOOR SINK WILL NOT BE APPROVED |
| IN ROOM 117. SECTION 106.1.1. |
| |
| 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE |
| VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR |
| THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE |
| IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION. |
| |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |