Plan Review Notes
Plan Review Notes For Permit 06090449
Permit Number 06090449
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-25 13:53:03*****DENIED*****
  
  
  
 1.)NFPA 101 (2003 EDITION) AND FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.)CONSTRUCTION, AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY AND THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.) ALL EXITS AND EXIT CORRIDORS ARE TO REMAIN CLEAR
 AND UNOBSTRUCTED DURING CONSTRUCTION OPERATIONS.
  
 5.)ON SHEET A.1 IT SHOWS THAT ACCESS TO THE FIRE
 EXTINGUISHER(S) WILL BE OBSTRUCTED WHEN THE DOOR IS/ARE
 OPENED.
  
 6.)PLANS OR INFORMATION DOES NOT INDICATE IF THE
 EXISTING BUILDING HAS A FIRE ALARM SYSTEM.IF SO,
 PLEASE SHOW A LAYOUT OF THE DEVICES IN THE EXISTING/NEW
 TENANT SPACE.
  
 7.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER
 SYSTEM, SEPARATE PERMIT AND DRAWINGS ARE TO SUBMITTED
 FOR REVIEW.
  
 8.)THE FIRE DEPARTMENT WILL BE NOTIFIED WHEN A FIRE
 PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED
 TO SERVICE.
  
  
  
  