Date |
Text |
2006-09-30 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE FAC 61G1-16.004, |
| WHICH REQUIRES THE PRINTED NAME OF THE |
| ARCHITECT ON TITLE BLOCKS. |
| PLEASE ALSO SEE THAT THE RAISED SEALS |
| MUST BE CLEAR AND VISABLE WITH ALL |
| INFORMATION AS REQUIRED ON SAID SEAL. |
| PLEASE SEE SEALS ARE NOT EASILY |
| READABLE. |
| FS 481.221, FAC 61G1-16.003 |
| ** THIS IS REQUIRED FOR ALL SHEETS AND |
| FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| 2) NOTE: PLEASE SEE THE FOLLOWING MIN |
| CODES SHALL BE STATED ON PLANS. IMPLY |
| STATING THE "LATEST EDITION" CAN NOT BE |
| USED AS THE LATEST EDITIONS OF SOME |
| CODES ARE OUT AND AVAILABLE YET NOT YET |
| ADOPTED BY THE STATE. |
| PLEASE STATE THE FOLLOWING. |
| 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003 |
| NFPA-101, 2004 FBC. |
| PLEASE KNOW, OTHER CODES RELEVANT MAY BE |
| REQUESTED BY OTHER REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE THAT NEC 517, 517.13 |
| DETAIL IS SHOWN ON PLANS. |
| PLEASE SEE NOTE BELOW RISER DENOTING |
| GROUND BOND PER NEC MAY NOT USED IN LEIU |
| OF DETAIL REQUIRED. |
| FBC 106.1.2 ADMIN SECT AS ADOPTED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 4) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| .1.2 AND .1.3. |
| PLEASE PROVIDE LIGHTING CONTROL(S), |
| STATED DEVICES, LOCATIONS OF OVER RIDES |
| AND EVICES. PLEASE INDICATE THE MAX |
| TIMES ON OVER RIDES. (FYI, TIMER TYPE |
| 4HRS MAX, OCCUPANT TYPE 30MINS MAX). |
| PLEASE INDICATE THE MAX LPD(LIGHTING |
| POWER DENSITIES). PER 13-415.2.ABC.1, |
| TABLES 415. |
| |
| 5) NOTE: PLEASE INDICATE ALL ROOM/AREAS DESIGNATIONS ON |
| PLANS AND CORRELATE |
| PANEL SCHEDULE WHICH IS TO BE SPECIFIC |
| TO AREAS BEING FED. |
| 408.4, |
| |
| 6) NOTE: PLEASE PROVIDE EITHER NEW OR |
| EXISTING SIGN CIRCUIT LOCATION PER |
| 600.5. IT IS UNCLEAR AT THIS TIME. |
| |
| 7) NOTE: PLEASE SEE RISER SHOW THE MAIN |
| PANEL IN SPACE AS 400 MCB. PLEASE SEE |
| THIS APPEARS TO BE A MISPRINT AS THE |
| SCHEDULE AND SERVICE PROVIDED MENTIONS |
| 300A. |
| POSSIBLE, 400MLO/300MCB. |
| FBC 106.1.2 ADMIN SECT. |
| |
| 8) NOTE: PLEASE INDICATE IF PANEL "A" |
| CONTAINS "FEED-THRU" LUGS OR IS THERE |
| OCP WHICH FEEDS PANEL"A-1'.?? |
| |
| 9) NOTE: PLEASE INDICATE WHERE THE |
| CONNECTED LOADS ARE BEIGN DERIVED. |
| PLEASE INDICATE A LOAD SUMMARY FOR |
| SPACE. PLEASE ALSO INDICATE ALL |
| CONTINUOUS LOADS AT 125% (3OR MORE HRS). |
| 220.3,220.10,220.11,220.13,215.3, 230.42 |
| ETC. |
| |
| 10) NOTE: PLEASE INDICATE "EQUIPMENT |
| GROUNDING" METHOD FROM MAIN MDP TO ALL |
| EQUIPMENT. |
| 250.110, 250.122. |
| ** PLEASE KNOW, IF USINGCONDUIT, THERE |
| MUST BE THE NEW CONNECTORS WHICH MUST BE |
| LSTED FOR THIS PURPOSE, OTHERWISE PLEASE |
| INDICATE THE "EQUIPMENT GROUNDING |
| CONDUCTOR" PER 250.122. |
| |
| 11) NOTE; PLEASE SEE PANEL "A-1" |
| INDICATES 30POLES, YET SHOWS 42 |
| CIRCUITS/POLES ARE SHOWN ON PANEL.. |
| PLEASE CORRELATE AND ADJUST. |
| 106.1.2 FBC. |
| |
| 12) NOTE; PLEASE PROVIDE THE AIC RATING |
| FOR THE NEW MB FROM MDP TO NEW TENANT |
| SPACE. |
| PLEASE ALSO SEE THE AIC RATING FOR EACH |
| OF THE TENANT PANELS IS BEING SHOWN AT |
| 22K, WHICH SEEMS HIGH FOR BRANCH BRKRS?? |
| ** THIS IS OK, HOWEVER PLEASE KNOW, IF |
| SHOWN, THEN 22K RATED BRNACH BRKRS WILL |
| BE REQUIRED. |
| 110.9, |
| FBC 106.1.2 ADMIN SECT. |
| 106.3.5.1.2 |
| |
| ** PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT THE ELECTRICAL PLANS/DEISGN. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |