Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop E
Sequence Number 5
Notes
Date Text
2007-10-18 16:33:37 
 *** DENIED 5TH REVIEW *****
  
 1) NOTE: PLEASE KNOW THIS IS THE FIRST TIME THE INPUT
 DATA REPORT IS BEING REVIEWED.
 PLEASE SEE THE INPUT DATA REPORT SUBMITTED WITH
 ARCHITECTURAL PLANS AND BLACK BINDER WHICH WAS NOT
 SUBMITTED AS A RESUB AND ALSO THE NEW INPUT DATA REPORT
 SHEETS LEFT AFTER MEETING HELD ON 10/11/07 DO NOT
 CORRELATE WITH THE ENERGY CALCULATIONS SUMMARY SHEETS
 NOR DO EITHER ONE COORDINATE WITH THE PLANS.
 PLEASE KNOW AS THIS IS THE FIRST TIME THE SHEETS WERE
 SUBMITTED THIS IS THE FIRST ACTUAL REVIEW OF
 DOCUMENTS.
 PLEASE SEE FOR EXAMPLE: THE IDR WHICH WAS RUN ON
 4/25/07 UNDER THE 3.0 VERSION CONTAINS EXTERIOR
 LIGHTING FIXTURES HOWEVER THE SUMMARY SHEETS STATES
 *NONE ENTERED*.
 PLEASE SEE FOR EXAMPLE: THE TYPE *M* FIXTURES FOR
 PARKING GARAGE WHICH ARE SHOWN AS 1000WATTS ON THE
 PLANS AND FIXTURE LEGEND ARE ONLY 455WATTS ON THE IDR.
 PLEASE SEE FOR EXAMPLE: THE INPUT DATA REPORT DATED
 9/11/07 DOES NOT CONTAIN ANY EXTERIOR LIGHTING FIXTURES
 WHICH ARE NOT POSSIBLE WHEN THE PLANS CONTAIN NUMEROUS
 INCLUDING THE TYPE *M* AS NOTED ABOVE ALONG WITH
 MISSING TYPE *K*.
 PLEASE SEE FOR EXAMPLE THE INTERIOR LIGHTING FIXTURES
 *J* AND *JQ* WHICH ARE IN SERVICE BAY AREAS IN WHICH
 THE NUMBER OF FIXTURES ON PLANS ARE DIFFERENT THAN THE
 IDR.
 PLEASE SEE FOR EXAMPLE: THE STAIRS (BOTH), HALLWAY
 AREA, VESTIBULE ETC WHICH THESE TOTAL NUMBER OF
 FIXTURES ON PLANS EXCEED THAT AS ON THE IDR.
  
 THESE ARE SOME EXAMPLES. PLEASE GO THROUGH THE ENERGY
 CALCULATIONS, PLEASE RUN COMPLETE ENERGY CALCULATIONS
 UNDER 2.11 (2004 FBC W/2005 REVISION).
 THIS OFFICE WILL REQUIRE BOTH THE SUMMARY SHEETS AND
 THE INPUT DATA SHEETS TO COORDINATE WITH THE DATES THEY
 HAVE BEEN RUN.\
 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3,13-103.1.1.1
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. THIS
 WILL BE A RE-SUBMITTAL AND THE RE-SUBMITTAL FEE OF 10%
 OF THE BASE PERMIT FEE WILL BE DUE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  