Plan Review Notes For Permit 06090410 |
Permit Number |
06090410 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-07-27 16:32:54 | | | *** UNSAT 4TH REVIEW *** | | | | 1) NOTE: PLEASE SEE THE PREVIOUS REVIEWS WHICH | | REQUESTED THE INPUT DATA REPORT TO BE SUBMITTED AS | | REQUIRED FOR REVIEW. THE RESPONSE LETTER FROM DESIGN | | TEAM MENTIONS THIS WILL BE SUBMITTED HOWEVER COULD NOT | | LOCATE THIS WITH THE ENERGY CALCULATIONS OR OTHER | | DOCUMENTS SUBMITTED. | | PLEASE SUBMIT SO THAT A REVIEW OF SAID ENTERED | | INFORMATION CAN BE REVIEW WITH PLANS. | | 13-415.1.B/13-415.2 | | | | 2) NOTE: PLEASE SEE PREVIOUS NOTES MENTIONED THAT THE | | MECHANICAL EQUIPMENT WAS STILL BEING SHOWN ON THE | | ADJACENT *BUILDING* ON ELECTRICAL AND OTHER TRADE | | SHEETS.. PLEASE SEE THE RESPONSE WAS THAT THIS | | EQUIPMENT WOULD BE MOVED TO ROOF. THIS WAS DONE ON | | ELECTRICAL PLANS HOWEVER THE MECHANICAL PLANS STILL | | INDICATE THIS EQUIPMENT ON THE ADJACENT BUILDING. | | PLEASE ADJUST M-PLANS. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|