Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-27 16:32:54 
 *** UNSAT 4TH REVIEW ***
  
 1) NOTE: PLEASE SEE THE PREVIOUS REVIEWS WHICH
 REQUESTED THE INPUT DATA REPORT TO BE SUBMITTED AS
 REQUIRED FOR REVIEW. THE RESPONSE LETTER FROM DESIGN
 TEAM MENTIONS THIS WILL BE SUBMITTED HOWEVER COULD NOT
 LOCATE THIS WITH THE ENERGY CALCULATIONS OR OTHER
 DOCUMENTS SUBMITTED.
 PLEASE SUBMIT SO THAT A REVIEW OF SAID ENTERED
 INFORMATION CAN BE REVIEW WITH PLANS.
 13-415.1.B/13-415.2
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES MENTIONED THAT THE
 MECHANICAL EQUIPMENT WAS STILL BEING SHOWN ON THE
 ADJACENT *BUILDING* ON ELECTRICAL AND OTHER TRADE
 SHEETS.. PLEASE SEE THE RESPONSE WAS THAT THIS
 EQUIPMENT WOULD BE MOVED TO ROOF. THIS WAS DONE ON
 ELECTRICAL PLANS HOWEVER THE MECHANICAL PLANS STILL
 INDICATE THIS EQUIPMENT ON THE ADJACENT BUILDING.
 PLEASE ADJUST M-PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]