2007-05-17 15:37:57 | *****UNSAT***** |
| |
| |
| PREVIOUS COMMENTS WHICH STILL NEED TO BE ADDRESSED: |
| |
| 03.ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS |
| EXIST.EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS |
| EVEN WHEN THEY ARE NOT CLEARY OBVIOUS.DISPLAY NEW |
| EXIT SIGN PLACEMENT SUCH THAT NO POINT IN AN EXIT |
| ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING |
| DISTANCE OR 100 FEET, WHICHEVER IS LESS, FROM THE |
| NEAREST SIGN. |
| |
| 04.NO EMERGENCY SIGN LIGHTING DECLARED ON PAGE E-103. |
| PLEASE INDICATE LOCATION OF THESE DEVICES |
| |
| 09.BUILDING ADDRESS WITH A MININIMUM OF 6" IN HEIGHT |
| AND 1" IN WIDTH REQUIRED.IN ADDITION TO THE HEIGHT |
| REQUIREMENT AS SHOWN ON SHEET A-5, THE WIDTH |
| REQUIREMENT SHALL BE ADHERED ALSO. |
| |
| 15.CONSTRUCTION, DEMOLITION, AND RENOVATION |
| OPERATIONS SHALL COMPLY WITH NFPA 241.INDICATE ON |
| APPROPIATE PLAN SHEET |
| |
| 16.DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| INDICATE ON THE APPROPIATE PLAN SHEET |
| |
| 17.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. |
| INDICATE ON THE APPROPIATE PLAN SHEET THAT THE KNOX BOX |
| WILL BE INSTALLED IN AN ACCESSIBLE LOCATION AND/OR |
| WHERE DIRECTED BY THE FIRE MARSHAL. |
| |
| NEW COMMENT |
| |
| AA.IT IS NOTED AS PER LILU URSA THAT THE NUMERICAL |
| ADDRESS IS 3023;HOWEVER3021 IS LISTED IN THE TITLE |
| BLOCK OF SOME OF THE SUBMITTED PLAN SHEETS. |
| |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT |
| WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |