2007-05-17 15:37:57*****UNSAT*****
  
  
 PREVIOUS COMMENTS WHICH STILL NEED TO BE ADDRESSED:
  
 03.ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS
 EXIST.EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS
 EVEN WHEN THEY ARE NOT CLEARY OBVIOUS.DISPLAY NEW
 EXIT SIGN PLACEMENT SUCH THAT NO POINT IN AN EXIT
 ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING
 DISTANCE OR 100 FEET, WHICHEVER IS LESS, FROM THE
 NEAREST SIGN.
  
 04.NO EMERGENCY SIGN LIGHTING DECLARED ON PAGE E-103.
 PLEASE INDICATE LOCATION OF THESE DEVICES
  
 09.BUILDING ADDRESS WITH A MININIMUM OF 6" IN HEIGHT
 AND 1" IN WIDTH REQUIRED.IN ADDITION TO THE HEIGHT
 REQUIREMENT AS SHOWN ON SHEET A-5, THE WIDTH
 REQUIREMENT SHALL BE ADHERED ALSO.
  
 15.CONSTRUCTION, DEMOLITION, AND RENOVATION
 OPERATIONS SHALL COMPLY WITH NFPA 241.INDICATE ON
 APPROPIATE PLAN SHEET
  
 16.DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
 INDICATE ON THE APPROPIATE PLAN SHEET
  
 17.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
 INDICATE ON THE APPROPIATE PLAN SHEET THAT THE KNOX BOX
 WILL BE INSTALLED IN AN ACCESSIBLE LOCATION AND/OR
 WHERE DIRECTED BY THE FIRE MARSHAL.
  
 NEW COMMENT
  
 AA.IT IS NOTED AS PER LILU URSA THAT THE NUMERICAL
 ADDRESS IS 3023;HOWEVER3021 IS LISTED IN THE TITLE
 BLOCK OF SOME OF THE SUBMITTED PLAN SHEETS.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722