Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-22 11:16:36 
 ******* UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE THAT THERE ARE STILL SOME ITEMS FROM
 PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN CLEARED UP AND
 NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE RESPONSE FROM DESIGNERS MENTIONS
 THE ADDRESS WHICH HAS BEEN GIVEN BY THE ADDRESSING
 REVIEWER IS THAT OF 3023 AND IS NOW ON ALL TITLE BLOCKS
 ACCORDINGLY, HOWEVER THE TITLE BLOCKS ON ALL SHEETS
 STILL INDICATE 3021?
 PLEASE KNOW IF THIS IS THE ONLY COMMENT ON SOME SHEETS,
 THIS MAY BE HAND PRINTED ON SHEETS BY CONTRACTOR OR
 OTHER DESIGN STAFF.
 PLEASE REVISE ON SHEETS WHICH NEED TO BE CHANGED OUT.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 CONTROL OF EGRESS LIGHTING IN STAIRS. RESPONSE MENTIONS
 THAT ONCE ON DEVICE IS ACTIVATED THAT 15MINS IS MORE
 THAN ENOUGH TIME TO EGRESS TO THE NEXT LEVEL, HOWEVER
 THE COMMENT IS FOR THE FAILURE OF ANY ONE SINGLE DEVICE
 (OCCUPANCY SENSORS) CAN NOT LEAVE ANY ONE AREA OF
 EGRESS IN TOTAL DARKNESS.
 PLEASE SEE 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE
 LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS
 OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE
 EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION
 TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND
 THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT
 IN THE AREA SERVED BY THE LIGHTING UNITS.
 PLEASE ALSO SEE CHAPTER 10 OF THE FBC 1006.1.2 WHICH
 STATES THE SAME.
 IT IS LS 101 7.9.2.2 WHICH MENTIONS THE FAILURE OF A
 SINGLE DEVICE, SWITCHING, TRIPPING OF A BREAKER ETC.
 THIS WOULD REQUIRE A MINIMUM OF TWO OCCUPANCY SENSORS
 OR DEVICES OF SOME TYPE TO DETECT THE OCCUPANT AND TURN
 ON THE LIGHTING. IF AN OCCUPANT WAS TO LEAVE AN UPPER
 FLOOR, AND THE DEVICE WAS NOT IN WORKING ORDER, THEN A
 SECOND DEVICE IS REQUIRED IN THE VICINITY TO DO THE
 SAME AS THE PRIMARY DEVICE.
  
 3) NOTE: PLEASE SEE THAT AS THIS IS BEING CONSIDERED
 AND CONSTRUCTED AS A SEPARATE BUILDING, AS NOTED ON
 PREVIOUS REVIEW, THE MECHANICAL AND ELECTRICAL
 EQUIPMENT IS STILL BE SHOWN ON THE EXISTING ROOF OF THE
 EXISTING BUILDING WHICH IS NOT CONSIDER PART OF THE NEW
 *BUILDING*
 PLEASE RELOCATE.
 PLEASE SEE SOME SHEETS STILL INDICATE THE PREVIOUS WALL
 AND FLOOR LAYOUTS WHICH DO NOT COORDINATE WITH THE REST
 OF THE PLANS. (*SITE PLANS*)
 FBC 106.1.2
 225.30, 230.3.
  
 4) NOTE: PLEASE SEE NOW THERE ARE HAND DRAWN CHANGES TO
 SHEET E-101 WHICH ONE OF THE ITEMS IN THAT OF AN EXIT
 SIGN WHICH IS PLACED SO THAT THE OCCUPANTS IN SOUTHEAST
 STAIR TOWER ARE TO EGRESS INTO THE ADJACENT HUMMER
 BUILDING??
 NO HAND DRAWN CHANGES ARE PERMITTED TO PLANS FS
 471.025
 PLEASE SEE FIRE AND BUILDING REVIEWS.
 PLEASE SEE THE ELEVATION ON A105 SHOWS WHAT APPEARS TO
 BE AN EXIT DOORWAY FROM VESTIBULE TO OUTSIDE, SHOULD
 NOT THIS EXIT LIGHT BE LOCATED ABOVE THE EAST DOOR IN
 THIS STAIR TOWER?
 PLEASE SEE OTHER HAND DRAWN CIRCULAR SYMBOL WHICH IS
 ALSO ADJACENT TO THIS SAME AREA?
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE RESPONSE LETTERS MENTIONS THE OVER
 RIDE TIMES AND TIMES HOWEVER COULD NOT LOCATE THE TIMES
 FOR THE OCCUPANCY DEVICES. PLANS DO NOTE THE TIME FOR
 THE OVER RIDE OF THE SERVICE BAY. 13-415.1.ABC.1.1
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 MINIMUM LEVELS FOR HORN AND STROBE DEVISE WHICH ARE
 REQUIRED TO BE STATED ON THE BASE SET OF BUILDING PLANS
 FOR FBC ADA COMPLIANCE. IT IS KNOWN THAT ANY FA WORK
 WILL BE UNDER SEPARATE PERMIT HOWEVER BASE BUILDINGS
 MUST INDICATE MINIMUM COMPLIANCE.
 FBC 11-4.28.1,.2 AND .3(4).
 FBC 106.3.5.1.2
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW AND RESPONSE
 MENTIONS THAT THE MINIMUM LEVELS FOR WIND LOADS FOR
 ROOF TOP LIGHT POLES WILL BE STATED ON PLANS AND TO SEE
 FIXTURE LEGEND HOWEVER THE FIXTURE LEGEND DOES NOT
 INDICATE THE *140MPH MINIMUM* DESIGNATION.
 THE CALCULATIONS CAN BE SET UP AS A *PROVISO* WHICH
 WILL ALLOW ISSUANCE AND CALCULATIONS TO BE SUBMITTED
 BEFORE INSTALLATION, HOWEVER PLEASE STATE THE 140. FBC
 106.1.2
  
 8) NOTE: PLEASE SEE THE THIRD PARKING
 LEVEL/OUTSIDE/EXTERIOR LIGHTING WHICH STILL INDICATE
 LIGHTING TO A LIGHTING CONTACTOR #3, BUT NO DETAIL WAS
 SUBMITTED.
 PLEASE SHOW.
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE PREVIOUS NOTES WHICH MENTIONED TO
 CORRELATE AND COMPLETE THE ENERGY CALCULATIONS AND TO
 VERIFY THE METHOD AS SUBMITTED.
 PLEASE SEE THE FRONT COVER SHEET MENTIONS THAT THE
 INPUT DATA REPORT MUST BE SUBMITTED ALONG WITH
 COMPLIANCE REPORT, HOWEVER THIS HAS NOT BEEN DONE.
 PLEASE SEE 13-415.1.AB.1.1
  
 10) NOTE: ** NOT A COMMENT FOR TEELE ENGINEERING.
 PLEASE SEE THE PREVIOUS REVIEW WHICH INDICATED THAT THE
 *S* SHEETS CONTAINED A *RUBBER-STAMP* FOR REQUIRED
 ORIGINAL SIGNATURE, AND RESPONSE WAS THAT ALL SHEETS
 WILL NOW BE SIGNED, HOWEVER ONLY ONE OF THE *S* SHEETS
 WERE CORRECTED. PLEASE SEE BUILDING REVIEW NOTES AS
 THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS TIME
 AND DOES NOT AFFECT THE ELECTRICAL PLANS.
 FS 471.025
  
 11) NOTE: PLEASE SEE NOTE BELOW ON PREVIOUS REVIEW
 WHICH REQUESTED ALL OLD/VOIDED SHEETS TO BE REMOVED
 FROM THE TWO COMPLETED SETS. ONE SET OF EACH OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED WITH THE TWO SETS
 SEPARATELY AND NOT INCLUDED IN SETS.
 THIS WILL HELP ALLEVIATE ANY CONFUSION FOR NEW AND OLD
 SHEETS , AND WILL HELP TO NOT CAUSE ANY FURTHER DELAYS
 IN THE PROJECT.
  
  
 ** PLEASE BE AWARE OF COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]