2007-04-22 11:16:36 | |
| ******* UNSAT 3RD REVIEW ****** |
| |
| ** PLEASE SEE THAT THERE ARE STILL SOME ITEMS FROM |
| PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN CLEARED UP AND |
| NEED TO BE ADDRESSED. |
| |
| 1) NOTE: PLEASE SEE RESPONSE FROM DESIGNERS MENTIONS |
| THE ADDRESS WHICH HAS BEEN GIVEN BY THE ADDRESSING |
| REVIEWER IS THAT OF 3023 AND IS NOW ON ALL TITLE BLOCKS |
| ACCORDINGLY, HOWEVER THE TITLE BLOCKS ON ALL SHEETS |
| STILL INDICATE 3021? |
| PLEASE KNOW IF THIS IS THE ONLY COMMENT ON SOME SHEETS, |
| THIS MAY BE HAND PRINTED ON SHEETS BY CONTRACTOR OR |
| OTHER DESIGN STAFF. |
| PLEASE REVISE ON SHEETS WHICH NEED TO BE CHANGED OUT. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| CONTROL OF EGRESS LIGHTING IN STAIRS. RESPONSE MENTIONS |
| THAT ONCE ON DEVICE IS ACTIVATED THAT 15MINS IS MORE |
| THAN ENOUGH TIME TO EGRESS TO THE NEXT LEVEL, HOWEVER |
| THE COMMENT IS FOR THE FAILURE OF ANY ONE SINGLE DEVICE |
| (OCCUPANCY SENSORS) CAN NOT LEAVE ANY ONE AREA OF |
| EGRESS IN TOTAL DARKNESS. |
| PLEASE SEE 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE |
| LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS |
| OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE |
| EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION |
| TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND |
| THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT |
| IN THE AREA SERVED BY THE LIGHTING UNITS. |
| PLEASE ALSO SEE CHAPTER 10 OF THE FBC 1006.1.2 WHICH |
| STATES THE SAME. |
| IT IS LS 101 7.9.2.2 WHICH MENTIONS THE FAILURE OF A |
| SINGLE DEVICE, SWITCHING, TRIPPING OF A BREAKER ETC. |
| THIS WOULD REQUIRE A MINIMUM OF TWO OCCUPANCY SENSORS |
| OR DEVICES OF SOME TYPE TO DETECT THE OCCUPANT AND TURN |
| ON THE LIGHTING. IF AN OCCUPANT WAS TO LEAVE AN UPPER |
| FLOOR, AND THE DEVICE WAS NOT IN WORKING ORDER, THEN A |
| SECOND DEVICE IS REQUIRED IN THE VICINITY TO DO THE |
| SAME AS THE PRIMARY DEVICE. |
| |
| 3) NOTE: PLEASE SEE THAT AS THIS IS BEING CONSIDERED |
| AND CONSTRUCTED AS A SEPARATE BUILDING, AS NOTED ON |
| PREVIOUS REVIEW, THE MECHANICAL AND ELECTRICAL |
| EQUIPMENT IS STILL BE SHOWN ON THE EXISTING ROOF OF THE |
| EXISTING BUILDING WHICH IS NOT CONSIDER PART OF THE NEW |
| *BUILDING* |
| PLEASE RELOCATE. |
| PLEASE SEE SOME SHEETS STILL INDICATE THE PREVIOUS WALL |
| AND FLOOR LAYOUTS WHICH DO NOT COORDINATE WITH THE REST |
| OF THE PLANS. (*SITE PLANS*) |
| FBC 106.1.2 |
| 225.30, 230.3. |
| |
| 4) NOTE: PLEASE SEE NOW THERE ARE HAND DRAWN CHANGES TO |
| SHEET E-101 WHICH ONE OF THE ITEMS IN THAT OF AN EXIT |
| SIGN WHICH IS PLACED SO THAT THE OCCUPANTS IN SOUTHEAST |
| STAIR TOWER ARE TO EGRESS INTO THE ADJACENT HUMMER |
| BUILDING?? |
| NO HAND DRAWN CHANGES ARE PERMITTED TO PLANS FS |
| 471.025 |
| PLEASE SEE FIRE AND BUILDING REVIEWS. |
| PLEASE SEE THE ELEVATION ON A105 SHOWS WHAT APPEARS TO |
| BE AN EXIT DOORWAY FROM VESTIBULE TO OUTSIDE, SHOULD |
| NOT THIS EXIT LIGHT BE LOCATED ABOVE THE EAST DOOR IN |
| THIS STAIR TOWER? |
| PLEASE SEE OTHER HAND DRAWN CIRCULAR SYMBOL WHICH IS |
| ALSO ADJACENT TO THIS SAME AREA? |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SEE RESPONSE LETTERS MENTIONS THE OVER |
| RIDE TIMES AND TIMES HOWEVER COULD NOT LOCATE THE TIMES |
| FOR THE OCCUPANCY DEVICES. PLANS DO NOTE THE TIME FOR |
| THE OVER RIDE OF THE SERVICE BAY. 13-415.1.ABC.1.1 |
| |
| 6) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE |
| MINIMUM LEVELS FOR HORN AND STROBE DEVISE WHICH ARE |
| REQUIRED TO BE STATED ON THE BASE SET OF BUILDING PLANS |
| FOR FBC ADA COMPLIANCE. IT IS KNOWN THAT ANY FA WORK |
| WILL BE UNDER SEPARATE PERMIT HOWEVER BASE BUILDINGS |
| MUST INDICATE MINIMUM COMPLIANCE. |
| FBC 11-4.28.1,.2 AND .3(4). |
| FBC 106.3.5.1.2 |
| |
| 7) NOTE: PLEASE SEE PREVIOUS REVIEW AND RESPONSE |
| MENTIONS THAT THE MINIMUM LEVELS FOR WIND LOADS FOR |
| ROOF TOP LIGHT POLES WILL BE STATED ON PLANS AND TO SEE |
| FIXTURE LEGEND HOWEVER THE FIXTURE LEGEND DOES NOT |
| INDICATE THE *140MPH MINIMUM* DESIGNATION. |
| THE CALCULATIONS CAN BE SET UP AS A *PROVISO* WHICH |
| WILL ALLOW ISSUANCE AND CALCULATIONS TO BE SUBMITTED |
| BEFORE INSTALLATION, HOWEVER PLEASE STATE THE 140. FBC |
| 106.1.2 |
| |
| 8) NOTE: PLEASE SEE THE THIRD PARKING |
| LEVEL/OUTSIDE/EXTERIOR LIGHTING WHICH STILL INDICATE |
| LIGHTING TO A LIGHTING CONTACTOR #3, BUT NO DETAIL WAS |
| SUBMITTED. |
| PLEASE SHOW. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 9) NOTE: PLEASE SEE PREVIOUS NOTES WHICH MENTIONED TO |
| CORRELATE AND COMPLETE THE ENERGY CALCULATIONS AND TO |
| VERIFY THE METHOD AS SUBMITTED. |
| PLEASE SEE THE FRONT COVER SHEET MENTIONS THAT THE |
| INPUT DATA REPORT MUST BE SUBMITTED ALONG WITH |
| COMPLIANCE REPORT, HOWEVER THIS HAS NOT BEEN DONE. |
| PLEASE SEE 13-415.1.AB.1.1 |
| |
| 10) NOTE: ** NOT A COMMENT FOR TEELE ENGINEERING. |
| PLEASE SEE THE PREVIOUS REVIEW WHICH INDICATED THAT THE |
| *S* SHEETS CONTAINED A *RUBBER-STAMP* FOR REQUIRED |
| ORIGINAL SIGNATURE, AND RESPONSE WAS THAT ALL SHEETS |
| WILL NOW BE SIGNED, HOWEVER ONLY ONE OF THE *S* SHEETS |
| WERE CORRECTED. PLEASE SEE BUILDING REVIEW NOTES AS |
| THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS TIME |
| AND DOES NOT AFFECT THE ELECTRICAL PLANS. |
| FS 471.025 |
| |
| 11) NOTE: PLEASE SEE NOTE BELOW ON PREVIOUS REVIEW |
| WHICH REQUESTED ALL OLD/VOIDED SHEETS TO BE REMOVED |
| FROM THE TWO COMPLETED SETS. ONE SET OF EACH OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED WITH THE TWO SETS |
| SEPARATELY AND NOT INCLUDED IN SETS. |
| THIS WILL HELP ALLEVIATE ANY CONFUSION FOR NEW AND OLD |
| SHEETS , AND WILL HELP TO NOT CAUSE ANY FURTHER DELAYS |
| IN THE PROJECT. |
| |
| |
| ** PLEASE BE AWARE OF COMMENTS FROM OTHER TRADES WHICH |
| MAY AFFECT ELECTRICAL PLANS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |