Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-22 13:55:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)ADDRESSED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4-5.) ADDRESSED.
  
 6.)THE INFORMATION REQUIRED FOR THE ENGINEER
 FAC61G15-23.002 IS TO BE ON EACH SHEET.THIS COMMENT
 IS FOR THE FIRE SPRINKLER ENGINEER.THIS APPLIES TO
 THE CALCS AND THE DRAWINGS.IF AN INDEX SHEET IS NOT
 PROVIDED FOR THE CALCS, EACH SHEET IS TO BE SIGNED,
 SEALED, AND DATED.
  
 7.) FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 3RD REVIEW ? ONLY TWO SETS WERE SUBMITTED.NOTE THAT
 ALTHOUGH THIS PLAN HAS PASSED SOME REVIEWS, ANOTHER
 REVIEW WILL BE REQUIRED SO THAT THOSE REVIEWERS CAN
 STAMP THEIR SHEETS WHEN THE THIRD SET IS SUBMITTED.
  
 8.) PROVIDE ORIGINAL SIGNED, SEALED, DATED SOILS
 REPORTS, FBC1802.2.1, 1802.2.3.THREE SETS REQUIRED.
 AS STATED IN THE PREVIOUS REVIEWS, THE SIGNATURE CANNOT
 BE A PHOTOCOPY.
  
 9.) ADDRESSED.
  
 10.)ADDRESSED, BUT SEE OTHER COMMENTS REGARDING
 PRODUCT APPROVALS.
  
 11.)ADDRESSED.
  
 12.)IT IS NOT CLEAR IF THE EQUIPMENT SHEDS WERE
 INCLUDED IN THE BUILDING CODE SUMMARY.THIS IS THE
 THIRD REQUEST FOR THIS INFORMATION.IS THIS AREA
 INCLUDED IN ONE OF THE OTHER EXISTING BUILDINGS?THE
 PLAN SHOWS THE EXISTING EQUIPMENT SHED AGAINST THIS
 BUILDING.ARE YOU DESIGNING AS ONE BUILDING OR TWO
 SEPARATE BUILDINGS?
  
 13-17.) ADDRESSED.
  
 18.)REGARDING MAXIMUM AREA OF EXTERIOR WALL OPENINGS,
 OPENINGS AND PERCENTAGES WERE PROVIDED FOR THE EXISTING
 BUILDINGS.PROVIDE ALSO FOR THE PROPOSED BUILDING TO
 SHOW COMPLIANCE WITH FBC TABLE 704.8.NOTE THAT EAST
 ELEVATION HAS A LARGE AMOUNT OF OPENINGS ON A PORTION
 OF THE WALL.SEE THE ATTACHED COMMENTARY IN REGARDS TO
 UNIFORM DISTRIBUTION.
  
 THE % OF WALL OPENINGS, EXISTING VW SERVICE TO NEW
 SERVICE, SHOULD BE 15%-45%.
  
 EQUIPMENT SHEDS ARE SHOWN.ARE THEY ALSO TYPE II B
 CONSTRUCTION?ONE IS SHOWN CONNECTED TO THE NEW
 SERVICE BUILDING, BUT NOT DETAILS ARE PROVIDED.IS
 THIS AN EXISTING BUILDING?COMPLIANCE WITH FBC TABLE
 601, FBC TABLE 704.8 IS TO BE SHOWN ON THE PLAN.
  
 19.)ADDRESSED.
  
 20.)MSP1 STATES THAT EXISTING HUMMER BUILDING HAS A 2
 HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE
 FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH
 THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER
 CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE
 EXISTING WALL.SEE FBC TABLE 602.IT IS ACCEPTABLE TO
 EXCEED CODE COMPLIANCE, BUT B OCCUPANCY REQUIREMENT IS
 1 HOUR.THE NEW SERVICE HAS A 2 HOUR REQUIREMENT.
  
 MSP1 STATES THAT THE EXISTING SERVICE BUILDING HAS A 2
 HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE
 FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH
 THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER
 CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE
 EXISTING WALL.
  
 PLEASE NOTE REQUIREMENTS FOR NEW SERVICE BUILDING. NOTE
 ON MSP1 AND SHOW REQUIREMENTS ON THE PLAN.MSP1 SHOWS
 2 HOUR ON THE WALL ADJACENT TO THE HUMMER SHOWROOM, BUT
 DOES NOT SHOW THE 2 HOUR REQUIREMENT FOR THE STORAGE
 AND OIL STORAGE AREAS.
  
 21.)ADDRESSED.
  
 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND
 EXISTING VW SERVICE/VW SHOWROOM?THIS WAS DISCUSSED IN
 A MEETING AS BEING A CANOPY. PLEASE LABEL THIS AREA.
  
 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A2-03,
 A303, SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED
 DOORS IN A SERIES.
  
 THIS WAS ADDRESSED ON MOST PAGES.PLEASE ALSO REVISE
 THE ELECTRICAL SHEETS AND CHECK ALL SHEETS.
  
 24-27.) ADDRESSED.
  
 28.)RESPONSE LETTER STATES THAT ALL LIFE SAFETY
 INFORMATION WAS INCLUDED IN MSP1.I WAS UNABLE TO
 LOCATE OCCUPANT LOAD, SEE FBC 1004.1.2, TABLE
 1004.1.2.
  
 34.)ADDRESSED.
  
 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN
 PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE
 CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON
 PLAN.
  
 PLEASE INCORPORATE INFORMATION INTO THE PLAN AS
 REQUESTED.THIRD REQUEST. THE RESPONSE LETTER STATES
 THAT THIS INFORMATION IS INCLUDED ON MSP1, BUT I WAS
 UNABLE TO FIND THE CLASSIFICATION OF OPEN OR ENCLOSED.
  
 34-36.) ADDRESSED.
  
 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN
 WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS
 TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM
 NORMALLY OCCUPIED SPACES.
  
 YOUR OBJECTION TO THE COMMENT IS NOTED.PLEASE SEE
 ATTACHED COMMENTARY, INCLUDING THE SENTENCE WHICH
 SPECIFICALLY EXCLUDES STORAGE CLOSETS AS THEY DO NOT
 CONSIDER THIS A "NORMALLY OCCUPIED SPACE" REGARDLESS OF
 BUILDING OCCUPANCY CLASSIFICATION.ALSO NOTE THAT
 ALTHOUGH YOU ARE PROPOSING ENCLOSED SPACE ON THE ROOF,
 A FIRE SPRINKLER PLAN WAS NOT PROVIDED FOR THE ROOF.
  
 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM
 THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS
 REQUIRED.GG-A108.
  
 YOUR RESPONSE STATES THAT VERTICAL OPENINGS ARE NOT
 REQUIRED TO BE PROTECTED.I WAS REFERRING TO THE FLOOR
 CEILING ASSEMBLY BETWEEN THE FIRE EXIT 1ST FLOOR, S1
 OCCUPANCY, AND THE RAMP/PARKING GARAGE, S2 ON THE
 SECOND FLOOR.A 2 HOUR IS SHOWN THROUGHOUT THE
 REMAINDER OF THE BUILDING ON SECTION G-G AND APPEARS TO
 ALSO BE SHOWN ON A-A-106.THIS ALSO APPLIES TO MENS
 ROOM F-F A108.
  
 39.)ADDRESSED.
  
 40.)PLEASE PROVIDE OCCUPANT LOAD AS PREVIOUSLY
 REQUESTED FOR THE LOUNGE/TRAINING AREA SO THAT EGRESS
 REQUIREMENTS AND COMPLIANCE CAN BE DETERMINED.
  
 41-51.) ADDRESSED.
  
 52.)PLEASE SUBMIT ALL PRODUCT APPROVALS REQUIRED AT
 THIS TIME.DOOR PRODUCT APPROVALS WERE NOT SUBMITTED.
 PROVIDE WIND DESIGN CRITERIA FBC1603.1.4 INCLUDING
 COMPONENTS AND CLADDING DESIGN PRESSURES.
  
 53.)THE SIGNATURE FOR AN ENGINEER CANNOT BE A STAMP
 (STRUCTURAL ENGINEER), SEE FAC61G15-23.002, FS471.025.
  
 54.)PLEASE CLOUD ALL CHANGES AND SUBMIT OLD SHEETS.
 PLEASE INCLUDE A RESPONSE LETTER INDICATING HOW EACH
 ITEM HAS BEEN ADDRESSED.
  
 NEW COMMENTS:
  
 55.)FLORIDA STATE PRODUCT APPROVAL COVER SHEET,
 FL5723, WAS SUBMITTED FOR SHUTTERS.USE OF REMOVABLE
 SHUTTERS ON COMMERCIAL BUILDINGS IS TO BE APPROVED BY
 THE BUILDING OFFICIAL, SEE ATTACHED POLICY, ITEM 13.
 SUBMIT AN INSTALLATION PLAN WITH ALL REQUIRED
 INFORMATION (SEE POLICY).THIS MAY BE DONE PRIOR TO
 RESUBMITTAL VIA EMAIL.ONCE A PRELIMINARY INSTALLATION
 PLAN IS APPROVED BY THE BUILDING OFFICIAL, ORIGINALS
 WILL BE REQUIRED.
  
 56.)IF YOU ARE USING SHUTTERS, AN INSTALLATION
 SCHEDULE IS REQUIRED ALONG WITH A KEY PLAN SHOWING
 INSTALLATION LOCATIONS; SEE ATTACHED.ALSO PRINT THE
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS.IT IS
 NOT CLEAR WHY SHUTTERS WERE INCLUDED IN THE PACKAGE
 (NOT CLEAR WHERE THEY WILL BE INSTALLED).
  
 57.)OLD SHEETS WERE LEFT IN THE PACKAGE.PLEASE MARK
 THESE SHEETS VOID, REMOVE FROM THE SETS, AND SUBMIT
 SEPARATELY FOR REFERENCE.
  
 58.)S2 SHOWS EXISTING FOOTERS AND FOOTERS WHICH
 APPEAR TO ENCROACH THE ASSUMED PROPERTY LINE AND THE
 EXISTING HUMMER BUILDING, 1'6" AWAY.PLEASE CLARIFY.