2007-06-22 13:55:13 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| PERMIT PICKUP, FS713.13. |
| |
| 2.)ADDRESSED. |
| |
| 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| 561-233-5025 FOR MORE INFORMATION. |
| |
| 4-5.) ADDRESSED. |
| |
| 6.)THE INFORMATION REQUIRED FOR THE ENGINEER |
| FAC61G15-23.002 IS TO BE ON EACH SHEET.THIS COMMENT |
| IS FOR THE FIRE SPRINKLER ENGINEER.THIS APPLIES TO |
| THE CALCS AND THE DRAWINGS.IF AN INDEX SHEET IS NOT |
| PROVIDED FOR THE CALCS, EACH SHEET IS TO BE SIGNED, |
| SEALED, AND DATED. |
| |
| 7.) FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| ONE OR MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQFT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| OF CONSTRUCTION |
| |
| ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| SERVICES MANAGER - TEL: |
| 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT |
| INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. |
| |
| 3RD REVIEW ? ONLY TWO SETS WERE SUBMITTED.NOTE THAT |
| ALTHOUGH THIS PLAN HAS PASSED SOME REVIEWS, ANOTHER |
| REVIEW WILL BE REQUIRED SO THAT THOSE REVIEWERS CAN |
| STAMP THEIR SHEETS WHEN THE THIRD SET IS SUBMITTED. |
| |
| 8.) PROVIDE ORIGINAL SIGNED, SEALED, DATED SOILS |
| REPORTS, FBC1802.2.1, 1802.2.3.THREE SETS REQUIRED. |
| AS STATED IN THE PREVIOUS REVIEWS, THE SIGNATURE CANNOT |
| BE A PHOTOCOPY. |
| |
| 9.) ADDRESSED. |
| |
| 10.)ADDRESSED, BUT SEE OTHER COMMENTS REGARDING |
| PRODUCT APPROVALS. |
| |
| 11.)ADDRESSED. |
| |
| 12.)IT IS NOT CLEAR IF THE EQUIPMENT SHEDS WERE |
| INCLUDED IN THE BUILDING CODE SUMMARY.THIS IS THE |
| THIRD REQUEST FOR THIS INFORMATION.IS THIS AREA |
| INCLUDED IN ONE OF THE OTHER EXISTING BUILDINGS?THE |
| PLAN SHOWS THE EXISTING EQUIPMENT SHED AGAINST THIS |
| BUILDING.ARE YOU DESIGNING AS ONE BUILDING OR TWO |
| SEPARATE BUILDINGS? |
| |
| 13-17.) ADDRESSED. |
| |
| 18.)REGARDING MAXIMUM AREA OF EXTERIOR WALL OPENINGS, |
| OPENINGS AND PERCENTAGES WERE PROVIDED FOR THE EXISTING |
| BUILDINGS.PROVIDE ALSO FOR THE PROPOSED BUILDING TO |
| SHOW COMPLIANCE WITH FBC TABLE 704.8.NOTE THAT EAST |
| ELEVATION HAS A LARGE AMOUNT OF OPENINGS ON A PORTION |
| OF THE WALL.SEE THE ATTACHED COMMENTARY IN REGARDS TO |
| UNIFORM DISTRIBUTION. |
| |
| THE % OF WALL OPENINGS, EXISTING VW SERVICE TO NEW |
| SERVICE, SHOULD BE 15%-45%. |
| |
| EQUIPMENT SHEDS ARE SHOWN.ARE THEY ALSO TYPE II B |
| CONSTRUCTION?ONE IS SHOWN CONNECTED TO THE NEW |
| SERVICE BUILDING, BUT NOT DETAILS ARE PROVIDED.IS |
| THIS AN EXISTING BUILDING?COMPLIANCE WITH FBC TABLE |
| 601, FBC TABLE 704.8 IS TO BE SHOWN ON THE PLAN. |
| |
| 19.)ADDRESSED. |
| |
| 20.)MSP1 STATES THAT EXISTING HUMMER BUILDING HAS A 2 |
| HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE |
| FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH |
| THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER |
| CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE |
| EXISTING WALL.SEE FBC TABLE 602.IT IS ACCEPTABLE TO |
| EXCEED CODE COMPLIANCE, BUT B OCCUPANCY REQUIREMENT IS |
| 1 HOUR.THE NEW SERVICE HAS A 2 HOUR REQUIREMENT. |
| |
| MSP1 STATES THAT THE EXISTING SERVICE BUILDING HAS A 2 |
| HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE |
| FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH |
| THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER |
| CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE |
| EXISTING WALL. |
| |
| PLEASE NOTE REQUIREMENTS FOR NEW SERVICE BUILDING. NOTE |
| ON MSP1 AND SHOW REQUIREMENTS ON THE PLAN.MSP1 SHOWS |
| 2 HOUR ON THE WALL ADJACENT TO THE HUMMER SHOWROOM, BUT |
| DOES NOT SHOW THE 2 HOUR REQUIREMENT FOR THE STORAGE |
| AND OIL STORAGE AREAS. |
| |
| 21.)ADDRESSED. |
| |
| 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND |
| EXISTING VW SERVICE/VW SHOWROOM?THIS WAS DISCUSSED IN |
| A MEETING AS BEING A CANOPY. PLEASE LABEL THIS AREA. |
| |
| 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A2-03, |
| A303, SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED |
| DOORS IN A SERIES. |
| |
| THIS WAS ADDRESSED ON MOST PAGES.PLEASE ALSO REVISE |
| THE ELECTRICAL SHEETS AND CHECK ALL SHEETS. |
| |
| 24-27.) ADDRESSED. |
| |
| 28.)RESPONSE LETTER STATES THAT ALL LIFE SAFETY |
| INFORMATION WAS INCLUDED IN MSP1.I WAS UNABLE TO |
| LOCATE OCCUPANT LOAD, SEE FBC 1004.1.2, TABLE |
| 1004.1.2. |
| |
| 34.)ADDRESSED. |
| |
| 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN |
| PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE |
| CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON |
| PLAN. |
| |
| PLEASE INCORPORATE INFORMATION INTO THE PLAN AS |
| REQUESTED.THIRD REQUEST. THE RESPONSE LETTER STATES |
| THAT THIS INFORMATION IS INCLUDED ON MSP1, BUT I WAS |
| UNABLE TO FIND THE CLASSIFICATION OF OPEN OR ENCLOSED. |
| |
| 34-36.) ADDRESSED. |
| |
| 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN |
| WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS |
| TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM |
| NORMALLY OCCUPIED SPACES. |
| |
| YOUR OBJECTION TO THE COMMENT IS NOTED.PLEASE SEE |
| ATTACHED COMMENTARY, INCLUDING THE SENTENCE WHICH |
| SPECIFICALLY EXCLUDES STORAGE CLOSETS AS THEY DO NOT |
| CONSIDER THIS A "NORMALLY OCCUPIED SPACE" REGARDLESS OF |
| BUILDING OCCUPANCY CLASSIFICATION.ALSO NOTE THAT |
| ALTHOUGH YOU ARE PROPOSING ENCLOSED SPACE ON THE ROOF, |
| A FIRE SPRINKLER PLAN WAS NOT PROVIDED FOR THE ROOF. |
| |
| 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM |
| THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS |
| REQUIRED.GG-A108. |
| |
| YOUR RESPONSE STATES THAT VERTICAL OPENINGS ARE NOT |
| REQUIRED TO BE PROTECTED.I WAS REFERRING TO THE FLOOR |
| CEILING ASSEMBLY BETWEEN THE FIRE EXIT 1ST FLOOR, S1 |
| OCCUPANCY, AND THE RAMP/PARKING GARAGE, S2 ON THE |
| SECOND FLOOR.A 2 HOUR IS SHOWN THROUGHOUT THE |
| REMAINDER OF THE BUILDING ON SECTION G-G AND APPEARS TO |
| ALSO BE SHOWN ON A-A-106.THIS ALSO APPLIES TO MENS |
| ROOM F-F A108. |
| |
| 39.)ADDRESSED. |
| |
| 40.)PLEASE PROVIDE OCCUPANT LOAD AS PREVIOUSLY |
| REQUESTED FOR THE LOUNGE/TRAINING AREA SO THAT EGRESS |
| REQUIREMENTS AND COMPLIANCE CAN BE DETERMINED. |
| |
| 41-51.) ADDRESSED. |
| |
| 52.)PLEASE SUBMIT ALL PRODUCT APPROVALS REQUIRED AT |
| THIS TIME.DOOR PRODUCT APPROVALS WERE NOT SUBMITTED. |
| PROVIDE WIND DESIGN CRITERIA FBC1603.1.4 INCLUDING |
| COMPONENTS AND CLADDING DESIGN PRESSURES. |
| |
| 53.)THE SIGNATURE FOR AN ENGINEER CANNOT BE A STAMP |
| (STRUCTURAL ENGINEER), SEE FAC61G15-23.002, FS471.025. |
| |
| 54.)PLEASE CLOUD ALL CHANGES AND SUBMIT OLD SHEETS. |
| PLEASE INCLUDE A RESPONSE LETTER INDICATING HOW EACH |
| ITEM HAS BEEN ADDRESSED. |
| |
| NEW COMMENTS: |
| |
| 55.)FLORIDA STATE PRODUCT APPROVAL COVER SHEET, |
| FL5723, WAS SUBMITTED FOR SHUTTERS.USE OF REMOVABLE |
| SHUTTERS ON COMMERCIAL BUILDINGS IS TO BE APPROVED BY |
| THE BUILDING OFFICIAL, SEE ATTACHED POLICY, ITEM 13. |
| SUBMIT AN INSTALLATION PLAN WITH ALL REQUIRED |
| INFORMATION (SEE POLICY).THIS MAY BE DONE PRIOR TO |
| RESUBMITTAL VIA EMAIL.ONCE A PRELIMINARY INSTALLATION |
| PLAN IS APPROVED BY THE BUILDING OFFICIAL, ORIGINALS |
| WILL BE REQUIRED. |
| |
| 56.)IF YOU ARE USING SHUTTERS, AN INSTALLATION |
| SCHEDULE IS REQUIRED ALONG WITH A KEY PLAN SHOWING |
| INSTALLATION LOCATIONS; SEE ATTACHED.ALSO PRINT THE |
| EVALUATION REPORT AND INSTALLATION INSTRUCTIONS.IT IS |
| NOT CLEAR WHY SHUTTERS WERE INCLUDED IN THE PACKAGE |
| (NOT CLEAR WHERE THEY WILL BE INSTALLED). |
| |
| 57.)OLD SHEETS WERE LEFT IN THE PACKAGE.PLEASE MARK |
| THESE SHEETS VOID, REMOVE FROM THE SETS, AND SUBMIT |
| SEPARATELY FOR REFERENCE. |
| |
| 58.)S2 SHOWS EXISTING FOOTERS AND FOOTERS WHICH |
| APPEAR TO ENCROACH THE ASSUMED PROPERTY LINE AND THE |
| EXISTING HUMMER BUILDING, 1'6" AWAY.PLEASE CLARIFY. |