2007-02-12 14:39:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE IMPRESSION SEAL SHALL
 IMPRESS INFORMATION REQUIRED BY FAC 61G1-16.002(1) & FS
 481.2055 ON EACH SHEET.
 *****RESPONSE NOTED, BUT ALL REQUIRED INFORMATION SHALL
 BE IMPRESSED ON EACH SHEET, AND THE INFORMATION SHALL
 BE LEGLBLE. NOT ALL INFORMATION IS LEGIBLE.
  
 2. OK
  
 3. SHT A-104 INDICATE THE SQUARE FOOTAGE AND OCCUPANCY
 OF THE SERVICE AREA, OIL STORAGE ARE, AND BUSINESS
 AREAS. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES FOR
 EACH OCCUPANCY PER TABLES 1004.1.2 & 403.1. SEPARATE
 FACILITIES ARE REQUIRED FOR EACH SEX PER SECTION 403.2.
 ONLY MEN'S FACILITIES ARE SHOWN.
 ****RESPONSE NOTED, BUT THE INFORMATION IS NOT LOCATED
 ON SHT A-104. ALSO RESPONSE "ALSO PLEASE SEE RESPONSES
 TO BUILDING PLAN REVIEW" IS NOT TOO CLEAR AS BUILDING
 HAS 51 COMMENTS. PLEASE INDICATE WHICH COMMENT WILL
 RESPOND TO MY COMMENT. THIS WILL HELP EXPEDITE THE PLAN
 REVIEW PROCESS. IT APPEARS THAT THERE ARE SOME AREAS
 THAT ARE NOT STORAGE. THE PARTS WARRANTY AREA, AND THE
 LOUNGE/TRAINING AREA.--SECTION 403.3 STATES THAT
 THE REQUIRED WATER CLOSETS, LAVS, SHALL BE DISTRIBUTED
 EQUALLY BETWEEN THE SEXES.THE OCCUPANT LOAD SHALL BE
 COMPOSED OF 50 PERCENT OF EACH SEX, UNLESS STATISTICAL
 DATA APPROVED BY THE CODE OFFICIAL INDICATE A DIFFERENT
 DISTRIBUTION OF THE SEXES.
  
 4. SHT A-200 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 W/C'S
 A. OK
 B. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT DETAILS 18 & 31 SHOW THE FLUSH
 CONTROL ON THE WALL SIDE.
 FOR TOILET STALL
 A. OK
 FOR THE URINAL
 A. OK
 FOR LAVS
 A. 11-4.19.2 CLEARANCES
 ****NOT ADDRESSED
 B. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED
  
 5. SHT A-201 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 KIT. SINK
 A. 11-4.24.5 CLEAR FLOOR SINK (FORWARD APPROACH
 REQUIRED)
 ****NOT ADDRESSED
 B. OK
  
 5. OK
  
 6. SHT P-100 BECAUSE OF THE AUTOMOBILE SERVICE WORK AN
 OIL/GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER FOR A
 DETERMINATION. CONTACT HER AT (561) 822-2271, OR BY FAX
 (561) 822-2279, OR BY E-MAIL [email protected]. WASTE
 ORD. 3434.
 ****WAITING FOR WORD FROM ENVIRONMENTAL COMPLIANCE AS
 THEY WILL HAVE TO ISSUE THE RESULTS OF THE REQUIREMENT.
 THERE ARE STILL SERVICE SINKS AND IT WILL BE THEIR
 DETERMINATION.
  
 7. SHT P-101 SUBMIT MANUF. SPECIFICATION SHEETS FOR THE
 INSTANT-FLOW WATER HEATER FOR THE KITCHEN SINK. SPECS.
 SHALL SHOW A LISTING FOR THE W/H. SECTIONS 106.1.2 &
 303.4.
 ****RESPONSE NOTED, BUT MANUF. SPECIFICATION SHEETS
 WERE NOT LOCATED.
  
 8. SHT P-200 SHOW THE CLEANOUTS AS REQUIRED IN SECTION
 1101.8 FOR THE STORM RISERS.
 ****RESPONSE NOTED, BUT THE CLEANOUTS FOR SECTIONS
 708.3.1, 708.3.2, 708.3.3, & 708.3.4 WERE NOT SHOWN ON
 THE FLOOR PLAN, NOR ON THE RISER DIAGRAMS.
  
 9.OK
 10. OK
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE BUILDING. SECTION 608.13.2.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED ON
 EACH BUILDING. PLEASE INDICATE A BACKFLOW PRIOR TO THE
 WATER SERVICE ENTERING THE BUILDING TO SHOW
 COMPLIANCE.
  
 12. SHT P-200 WATER RISER DIAGRAM. FULL OPEN VALVES
 REQUIRED ON EACH WATER DOWN-FEED PIPE. SECTION
 606.1(4).
 ****RESPONSE NOTED, BUT THE VALVES ARE NOT SHOWN AT
 FIXTURES P1, P2, P3, P4, P4, P6 & P9.
  
 13. OK
 14. OK
 15. OK
 16. OK
  
 ************NEW COMMENT*************
  
 1B. SHTS A-200 & A-201 ARE OUT OF SEQUENCE IN ONE SET
 OF PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]