2007-02-14 15:42:53COMMENTS LIST BELOW IN RELATION TO PREVIOUS PLAN REVIEW
 COMMENTS AS WELL AS RESPONSES.
  
 1. OK
  
 2. AIR FROM SERVICE GARAGE MAY NOT BE USED FOR
 VENTILLATION OF MEN'S LOCKER ROOM PER FBC,M 403.2.1(3).
 VENTILLATION SHOULD COME DIRECTLY FROM THE OUTDOORS.
  
 3. FBC,M 804.3.5 APPLIES TO CHIMNEYS AND VENTS FOR
 SOLID FUEL BURNING APPLIANCES AND DOS NOT APPLY IN THIS
 CIRCUMSTANCE. A MINIMUM OF 10' BETWEEN GARAGE EXHAUST
 FANS AND INTAKE OPENINGS IS REQUIRED PER FBC,M
 401.5.1.
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. SEE COMMENT #3
  
  