Plan Review Notes For Permit 06090410 |
Permit Number |
06090410 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-02-14 15:42:53 | COMMENTS LIST BELOW IN RELATION TO PREVIOUS PLAN REVIEW | | COMMENTS AS WELL AS RESPONSES. | | | | 1. OK | | | | 2. AIR FROM SERVICE GARAGE MAY NOT BE USED FOR | | VENTILLATION OF MEN'S LOCKER ROOM PER FBC,M 403.2.1(3). | | VENTILLATION SHOULD COME DIRECTLY FROM THE OUTDOORS. | | | | 3. FBC,M 804.3.5 APPLIES TO CHIMNEYS AND VENTS FOR | | SOLID FUEL BURNING APPLIANCES AND DOS NOT APPLY IN THIS | | CIRCUMSTANCE. A MINIMUM OF 10' BETWEEN GARAGE EXHAUST | | FANS AND INTAKE OPENINGS IS REQUIRED PER FBC,M | | 401.5.1. | | | | 4. OK | | | | 5. OK | | | | 6. OK | | | | 7. SEE COMMENT #3 | | | | | | PLAN REVIEW BY: | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|