2007-02-23 10:18:31 | *****UNSAT***** |
| |
| |
| THE FOLLOWING COMMENTS TAKEN FROM PREVIOUS FIRE PLAN |
| REVIEW OF 10/25/2006 STILL NEED TO BE ADDRESSED: |
| |
| |
| 01.INDICATE THE TYPES OF AUTOMOTIVE REPAIRS THAT ARE |
| PLANNED FOR THE BUILDING.PLEASE BE SPECIFIC |
| |
| 02.SPRINKLER PLANS WERE SUBMITTED, HOWEVER, SEE |
| ELECTRICAL PLAN REVIEW NOTE #22 IN REFERENCE TO THE |
| SIGNING AND SEALING OF DOCUMENTS. |
| |
| 03.ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS |
| EXIST.EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS |
| EVEN WHEN THEY ARE NOT CLEARY OBVIOUS. ADD EXTRA EXIT |
| SIGN LIGHTIN PARKING AREA DIRECTING PERSONS TO THE |
| NEAREST EXIT. |
| |
| 04.NO EMERGENCY SIGN LIGHTING DECLARED ON PAGE E-103. |
| PLEASE INDICATE LOCATION OF THESE DEVICES |
| |
| 06.PLEASE PROVIDE PRODUCT APPROVALS FOR THE CO |
| DETECTORS PLANNED FOR USE. |
| |
| 09.BUILDING ADDRESS WITH A MININIMUM OF 6" IN HEIGHT |
| AND 1" IN WIDTH REQUIRED.PLEASE DISPLAY/SHOW ON THE |
| APPROPIATE EXTERIOR ELEVATION |
| |
| 12.NO PORTABLE FIRE EXTINGUISHERS PROVIDED.SHOW THE |
| LOCATION OF THE FIRE EXTINGUISHERS WHICH SATISFY THE |
| 75' TRAVEL DISTANCE |
| |
| 13.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS |
| FOR ALL HANDRAILS, GUARDRAILS, AND CABLE RAIL SYSTEMS. |
| INDICATE THE LOCATION OF THIS INFORMATION ON THE |
| SPECIFIC STRUCTURAL SHEET(S) |
| |
| 15.CONSTRUCTION, DEMOLITION, AND RENOVATION |
| OPERATIONS SHALL COMPLY WITH NFPA 241.INDICATE ON |
| APPROPIATE PLAN SHEET |
| |
| 16.DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| INDICATE ON THE APPROPIATE PLAN SHEET |
| |
| 17.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. |
| INDICATE ITS LOCATION ON THE APPROPIATE EXTERIOR |
| ELEVATION |
| |
| 19.PLEASE DECLARE DISTANCE FROM EXHAUST TERMINATION |
| POINTS TO ANY BUILDING OPENINGS.SHOW THE DISTANCE OF |
| EXHAUST FUMES BEING EMITTED TO THE NEAREST WINDOWS, |
| DOORS, AIR INTAKES, OR SIMILAR OPENINGS |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT |
| WAS ADDRESSED |
| |
| |