Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-14 16:26:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)PROVIDE A SURVEY FOR THIS PROPERTY, FBC*106.3.4,
 SHOWING PROPERTY LINE AND ALL EXISTING IMPROVEMENTS.
 THE RESPONSE LETTER STATES THAT A SURVEY HAS BEEN
 INCLUDED BUT IT WAS NOT IN THE PACKAGE.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4.)RADON FEES DUE, FS*553.721.SEE ATTACHED.THIS
 FEE MUST BE PAID WHEN THE PLANS ARE PICKED UP.
  
 5.)DUE TO VALUATION ADJUSTMENT, FEES HAVE BEEN
 INCREASED.SEE ATTACHED.PLEASE PAY AT THE TIME THAT
 THE PLANS ARE PICKED UP.
  
 6.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 THE FIRE SPRINKLER PLANS WERE IN THE PACKAGE, BUT THE
 INFORMATION REQUIRED FOR THE ENGINEER FAC61G15-23.002
 IS NOT ON EACH SHEET, AND THE SEAL IS ILLEGIBLE.
  
 7.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 8.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.1,
 1802.2.3.THREE SETS REQUIRED.
  
 THE SIGNATURE FOR AN ENGINEER CANNOT BE A PHOTOCOPY,
 SEE FAC61G15-23.002, FS471.025.
  
 9.)THE SEAL IS ILLEGIBLE (ARCHITECT).PLEASE
 ADDRESS, FS481.221.
  
 RESPONSE LETTER STATES THAT THIS HAS BEEN ADDRESSED,
 BUT I STILL CANNOT READ THE SEAL.
  
 10.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 THE RESPONSE LETTER STATES THAT THE PRODUCT APPROVALS
 HAVE BEEN REVIEWED BY DESIGNER OF RECORD.ONLY ONE
 FLORIDA STATE PRODUCT APPROVAL WAS SUBMITTED AND AN NOA
 FOR LOUVERS, WITHOUT THE REQUIRED DOCUMENTATION
 (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) TO SHOW
 CODE COMPLIANCE AND FOR INSPECTIONS.THE PRODUCT
 APPROVALS DID NOT HAVE A SHOP DRAWING REVIEW STAMP.
 APPROVAL IS TO BE IN THE FORM OF A REVIEW STAMP OR A
 COVER LETTER SPECIFICALLY REFERRING TO EACH PRODUCT
 APPROVAL IN THE PACKAGE.STATING ?PRODUCT APPROVALS
 HAVE BEEN REVIEWED BY DESIGNER OF RECORD? (A STATEMENT
 IN A TYPED RESPONSE LETTER WHICH IS NOT SIGNED AND
 GIVES NO INDICATION WHATSOEVER AS TO WHO PREPARED THE
 DOCUMENT; NO LETTERHEAD, NAME, SIGNATURE) DOES NOT SHOW
 CODE COMPLIANCE; IT DOESN?T STATE WHICH DESIGN
 PROFESSIONAL REVIEWED THE PRODUCT APPROVALS NOR WHICH
 PRODUCT APPROVALS WERE REVIEWED, AND NOTHING SIGNED BY
 THE DESIGNER WHO REVIEWED THE PRODUCT APPROVALS.
  
 11.)INCLUDE FBC EB IN GOVERNING CODE.THIS PROPOSED
 IMPROVEMENT IS TO COMPLY WITH FBC EB CHAPTER 9; SEE
 ALSO FBC EB 901.2.SOME COMMENTS AND REQUEST FOR
 ADDITIONAL INFORMATION RELATE TO THIS CODE SECTION.
  
 12.)INCLUDE A CODE SUMMARY. DECLARE BUILDING TYPE
 FBC6 (INCLUDE A OR B), BUILDING HEIGHT AND AREA FBC5,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY,
 FIRE SPRINKLER INFORMATION.NOTE THAT CANOPIES AND
 EQUIPMENT SHEDS ARE TO BE INCLUDED, SEE FBC 502,
 DEFINITION OF AREA, BUILDING.BUILDING TYPE WILL BE
 BASED ON WORST CASE UNLESS A FIRE WALL SEPARATES THE
 BUILDING AREAS.DETAILS OF EXISTING CONDITIONS SHOWING
 FIRE RESISTANCE MAY BE REQUIRED.PLEASE CONTACT ME IF
 YOU ARE UNSURE OF WHICH DETAILS TO INCLUDE.
  
 THIS INFORMATION IS TO BE ON THE PLAN, NOT IN THE
 RESPONSE LETTER.NOTE THAT THE RESPONSE LETTER IS NOT
 ON LETTERHEAD, AND DOES NOT INDICATE WHO PREPARED IT,
 AND IS UNSIGNED.PLANS ARE TO SHOW CODE COMPLIANCE,
 BUT IF LETTERS ARE ACCEPTED AS A SUPPLEMENT TO THE PLAN
 AT OTHER TIMES, THEY ARE TO MEET THE SAME REQUIREMENTS
 AS ANY DOCUMENT PREPARED BY AN ARCHITECT OR ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD.
  
  
 A 2 HOUR WALL WAS ADDED ON THE PROPOSED SERVICE
 BUILDING ADJACENT TO THE HUMMER SHOWROOM.IT IS NOT
 CLEAR WHAT DESIGN INTENT IS AS THIS DOES NOT COMPLY
 WITH FBC 705, OPENINGS IN COMPLIANCE WITH FBC705.8.IF
 YOU ARE USING AN ASSUMED PROPERTY LINE BETWEEN
 BUILDINGS, INFORMATION REGARDING THE HUMMER SHOWROOM
 AND THE VW CANOPY BUILDING IS REQUIRED TO DETERMINE
 COMPLIANCE WITH FBC TABLE 503, FBC TABLE 601, FBC TABLE
 620, NO OPENINGS ALLOWED. THE SITE PLAN STILL SHOWS
 THIS AS ONE BUILDING.SHEET A102 SHOWS THE EQUIPMENT
 ADJACENT TO THE PROPOSED SERVICE BUILDING (ATTACHED),
  
 THIS LIST MAY NOT BE COMPLETE AS DESIGN INTENT IS NOT
 CLEAR.IT APPEARS THAT THIS IS TO BE SEPARATE
 BUILDINGS, BUT OPENINGS ARE SHOWN WITH NO INFORMATION
 REGARDING THE EXISTING BUILDINGS WAS PROVIDED.IF THE
 PROPOSED BUILDING IS TO BE SEPARATED FROM THE EXISTING
 BUILDINGS WITH A FIRE WALL, SEE FBC705 AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 13.)REGARDING OCCUPANCY CLASSIFICATIONS, PLEASE SEE
 FBC304, FBC311.2, FBC311.3.OTHER CODE SECTIONS MAY
 APPLY.
  
 SEE ITEM 12 ABOVE.ALL REQUIRED INFORMATION IS TO BE
 ON THE PLAN.THE LETTER STATES THAT THIS IS S1 AND S2,
 BUT IT SHOWS A VEHICLE SHOWROOM, FBC304.INFORMATION
 IN REGARDS TO THE ADJACENT BUILDINGS MUST BE PROVIDED
 TO DETERMINE CODE COMPLIANCE.
  
 14.)WHAT HAZARDOUS MATERIALS WILL BE STORED AND IN
 WHAT QUANTITIES?SEE FBC TABLE 307.7(1), FBC 406.6.
  
 ADDRESS THIS IN THE PLAN.PROVIDE MSDS FOR THE
 HAZARDOUS MATERIALS.
  
 15.)DECLARE AN OCCUPANCY CLASSIFICATION FOR THE OIL
 STORAGE, SEE FBC TABLE 307.7(1), FBC406.6.NOTE
 QUANTITIES.
  
 THIS IS TO BE DONE ON THE PLAN; DECLARE OCCUPANCY
 CLASSIFICATION AND QUANTITIES.THE RESPONSE LETTER
 STATES THAT THIS IS S1, PLEASE STATE QUANTITY OF
 MAXIMUM HAZARDOUS MATERIALS STORED ON THE PLAN.
  
 16.)SHOW HOW COMPLIANCE WITH FBC TABLE 503 HAS BEEN
 ACCOMPLISHED; SEE ALSO FBC 302.IF HEIGHT OR AREA
 MODIFICATIONS HAVE BEEN USED AS PER FBC 503 THROUGH
 508, PUT ALL INFORMATION AND CALCULATIONS ON THE PLAN.
 INFORMATION PROVIDED SHOULD BE CLEAR IN REGARDS TO
 BUILDING TYPE, BUILDING AREA, AND OCCUPANCY
 CLASSIFICATION IN REGARDS TO THE EXISTING BUILDINGS
 (INCLUDING AREAS REFERRED TO AS "CANOPY" AND
 "EQUIP.SHED", ETC.) AS WELL AS THE NEW IMPROVEMENT.
  
 THIS IS TO BE DONE ON THE PLAN.SEE OTHER COMMENTS;
 CODE COMPLIANCE CANNOT BE DETERMINED.
  
 17.)IT IS NOT CLEAR WHETHER THE EXISTING SERVICE
 SHOWN ON THE WEST SIDE MSP-1 WILL BE A PART OF THE NEW
 BUILDING (APPEARS TO BE ATTACHED AT THE NORTHWEST
 PORTION, THE REST OF THE EXISTING SERVICE IS ALONG THE
 RAMP) OR IF IT A SEPARATE BUILDING, TO BE SEPARATED
 WITH AN ASSUMED PROPERTY LINE.IF THIS IS A SEPARATE
 BUILDING, SHOW COMPLIANCE WITH FBC TABLE 602 BY SHOWING
 THE BUILDING TYPE AND OCCUPANCY, ASSUMED PROPERTY LINE,
 DISTANCE OF EACH BUILDING FROM THE ASSUMED PROPERTY
 LINE.COMPLIANCE FOR EACH BUILDING MUST BE SHOWN,
 INCLUDING FIRE RESISTANCE RATING FOR THE EXISTING
 BUILDING.
  
 IF THIS IS NOT A SEPARATE BUILDING, INCLUDE THIS
 BUILDING IN THE CODE SUMMARY, SEE ITEM 3.
  
 NOT ADDRESSED.THE RESPONSE LETTER STATES THAT THIS IS
 A SEPARATE BUILDING, BUT NO INFORMATION WAS PROVIDED AS
 REQUESTED.
  
 18.)SEPARATIONS ARE TO COMPLY WITH FBC TABLE 302.3.2.
 AS NO FIRE SPRINKLER INFORMATION OR FBC TABLE 503
 COMPLIANCE WAS PROVIDED, IT IS NOT CLEAR IF THE 2 HOUR
 SHOWN BETWEEN B AND S1 IS CORRECT.
  
 INCLUDE SPRINKLER INFORMATION IN A CODE SUMMARY.THE
 RESPONSE LETTER AND PLAN SHOWS THAT THE PROPOSED GARAGE
 WILL BE SPRINKLERED.ARE THE OTHER BUILDINGS FULLY
 SPRINKLERED, INCLUDING THE CANOPY AREA, EQUIPMENT SHED,
 ETC.?IF THIS IS TWO BUILDING SEPARATED AS PER FBC
 TABLE 602, BOTH BUILDINGS MUST COMPLY AND NO OPENINGS
 ALLOWED FBC TABLE 704.8.
  
 19.)NO HORIZONTAL SEPARATIONS WERE SHOWN.
  
 PLEASE SHOW ALL REQUIRED SEPARATIONS; BETWEEN S1 AND
 THE PARKING GARAGE FBC406.2.7.PROVIDE DETAILS.
  
 20.)PROVIDE DISTANCE OF ADJACENT BUILDINGS TO THE
 PROPOSED RENOVATED BUILDING.FOR INSTANCE, DISTANCE
 FROM USED CARS TO HUMMER SHOWROOM, USED CARS TO
 EXISTING SERVICE.CONNECTING MULTIPLE BUILDINGS MAY
 AFFECT BUILDING TYPE FBC5, WHICH MAY AFFECT CODE
 COMPLIANCE WITH FBC TABLE 602.PROVIDE INFORMATION IN
 REGARDS TO OCCUPANCY CLASSIFICATION AND BUILDING TYPE
 FOR OTHER STRUCTURES.
  
 SEE OTHER COMMENTS.DESIGN INTENT IS NOT CLEAR. THE
 RESPONSE LETTER STATES THAT THE PROPOSED BUILDING IS A
 SEPARATE STRUCTURE, BUT IT SHOWS OPENINGS WHICH ARE NOT
 ALLOWED FBC TABLE 704.8 AND NO INFORMATION PROVIDED IN
 REGARDS TO THE OTHER BUILDINGS.
  
 21.)MSP-1, BUILDING/LOT COVERAGE ZONING INFORMATION
 REFERS TO AN EXISTING LEVITZ BUILDING BUT THAT BUILDING
 IS NOT REFERENCED ON THE SITE PLAN.
  
 THE RESPONSE LETTER REQUESTS THAT I SPEAK WITH
 PLANNING.THE PLANS ARE TO SHOW CODE COMPLIANCE.
 PLEASE PROVIDE INFORMATION REGARDING THE BUILDINGS ON
 THE SITE AS REQUESTED IN OTHER COMMENTS.THE CODE
 SUMMARY PROVIDED IS TO CORRELATE WITH THE BUILDING
 NAMES ON THE SITE PLAN.FOR INSTANCE, THE SITE PLAN
 STATES THAT EXISTING LEVITZ BUILDING IS 62,399 SQUARE
 FEET, BUT THERE IS NOTHING LABELED LEVITZ BUILDING ON
 THE PLAN.
  
 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND
 EXISTING VW SERVICE/VW SHOWROOM?
  
 THE RESPONSE LETTER STATES THAT THERE ARE EXISTING
 CANOPIES.THIS AREA IS CONSIDERED TO BE BUILDING AREA.
 SEE OTHER COMMENTS REGARDING BUILDING SEPARATION AND
 OPENINGS.SEE OTHER COMMENTS REGARDING WHETHER OR NOT
 THIS IS CONSIDERED ONE BUILDING OR SEPARATE BUILDINGS
 AS THE PLANS ARE NOT CLEAR.
  
 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A2-03,
 A303, SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED
 DOORS IN A SERIES.
  
 THIS WAS ADDRESSED ON MOST PAGES.PLEASE ALSO REVISE
 THE MECHANICAL SHEETS.
  
 24.)A111E, DOOR TO MENS LOCKER, SHOW MANEUVERING
 SPACE, PULL SIDE, FBC11 FIGURE 25.
  
 THIS SHEET IS NO LONGER IN THE PLAN.WAS THIS A
 DETAILED FLOOR PLAN?PROVIDE OLD SHEETS WHEN
 RESUBMITTING.
  
 25.)MSP-1 SHOWS A PROPOSED PHASE 2 OF PARKING
 STRUCTURE.NOTE THAT ONLY THE CURRENT IMPROVEMENT IS
 UNDER REVIEW FOR CODE COMPLIANCE.
  
 26.)ADDRESSED.
  
 27.)MSP-1, ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS
 SHOWN FBC11-4.1.2(1), SHOW MAXIMUM SLOPE ON THE PLAN.
  
 THE RESPONSE LETTER STATES THAT THIS HAS BEEN REVIEWED
 UNDER PRIOR PERMIT APPLICATIONS.THIS PLAN IS TO SHOW
 CODE COMPLIANCE.PLEASE ADDRESS THE COMMENT AS
 REQUESTED.
  
 28.)PROVIDE A LIFE SAFETY PLAN FOR THE PROPOSED
 SERVICE/PARKING GARAGE BUILDING, ALL FLOORS SHOWING
 TRAVEL DISTANCE AND EXITS, EGRESS COMPONENT WIDTHS,
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, DISTANCE APART
 OF REQUIRED EXITS, ANY OTHER PERTINENT INFORMATION TO
 DETERMINE CODE COMPLIANCE.THE EXIT DISCHARGE IS TO
 BE TO THE OUTSIDE OF THE BUILDING, INCLUDING OUTSIDE OF
 THE CANOPY COVERED AREAS, AND TRAVEL DISTANCE IS TO
 INCLUDE TRAVEL THROUGH THESE AREAS IF THIS.
  
 PLEASE PROVIDE ALL REQUESTED INFORMATION.THE LIFE
 SAFETY PLAN PROVIDED DOES NOT INCLUDE ALL OF THE ABOVE
 INFORMATION.NO OCCUPANT LOAD WAS PROVIDED, AND THE
 TRAVEL DISTANCE IS SHOWN TO THE CANOPY AREA.TRAVEL
 DISTANCE IS TO BE TO THE OUTSIDE, NOT TO THE BUILDING
 AREA OF AN ADJACENT BUILDING.AS NO OPENINGS WOULD BE
 ALLOWED WITH A 0? TO 3? BUILDING SEPARATION (SEE FBC,
 THE OPEN AREA LEADING TO THE CANOPY WOULD ALSO NOT BE
 ALLOWED.A COMPLETE REVIEW CANNOT BE PERFORMED UNTIL
 DESIGN INTENT IS CLEAR.
  
 29.)ADDRESSED.
  
 30.)THERE APPEARS TO BE AN EXISTING SERVICE BUILDING
 ON THE WEST SIDE.INCLUDE A LIFE SAFETY PLAN SHOWING
 HOW EGRESS WILL BE AFFECTED.
  
 THE RESPONSE LETTER PARTIALLY ADDRESSES THIS COMMENT.
 PLEASE INCORPORATE THE INFORMATION INTO THE PLAN.
 PLEASE SHOW MEANS OF EGRESS FROM THE EXISTING SERVICE
 BUILDING; SHOW THAT IT IS NOT THROUGH THE SIDE ADJACENT
 TO THE PROPOSED SERVICE BUILDING AND PARKING
 STRUCTURE.
  
 31.)PROVIDE A LIFE SAFETY PLAN FOR THE EXISTING
 HUMMER BUILDING, FIRST FLOOR AND SECOND FLOOR (2 HOUR
 WALL SHOWN ON 2ND FLOOR) IF APPLICABLE.
  
 THE RESPONSE LETTER PARTIALLY ADDRESSES THIS COMMENT.
 PLEASE INCORPORATE THE INFORMATION INTO THE PLAN.
 PLEASE SHOW MEANS OF EGRESS FROM THE EXISTING HUMMER
 BUILDING; SHOW THAT IT IS NOT THROUGH THE CANOPY AREA.
 IF IT IS, AS YOU ARE CLOSING OFF THE CANOPY AREA, THAT
 DISTANCE MUST BE ADDED TO THE TRAVEL DISTANCE.
  
 32.)A FOLDING PARTITION IS SHOWN ON THE PLAN IN THE
 MEZZANINE/TRAINING AREA.DOES THIS PARTITION CLOSE? IT
 DOES NOT COMPLY WITH EGRESS DOOR REQUIREMENTS,
 FBC1008.1.2, PLEASE ADDRESS.IF IT DOES NOT CLOSE, PUT
 THAT REQUIREMENT ON THE PLAN.
  
 THE PARTITION WAS REMOVED FROM MOST SHEETS BUT STILL
 APPEARS ON THE MECHANICAL PAGES.PLEASE CHECK ALL
 SHEETS.
  
 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN
 PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE
 CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON
 PLAN.
  
 PLEASE INCORPORATE INFORMATION INTO THE PLAN AS
 REQUESTED.THE RESPONSE LETTER STATES TO SEE ITEM 12
 FOR THE CODE SUMMARY, BUT REQUESTED INFORMATION WAS NOT
 PROVIDED.PLEASE INCLUDE IN THE PLAN.
  
 34.)PROVIDE DESIGN SPECIFICATIONS FOR THE GUARD,
 FBC1607.7, FBC1012.
  
 THE RESPONSE LETTER STATES THAT THIS WILL BE DONE
 THROUGH SHOP DRAWINGS.DESIGNER OF RECORD IS TO
 PROVIDE DETAILS AND DESIGN CRITERIA AS REQUESTED
 FBC*106.1.1.
  
 35.)ADDRESSED.
  
 36.)WHAT IS THE 3FT4IN DIMENSION SHOWN AT THE STAIR,
 #303 AND 203?IT APPEARS TO BE AN OPENING, NOT ALLOWED
 IN A VERTICAL EXIT.PLEASE CLARIFY.
  
 THIS WAS REMOVED FROM MOST SHEETS BUT STILL APPEARS ON
 THE MECHANICAL SHEETS.PLEASE ADDRESS AND MAKE ALL
 SHEETS CONSISTENT.
  
 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN
 WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS
 TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM
 NORMALLY OCCUPIED SPACES.
  
 THE RESPONSE LETTER STATES, ?THIS SPACE IS A FREQUENTLY
 VISITED STORAGE AREA.OPENINGS TO EXIT STAIR SHOULD BE
 ALLOWED.?PLEASE SHOW IN THE CODE WHERE THIS IS
 ALLOWED.
  
 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM
 THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS
 REQUIRED.GG-A108.
  
 AN OCCUPANCY SEPARATION IS REQUIRED FOR GARAGES,
 FBC406.2.7.FBC302.3.1 STATES THAT FIRE SEPARATIONS
 ARE NOT REQUIRED BETWEEN USES, EXCEPT AS REQUIRED BY
 OTHER PROVISIONS.YOUR RESPONSE LETTER STATES THAT YOU
 HAVE COMPLIED WITH THE MOST STRINGENT REQUIREMENT, BUT
 COMPLIANCE HAS NOT BEEN SHOWN.PLEASE SEE OTHER
 COMMENTS.
  
 39.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 PLEASE ADDRESS ON THE PLAN.
  
 40.)THE LOUNGE/TRAINING AREA SHOWS A 2 HOUR
 SEPARATION, NO HORIZONTAL SEPARATION.IF THE OCCUPANCY
 SEPARATION IS REQUIRED, HORIZONTAL SEPARATION ALSO
 REQUIRED, PROVIDE CALCULATED FIRE RESISTANCE FBC7 OR
 TESTED ASSEMBLY, FLOOR AND CEILING.
  
 WHAT IS THE OCCUPANCY CLASSIFICATION OF THE
 LOUNGE/TRAINING AREA?PLEASE SEE FBC302.ALSO PROVIDE
 OCCUPANT LOAD FOR THIS AREA.SEE OTHER COMMENTS.
  
 41.)ADDRESSED.
  
 42.)ADDRESSED.PLEASE INCLUDE OCCUPANCY
 CLASSIFICATION SO THAT COMPLIANCE WITH FBC1607.1 CAN BE
 DETERMINED.
  
 43.)NO EXIT LIGHTS SHOWN ON FIRST FLOOR OR ROOF,
 FBC1006.3.
  
 44.)ADDRESSED.
  
 45.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13.
  
 THIS HAS BEEN DONE, BUT IF THE ENERGY CALCS CHANGE
 THROUGH THE PLAN REVIEW PROCESS, PLEASE SIGN NEW ENERGY
 CALCS.
  
 46-49.)THESE COMMENTS RELATE TO PRODUCT APPROVALS
 WHICH WERE NOT SUBMITTED.
  
 50.)ADDRESSED.
  
 51.)ADDRESSED ON A201, SHEET A200 NO LONGER IN THE
 PACKAGE.
  
 NEW COMMENTS:
  
 52.)PRODUCT APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.NO PRODUCT
 APPROVALS SUBMITTED WITH THIS PERMIT APPLICATION
 PACKAGE.
  
 53.)THE SIGNATURE FOR AN ENGINEER CANNOT BE A STAMP
 (STRUCTURAL ENGINEER), SEE FAC61G15-23.002, FS471.025.
  
 54.)PLEASE CLOUD ALL CHANGES AND SUBMIT OLD SHEETS.
 PLEASE INCLUDE A RESPONSE LETTER INDICATING HOW EACH
 ITEM HAS BEEN ADDRESSED.