Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop P
Sequence Number 1
Notes
Date Text
2006-10-14 16:51:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE IMPRESSION SEAL SHALL
 IMPRESS INFORMATION REQUIRED BY FAC 61G1-16.002(1) & FS
 481.2055 ON EACH SHEET.
  
 2. ALL PME SHEETS SHALL SHOW THE CERTIFICATE OF
 AUTHORIZATION NUMBER ON EACH SHEET. SOME SHEETS HAVE
 OTHERS DO NOT. FAC 61G15-23.002(2) & FS 471.025.
  
 3. SHT A-104 INDICATE THE SQUARE FOOTAGE AND OCCUPANCY
 OF THE SERVICE AREA, OIL STORAGE ARE, AND BUSINESS
 AREAS. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES FOR
 EACH OCCUPANCY PER TABLES 1004.1.2 & 403.1. SEPARATE
 FACILITIES ARE REQUIRED FOR EACH SEX PER SECTION 403.2.
 ONLY MEN'S FACILITIES ARE SHOWN.
  
 4. SHT A-200 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR TOILET STALL
 A. 11-4.17.3 EXCEPTION(1) - 60" REQUIRED FROM WALL
 NEXT TO THE W/C TO THE SIDE OF THE LAV. SEE FIG.
 11-30(E)
 FOR URINAL
 A. 11-4.18.4 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.5 FAUCETS
  
 5. SHT A-201 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 KIT. SINK
 A. 11-4.24.5 CLEAR FLOOR SINK (FORWARD APPROACH
 REQUIRED)
 B. 11-4.24.7 FAUCETS (VIEW 1 SHOWS A DIFFERENT FAUCET
 TYPE FROM THE COUNTER DETAIL PLEASE CORRELATE TO
 REQUIRED TYPE FAUCET).
  
 5. SHT P-100 INDICATES EXISTING SANITARY BLDG DRAIN.
 THIS WAS PROBABLY INSTALLED AS A SEWER FROM THE HUMMER
 BLDG. ORIGINALLY. PLEASE INDICATE THE MATERIAL THAT WAS
 INSTALLED, AS THE MATERIAL WILL BE REQUIRED TO COMPLY
 WITH TABLES 702.1 & 702.2. INDICATE THE DRAINAGE
 FIXTURE UNITS FROM THE HUMMER BUILDING. A COPY OF THE
 HUMMER BUILDING PLUMBING RISER DIAGRAM SHALL BE
 SUBMITTED TO VERIFY DFU'S IN ORDER TO PROPERLY SIZE THE
 BUILDING DRAIN FOR THE SERVICE/PARKING BUILDING.
 INDICATE IF THE CLEANOUT REQUIRED BY SECTION 708.3.5
 NEAR THE JUNCTION OF THE BLDG DRAIN AND THE BLDG SEWER
 OF THE HUMMER BLDG HAS BEEN DELETED. SECTION 106.1.1 &
 TABLE 710.1(1).
  
 6. SHT P-100 BECAUSE OF THE AUTOMOBILE SERVICE WORK AN
 OIL/GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER FOR A
 DETERMINATION. CONTACT HER AT (561) 822-2271, OR BY FAX
 (561) 822-2279, OR BY E-MAIL [email protected]. WASTE
 ORD. 3434.
  
 7. SHT P-101 SUBMIT MANUF. SPECIFICATION SHEETS FOR THE
 INSTANT-FLOW WATER HEATER FOR THE KITCHEN SINK. SPECS.
 SHALL SHOW A LISTING FOR THE W/H. SECTIONS 106.1.2 &
 303.4
  
 8. SHT P-200 SHOW THE CLEANOUTS AS REQUIRED IN SECTION
 1101.8 FOR THE STORM RISERS.
  
 9. SHT P-200 THE SQUARE FOOTAGE SHOWN ON RISERS RD1,
 RD3, & RD4 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON
 THE ROOF PLUMBING PLAN. PLEASE CORRELATE RISERS AND
 ROOF PLAN. SECTION 106.1.1 & TABLE 1106.3.
  
 10. SHT P-200 EWH PIPING SCHEMATIC. SHOW COMPLIANCE
 WITH SECTION 607.3.2 THERMAL EXPANSION CONTROL.
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE BUILDING. SECTION 608.13.2.
  
 12. SHT P-200 WATER RISER DIAGRAM. FULL OPEN VALVES
 REQUIRED ON EACH WATER DOWN-FEED PIPE. SECTION
 606.1(4).
  
 13. SHT P-200 SANT. RISER DIAGRAM INDICATE IF CLEANOUT
 REQUIRED BY SECTION 708.3.5 FROM HUMMER BLDG HAS BEEN
 DELETED. SHOW THE CLEANOUT REQUIRED BY SECTION 708.3.5
 NEAR THE JUNCTION OF THE BLDG DRAIN AND THE BUILDING
 SEWER FOR THE SERVICE/PARKING BUILDING. SHOW THE DFU'S
 AS THEY ACCUMULATE THE THE SYSTEM, INCLUDING THE DFU'S
 FROM THE HUMMER BUILDING. TABLE 710.1(1) & SECTION
 106.1.1.
  
 14. SHT P-200 PLUMBING SPECIFICATIONS #5(A) INDICATES
 CPVC AS AN ACCEPTABLE SUBSTATUTE FOR THE SANITARY
 WASTE. THIS IS NOT APPROVED PER TABLES 702.1 & 702.2.
  
 15. SHT P-200 PLUMBING SPECIFICATIONS #5(F) AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM REFERENCE.
 SECTION 604.9.
  
 16. SHT P-200 SANT., STORM, AND WATER RISER DIAGRAM
 REFER TO THE CIVIL PLANS. THE CIVIL PLANS WERE NOT
 SUBMITTED. PLEASE SUBMIT A COPY OF THE CIVIL PLANS.
 SECTION 106.1.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  