2006-10-18 08:32:40 | DENIED: |
| 1.PLEASE NOTE PERMIT APPLICATION INDICATES 2 STORY |
| PARKING GARAGE WHEREAS THE THE PLANS APPEAR TO HAVE THE |
| REPAIR OR SERVICE GARAGE ON THE FIRST FLOOR WITH |
| PARKING ABOVE. |
| |
| 2.PLAN SHEET M-100,THE DOOR INTO THE MEN'S LOCKER |
| ROOM (A111) IS INDICATED AS "LOUVERED BOTH SIDES". |
| PLEASE CLARIFY IS THIS AIR MAKE-UP?PLEASE SHOW |
| COMPLIANCE WITH THE FOLLOWING: |
| |
| 3. PER 2004 FMC 401.5.1 OUTSIDE AIR INTAKE OPENINGS |
| SHALL BE LOCATED A MINIMUM OF 10FT FROM ANY HAZARDOUS |
| EXHAUST.AIR FROM THE GARAGE SHALL NOT BE |
| RECIRCULATED. |
| |
| 4. 2004 FMC 404.3 CONNECTING WAITING ROOMS, OFFICES AND |
| SIMILAR USES THAT ARE ACCESSORY TO THE PUBLIC GARAGE |
| SHALL BE MAINTAINED AT A POSITIVE PRESSURE. |
| |
| 5. 2004 FMC 502.14,THE EXHAUST FROMA REPAIR GARAGE |
| SHALL RUN CONTINUOUSLY. |
| |
| 6.PLEASE PROVIDE FRESH AIR CALCULATIONS FOR ALL AREAS |
| IN ACCORDANCE WITH 2004 FMC TABLE 403.3. |
| |
| 7.PLAN SHEET A-109 THE EXHAUST APPEARS TO TO BE |
| WITHIN 10 FT OF THE FRESH AIR INTAKE LOUVERS, AIR |
| REMOVED BY BY THE EXHAUST SHALL BE DISCHARGED OUTDOORS |
| AT A POINT WHERE IT CAN NOT BE READILY DRAWN BACK INTO |
| THE BUILDING. |
| |
| 8.PLEASE PROVIDE CLEARANCES FROM OTHER BUILDINGS ON |
| THE SAME LOT, FRESH AIR INTAKES, DOORS, WINDOWS, ETC. |
| |