Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-18 08:32:40DENIED:
 1.PLEASE NOTE PERMIT APPLICATION INDICATES 2 STORY
 PARKING GARAGE WHEREAS THE THE PLANS APPEAR TO HAVE THE
 REPAIR OR SERVICE GARAGE ON THE FIRST FLOOR WITH
 PARKING ABOVE.
  
 2.PLAN SHEET M-100,THE DOOR INTO THE MEN'S LOCKER
 ROOM (A111) IS INDICATED AS "LOUVERED BOTH SIDES".
 PLEASE CLARIFY IS THIS AIR MAKE-UP?PLEASE SHOW
 COMPLIANCE WITH THE FOLLOWING:
  
 3. PER 2004 FMC 401.5.1 OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10FT FROM ANY HAZARDOUS
 EXHAUST.AIR FROM THE GARAGE SHALL NOT BE
 RECIRCULATED.
  
 4. 2004 FMC 404.3 CONNECTING WAITING ROOMS, OFFICES AND
 SIMILAR USES THAT ARE ACCESSORY TO THE PUBLIC GARAGE
 SHALL BE MAINTAINED AT A POSITIVE PRESSURE.
  
 5. 2004 FMC 502.14,THE EXHAUST FROMA REPAIR GARAGE
 SHALL RUN CONTINUOUSLY.
  
 6.PLEASE PROVIDE FRESH AIR CALCULATIONS FOR ALL AREAS
 IN ACCORDANCE WITH 2004 FMC TABLE 403.3.
  
 7.PLAN SHEET A-109 THE EXHAUST APPEARS TO TO BE
 WITHIN 10 FT OF THE FRESH AIR INTAKE LOUVERS, AIR
 REMOVED BY BY THE EXHAUST SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT CAN NOT BE READILY DRAWN BACK INTO
 THE BUILDING.
  
 8.PLEASE PROVIDE CLEARANCES FROM OTHER BUILDINGS ON
 THE SAME LOT, FRESH AIR INTAKES, DOORS, WINDOWS, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].