2006-10-25 14:48:51 | 1. PLEASE INDICATE THE TYPES OF AUTOMOTIVE REPAIRS THAT |
| ARE PLANNED FOR THE BUILDING. |
| 2. PLANS SEEM TO INDICATE THAT THE BUILDING WILL BE |
| FIRE SPRINKLER PROTECTED HOWEVER NO FIRE SPRINKLER |
| PLANS WERE NOTED. |
| 3. ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS EXIST. |
| EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS EVEN |
| WHEN THEY ARE NOT CLEARLY OBVIOUS. |
| 4. NO EMERGENCY LIGHTING DECLARED ON PAGE E-103. 5. NO |
| EXIT SIGN MARKINGS SHOWN ON PAGE E-200. |
| 6. PLEASE PROVIDE PRODUCT APPROVALS FOR THE CO |
| DETECTORS PLANNED FOR USE. DO THEY COME FACTORY SET OR |
| WILL CALIBRATION GAS BE NEEDED TO SET THESE POINTS. 7. |
| NO EMERGENCY LIGHTS DISPLAYED FOR MEZZANINE ON PAGE |
| E-102. |
| 8. PLEASE PROVIDE A LIST OF CHEMICALS AND THEIR AMOUNTS |
| PLANNED FOR THE BUILDING. |
| 9. BUILDIND ADDRESS REQUIRED . A MINIMUM OF AT LEAST 6" |
| IN HEIGHT AND 1" IN WIDTH. |
| 10. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| WALLS AND CEILINGS IN NON AUTOMOTIVE WORK AREAS. 11. |
| SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE SPRINKLER |
| AND FIRE ALARM SYSTEM. |
| 12. NO PORTABLE FIRE EXTINGUISHERS PROVIDED. |
| 13. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR ALL HANDRAILS, GUARDRAILS, AND CABLE RAIL SYSTEMS. |
| 14. PLEASE DECLARE OCCUPANCY TYPE AND OCCUPANT LOADS |
| FOR THE BUILDING. |
| 15. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. |
| 16. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. 17. A |
| KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. 18. IS THE |
| BUILDING CONSIDERED OPEN OR CLOSED FOR DESIGN |
| PURPOSES. |
| 19. PLEASE DECLARE DISTANCE FROM EXHAUST TERMINATION |
| POINTS TO ANY BUILDING OPENINGS. |
| 20. PLEASE INDICATE HOW FLAMMABLE OR COMBUSTIBE LIQUIDS |
| WILL BE STORED, HANDLED, AND DISPOSED OF WITHIN THE |
| BUILDING. |
| |
| MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709 |
| |
| MICHAEL A. WILLIAMS, FIRE PREVENTION CAPTAIN 805-6722 |