Plan Review Notes
Plan Review Notes For Permit 06090410
Permit Number 06090410
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-02 00:00:00*******UNSAT ******
  
  
 1)A) NOTE: PLEASE SEE PERMIT APPLICATION
 AND PLANS MENTIONS AND SHOWS "3021",
 HOWEVER THIS PROJETC IS LOCATED ON A
 LEGAL ADDRESS IN OUR SYSTEM OF "3001".
 PLEASE KNOW TITLE BLOCKS SHALL BE
 REVISED UPON CORRECTING OF ADDRESS.
  
 1) NOTE: PLEASE BE SURE ALL OF THE
 FOLLOWING CODES ARE STATED ON PLANS AT A
 MINIMUM.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101, NFPA-30A AND 2004 FBC.
 PLEASE KNOW, THERE MAY BE OTHER CODES
 REQUESTED BY OTHER TRADES TO BE STATED
 ON PLANS RELEVANT TO DESIGN.
  
 2) NOTE: PLEASE SEE MISSING LICENSING
 INFORMATION ON TITLE BLOCKS FOR ALL MEP
 PLANS AS REQUIRED PER FAC 61G15-23.002,
 FS 471.023
  
 3) NOTE: PLEASE NEC 511, AND PLEASE
 INDICATE ALLRELEVANT AREAS AND LAYOUT
 ON PLANS.
  
 4) NOTE: PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2. PLEASE SUBMIT AND SUPPLY ALL
 MIN PHOTO-METRICS REQUIRED FOR STAIR
 TOWERS UNDER NORMAL AND EMERGENCY POWER.
 PLEASE ALSO INDICATE LIGHTING LEVELS
 (MIN) REQUIRED FOR ALL OTHER AREAS OF
 EGRESS. PLEASE SEE THERE ARE AREAS ON
 PLANS WHICH DO NOT SEEM TO MEET THIS.
 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EM IN STAIRS.
 ALL OTHER AREAS 1FT MIN.
  
 5) NOTE: PLEASE SEE THERE ARE AREAS OF
 EGRESS WHICH IS NOT INDICATING ANY
 EGRESS OR BATTERY BACK UP LTS. PLEASE
 SEE ALL AREAS OF COMMON USAGE
 INCLUDING MAIN ELECTRICAL ROOM, ELEVATOR
 EQUIPMENT RM AND OTHER AREAS ON PLANS
 WHICH WILL REQUIRE BATTERY BACK UP
 FIXTURES OF SOME SORT. PLEASE SEE
 700.12E, 700.16, LS 101 7.8, 7.9, STATE
 ELEVATOR CODE.
 ** PLEASE KNOW, EM ILLUMINATION IS
 REQUIRED OUT OF THE BUILDING TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE ALSO BE SURE TO ADJUST FIXTURE
 SCHEDULE FOR ALL.
  
 6) NOTE: PLEASE LIST AND IDENTIFY ALL
 LIGHTING FIXTURES ON PLANS AND CORRELATE
 WITH THE SUBMITTED SCHEDULE.
 FBC 106.1.2, 106.3.5.1.2 ADMINISTRATIVE
 SECTIONS AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 7) NOTE: PLEASE PROVIDE ROOM AND AREA
 DESIGNATIONS ON PLANS FOR ALL SPACES.
 PLEASE KNOW, MANY ITEMS FOR REVIEW OF
 CODE COMPLIANCE MAY NOT BE DONE AT THIS
 TIME.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECT.
  
 8) NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 408.4, 310.16, 240.4
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE 620.23 AND 620.24.
 PLEASE SEE LTS/RECEPTS FOR THE ELEVATOR
 ROOM(S) SHALL CONTAIN DEDICATED CIRCUITS
 AND MAY NOT FEED ANY OTHER AREAS.
  
 10) NOTE: PLEASE SEE SOME LOCATION ON
 PLANS WHERE AN "S" IS SHOWN WHICH IS THE
 SYMBOL FOR "SWITCH" ON LEGEND, HOWEVER
 THEY ARE NOT SHOWN AS CONTROLLING
 ANYTHING?
 PLEASE COMPLETE, OR ADJUST.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE A BATH RM WITH NOT
 LT FIXTURE BEING SHOWN.
 PLEASE ALSO SEE BATH RMS WITH MULTIPLE
 STALLS SHALL ALSO CONTAIN EM BATTERY
 BACK UP FIXTURES.
 LS 101 7.8,7.9
  
 12) NOTE: PLEASE SEE FIRE REVIEW
 COMMENTS FOR GARAGE AREAS LTS, REQ'D EM
 BACK UP.
 AS PREVIOUSLY NOTED ABOVE FOR ELECTRICAL
 REVIEW ALSO.
 LS101 7.9
  
 13) NOTE: PLEASE SEE 2004 FBC CHAPTER 13
 FOR CONTROLS FOR ALL LIGHTING.
 PLEASE INDICATE AND SHOW THE SYSTEM
 BEING PROPOSED. PLEASE PROVIDE
 SCHEDULING OF SYSTEMS.
 PLEASE PROVIDE OVER RIDES, LOCATIONS,
 AND AREAS FOR SEPARATE CONTROLS
 REQUIRED. PLEASE SEE FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SHOW AND INDICATE THE TYPE OF
 OVER RIDE DEVICES,A ND MAX ALLOWED
 TIMES. (NOTE: TIMER TYPE (4HRS MAX),
 OCCUPANT SENSOR TYPE 30MINS MAX).
 ALL AREAS WITH FLR TO CEILING HEIGHT
 PARTITIONS REQUIRE SEPARATE CONTROLS.
 PLEASE PROVIDE PERFORMANCE CALCULATIONS
 AND PLEASE SEE THE MAXIMUM PERMITTED
 "LIGHTING POWER DENSITIES" (LPD) ALLOWED
 FOR AREAS.
 PLEASE SEE SPACES AND USE PERMITTED IN
 TABLES.
 13-415.2, 13-415.2.ABC.1, TABLES
 13-415.2.B.
 ALL LPD'S ARE TO BE SHOWN.
  
 14) NOTE: PLEASE SEE THIS IS NOT BEING
 CONSIDERED A SEPARATE "BUILDING" AND IS
 PART OF THE CURRENT STRUCTURE AS THIS
 NEW STRUCTURE CONTAINS OPENINGS ECT FOR
 EGRESS ETC.
 PLEASE SEE FBC DEFINITIONS.
 PLEASE SEE NEC 230.2, AS THE NEW
 PROPOSED SEPARATE SERVICE NOT BEING FED
 FROM THE EXISTING SERVICE LOCATION
 GROUPED ETC IS NOT PERMITTED AS SHOWN. 230.2,230.72
 ETC.
 IN ORDER TO GRANT THE NEW SERVICE FOR A
 NEW "BUILDING", THIS WOULD REQUIRE AND
 "FIREWALL", 4 HR RATED, COLLAPSIBLE ON
 BOTH SIDES WITH OUT AFFECT THE
 STRUCTURAL INTEGRITY OF EITHER
 STRUCTURE. BY THE PLANS SUBMITTED,THIS
 IS NOT ACHIEVED AT THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING EXT/EM LT
 AS VEST, FOR EGRESS.
 LS 101 7.8, 7.9
 PLEASE SEE PLANS ARE REDLINED FOR MANY
 AREAS IN WHICH SOME COMMENTS ARE
 RELEVANT, HOWEVER ARE IN NO WAY ALL.
  
 16) NOTE: PLEASE SEE 250.50, AS THE NEW
 FOOTER STEEL SHALL BE PART OF THE
 EXISTING GROUNDING ELECTRODE SYSTEM.
 250.50
  
 17) NOTE: PLEASE SEE AREA ON "MEZZ"
 LEVEL WHICH SEEMS TO INDICATE A/C
 EQUIPMENT. PLEASE SEE 210.63 FOR MISSING GFI.210.8B
  
 18) NOTE: PLEASE SUBMIT ALL WIND LOAD
 CALCULATIONS FOR ROOF TOP LT POLES WITH
 EPA FIGURED FOR ALL LT FIXTURES
 PROPOSED.
 THE CALCULATIONS AND SPEC FOR POLES WILL
 BE REVIEWED FOR STRUCTURAL CONNECTIONS,
 WIND LOADS ETC BY THE STRUCTURAL
 REVIEWER.
 THEY MUST MEET FBC 2004 140MPH MIN, 3
 SEC GUST.
  
 19) NOTE: PLEASE SUBMIT THE MANUFACTURE
 SPECS /CUT SHEETS FOR THE TANKLESS WATER
 HEATER. PLEASE BE SURE THEY INDICATE THE
 NRTL LISTING.
 110.3, 90.7.
  
 20) NOTE: PLEASE SEE AS PLUMBING PLANS
 ALSO INDICATE BEING TIED INTO THE
 EXISTING BUILDING, IT SEEMS THE PERMIT
 APPLICATION WOULD BETTER DESCRIBE
 PROJECT AS AN ADDITION.
 THIS WILL BE DECIDED BY DESIGN FOR NOTES
 FROM ALL REVIEWER(S).
  
 ** PLEASE KNOW, AS THERE ARE ITEMS NOT
 IN DESIGN AT THIS TIME REQUIRED FOR
 REVIEW, THERE MAY BE COMMENTS ON FURTHER
 REVIEWS.
  
 ** PLEASE BE AWARE OF COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT
 ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-10-01 00:00:00*** REVIEW IN PROGRESS, PLANS TO GO
 INTO "F" STATUS, NOTES OT FOLLOW.
2006-09-29 00:00:00IN ELEC FOR REVIEW,