Date |
Text |
2006-10-02 00:00:00 | *******UNSAT ****** |
| |
| |
| 1)A) NOTE: PLEASE SEE PERMIT APPLICATION |
| AND PLANS MENTIONS AND SHOWS "3021", |
| HOWEVER THIS PROJETC IS LOCATED ON A |
| LEGAL ADDRESS IN OUR SYSTEM OF "3001". |
| PLEASE KNOW TITLE BLOCKS SHALL BE |
| REVISED UPON CORRECTING OF ADDRESS. |
| |
| 1) NOTE: PLEASE BE SURE ALL OF THE |
| FOLLOWING CODES ARE STATED ON PLANS AT A |
| MINIMUM. |
| 2002 NFPA-70, 2002 NFPA-72, 2003 |
| NFPA-101, NFPA-30A AND 2004 FBC. |
| PLEASE KNOW, THERE MAY BE OTHER CODES |
| REQUESTED BY OTHER TRADES TO BE STATED |
| ON PLANS RELEVANT TO DESIGN. |
| |
| 2) NOTE: PLEASE SEE MISSING LICENSING |
| INFORMATION ON TITLE BLOCKS FOR ALL MEP |
| PLANS AS REQUIRED PER FAC 61G15-23.002, |
| FS 471.023 |
| |
| 3) NOTE: PLEASE NEC 511, AND PLEASE |
| INDICATE ALLRELEVANT AREAS AND LAYOUT |
| ON PLANS. |
| |
| 4) NOTE: PLEASE SEE NFPA-101 7.8.1.3, |
| 7.9.2.2. PLEASE SUBMIT AND SUPPLY ALL |
| MIN PHOTO-METRICS REQUIRED FOR STAIR |
| TOWERS UNDER NORMAL AND EMERGENCY POWER. |
| PLEASE ALSO INDICATE LIGHTING LEVELS |
| (MIN) REQUIRED FOR ALL OTHER AREAS OF |
| EGRESS. PLEASE SEE THERE ARE AREAS ON |
| PLANS WHICH DO NOT SEEM TO MEET THIS. |
| 10FT CANDLES UNDER NORMAL AND 1FT CANDLE |
| UNDER EM IN STAIRS. |
| ALL OTHER AREAS 1FT MIN. |
| |
| 5) NOTE: PLEASE SEE THERE ARE AREAS OF |
| EGRESS WHICH IS NOT INDICATING ANY |
| EGRESS OR BATTERY BACK UP LTS. PLEASE |
| SEE ALL AREAS OF COMMON USAGE |
| INCLUDING MAIN ELECTRICAL ROOM, ELEVATOR |
| EQUIPMENT RM AND OTHER AREAS ON PLANS |
| WHICH WILL REQUIRE BATTERY BACK UP |
| FIXTURES OF SOME SORT. PLEASE SEE |
| 700.12E, 700.16, LS 101 7.8, 7.9, STATE |
| ELEVATOR CODE. |
| ** PLEASE KNOW, EM ILLUMINATION IS |
| REQUIRED OUT OF THE BUILDING TO THE |
| PUBLIC RIGHT OF WAY. |
| PLEASE ALSO BE SURE TO ADJUST FIXTURE |
| SCHEDULE FOR ALL. |
| |
| 6) NOTE: PLEASE LIST AND IDENTIFY ALL |
| LIGHTING FIXTURES ON PLANS AND CORRELATE |
| WITH THE SUBMITTED SCHEDULE. |
| FBC 106.1.2, 106.3.5.1.2 ADMINISTRATIVE |
| SECTIONS AS ADOPTED BY THE CITY OF WEST |
| PALM BEACH. |
| |
| 7) NOTE: PLEASE PROVIDE ROOM AND AREA |
| DESIGNATIONS ON PLANS FOR ALL SPACES. |
| PLEASE KNOW, MANY ITEMS FOR REVIEW OF |
| CODE COMPLIANCE MAY NOT BE DONE AT THIS |
| TIME. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECT. |
| |
| 8) NOTE: PLEASE COMPLETE ALL CIRCUITING |
| ON PLANS AND CORRELATE WITH THE PANEL |
| SCHEDULES SUBMITTED. |
| 408.4, 310.16, 240.4 |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 9) NOTE: PLEASE SEE 620.23 AND 620.24. |
| PLEASE SEE LTS/RECEPTS FOR THE ELEVATOR |
| ROOM(S) SHALL CONTAIN DEDICATED CIRCUITS |
| AND MAY NOT FEED ANY OTHER AREAS. |
| |
| 10) NOTE: PLEASE SEE SOME LOCATION ON |
| PLANS WHERE AN "S" IS SHOWN WHICH IS THE |
| SYMBOL FOR "SWITCH" ON LEGEND, HOWEVER |
| THEY ARE NOT SHOWN AS CONTROLLING |
| ANYTHING? |
| PLEASE COMPLETE, OR ADJUST. |
| FBC 106.1.2 |
| |
| 11) NOTE: PLEASE SEE A BATH RM WITH NOT |
| LT FIXTURE BEING SHOWN. |
| PLEASE ALSO SEE BATH RMS WITH MULTIPLE |
| STALLS SHALL ALSO CONTAIN EM BATTERY |
| BACK UP FIXTURES. |
| LS 101 7.8,7.9 |
| |
| 12) NOTE: PLEASE SEE FIRE REVIEW |
| COMMENTS FOR GARAGE AREAS LTS, REQ'D EM |
| BACK UP. |
| AS PREVIOUSLY NOTED ABOVE FOR ELECTRICAL |
| REVIEW ALSO. |
| LS101 7.9 |
| |
| 13) NOTE: PLEASE SEE 2004 FBC CHAPTER 13 |
| FOR CONTROLS FOR ALL LIGHTING. |
| PLEASE INDICATE AND SHOW THE SYSTEM |
| BEING PROPOSED. PLEASE PROVIDE |
| SCHEDULING OF SYSTEMS. |
| PLEASE PROVIDE OVER RIDES, LOCATIONS, |
| AND AREAS FOR SEPARATE CONTROLS |
| REQUIRED. PLEASE SEE FBC |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE SHOW AND INDICATE THE TYPE OF |
| OVER RIDE DEVICES,A ND MAX ALLOWED |
| TIMES. (NOTE: TIMER TYPE (4HRS MAX), |
| OCCUPANT SENSOR TYPE 30MINS MAX). |
| ALL AREAS WITH FLR TO CEILING HEIGHT |
| PARTITIONS REQUIRE SEPARATE CONTROLS. |
| PLEASE PROVIDE PERFORMANCE CALCULATIONS |
| AND PLEASE SEE THE MAXIMUM PERMITTED |
| "LIGHTING POWER DENSITIES" (LPD) ALLOWED |
| FOR AREAS. |
| PLEASE SEE SPACES AND USE PERMITTED IN |
| TABLES. |
| 13-415.2, 13-415.2.ABC.1, TABLES |
| 13-415.2.B. |
| ALL LPD'S ARE TO BE SHOWN. |
| |
| 14) NOTE: PLEASE SEE THIS IS NOT BEING |
| CONSIDERED A SEPARATE "BUILDING" AND IS |
| PART OF THE CURRENT STRUCTURE AS THIS |
| NEW STRUCTURE CONTAINS OPENINGS ECT FOR |
| EGRESS ETC. |
| PLEASE SEE FBC DEFINITIONS. |
| PLEASE SEE NEC 230.2, AS THE NEW |
| PROPOSED SEPARATE SERVICE NOT BEING FED |
| FROM THE EXISTING SERVICE LOCATION |
| GROUPED ETC IS NOT PERMITTED AS SHOWN. 230.2,230.72 |
| ETC. |
| IN ORDER TO GRANT THE NEW SERVICE FOR A |
| NEW "BUILDING", THIS WOULD REQUIRE AND |
| "FIREWALL", 4 HR RATED, COLLAPSIBLE ON |
| BOTH SIDES WITH OUT AFFECT THE |
| STRUCTURAL INTEGRITY OF EITHER |
| STRUCTURE. BY THE PLANS SUBMITTED,THIS |
| IS NOT ACHIEVED AT THIS TIME. |
| |
| 15) NOTE: PLEASE SEE MISSING EXT/EM LT |
| AS VEST, FOR EGRESS. |
| LS 101 7.8, 7.9 |
| PLEASE SEE PLANS ARE REDLINED FOR MANY |
| AREAS IN WHICH SOME COMMENTS ARE |
| RELEVANT, HOWEVER ARE IN NO WAY ALL. |
| |
| 16) NOTE: PLEASE SEE 250.50, AS THE NEW |
| FOOTER STEEL SHALL BE PART OF THE |
| EXISTING GROUNDING ELECTRODE SYSTEM. |
| 250.50 |
| |
| 17) NOTE: PLEASE SEE AREA ON "MEZZ" |
| LEVEL WHICH SEEMS TO INDICATE A/C |
| EQUIPMENT. PLEASE SEE 210.63 FOR MISSING GFI.210.8B |
| |
| 18) NOTE: PLEASE SUBMIT ALL WIND LOAD |
| CALCULATIONS FOR ROOF TOP LT POLES WITH |
| EPA FIGURED FOR ALL LT FIXTURES |
| PROPOSED. |
| THE CALCULATIONS AND SPEC FOR POLES WILL |
| BE REVIEWED FOR STRUCTURAL CONNECTIONS, |
| WIND LOADS ETC BY THE STRUCTURAL |
| REVIEWER. |
| THEY MUST MEET FBC 2004 140MPH MIN, 3 |
| SEC GUST. |
| |
| 19) NOTE: PLEASE SUBMIT THE MANUFACTURE |
| SPECS /CUT SHEETS FOR THE TANKLESS WATER |
| HEATER. PLEASE BE SURE THEY INDICATE THE |
| NRTL LISTING. |
| 110.3, 90.7. |
| |
| 20) NOTE: PLEASE SEE AS PLUMBING PLANS |
| ALSO INDICATE BEING TIED INTO THE |
| EXISTING BUILDING, IT SEEMS THE PERMIT |
| APPLICATION WOULD BETTER DESCRIBE |
| PROJECT AS AN ADDITION. |
| THIS WILL BE DECIDED BY DESIGN FOR NOTES |
| FROM ALL REVIEWER(S). |
| |
| ** PLEASE KNOW, AS THERE ARE ITEMS NOT |
| IN DESIGN AT THIS TIME REQUIRED FOR |
| REVIEW, THERE MAY BE COMMENTS ON FURTHER |
| REVIEWS. |
| |
| ** PLEASE BE AWARE OF COMMENTS FROM |
| OTHER TRADES WHICH WILL AFFECT |
| ELECTRICAL PLANS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
2006-10-01 00:00:00 | *** REVIEW IN PROGRESS, PLANS TO GO |
| INTO "F" STATUS, NOTES OT FOLLOW. |
2006-09-29 00:00:00 | IN ELEC FOR REVIEW, |