2006-10-13 13:06:43 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC2004 |
| |
| |
| 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| PERMIT PICKUP, FS713.13. |
| |
| 2.)PROVIDE A SURVEY FOR THIS PROPERTY, FBC*106.3.4, |
| SHOWING PROPERTY LINE AND ALL EXISTING IMPROVEMENTS. |
| |
| 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| 561-233-5025 FOR MORE INFORMATION. |
| |
| 4.)RADON FEES DUE, FS*553.721.SEE ATTACHED. |
| |
| 5.)DUE TO VALUATION ADJUSTMENT, FEES HAVE BEEN |
| INCREASED.SEE ATTACHED. |
| |
| 6.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| FS553.79 (2), ATTACHED LETTER FROM DCA. |
| |
| 7.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| ONE OR MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQFT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| OF CONSTRUCTION |
| |
| ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| SERVICES MANAGER - TEL: |
| 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT |
| INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. |
| |
| 8.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.1, |
| 1802.2.3.THREE SETS REQUIRED. |
| |
| 9.)THE SEAL IS ILLEGIBLE (ARCHITECT).PLEASE |
| ADDRESS, FS481.221. |
| |
| 10.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD, FBC*106.3.3. |
| |
| 11.)INCLUDE FBC EB IN GOVERNING CODE.THIS PROPOSED |
| IMPROVEMENT IS TO COMPLY WITH FBC EB CHAPTER 9; SEE |
| ALSO FBC EB 901.2.SOME COMMENTS AND REQUEST FOR |
| ADDITIONAL INFORMATION RELATE TO THIS CODE SECTION. |
| |
| 12.)INCLUDE A CODE SUMMARY. DECLARE BUILDING TYPE |
| FBC6 (INCLUDE A OR B), BUILDING HEIGHT AND AREA FBC5, |
| OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY, |
| FIRE SPRINKLER INFORMATION.NOTE THAT CANOPIES AND |
| EQUIPMENT SHEDS ARE TO BE INCLUDED, SEE FBC 502, |
| DEFINITION OF AREA, BUILDING.BUILDING TYPE WILL BE |
| BASED ON WORST CASE UNLESS A FIRE WALL SEPARATES THE |
| BUILDING AREAS.DETAILS OF EXISTING CONDITIONS SHOWING |
| FIRE RESISTANCE MAY BE REQUIRED.PLEASE CONTACT ME IF |
| YOU ARE UNSURE OF WHICH DETAILS TO INCLUDE. |
| |
| 13.)REGARDING OCCUPANCY CLASSIFICATIONS, PLEASE SEE |
| FBC304, FBC311.2, FBC311.3.OTHER CODE SECTIONS MAY |
| APPLY. |
| |
| 14.)WHAT HAZARDOUS MATERIALS WILL BE STORED AND IN |
| WHAT QUANTITIES?SEE FBC TABLE 307.7(1), FBC 406.6. |
| |
| 15.)DECLARE AN OCCUPANCY CLASSIFICATION FOR THE OIL |
| STORAGE, SEE FBC TABLE 307.7(1), FBC406.6.NOTE |
| QUANTITIES. |
| |
| 16.)SHOW HOW COMPLIANCE WITH FBC TABLE 503 HAS BEEN |
| ACCOMPLISHED; SEE ALSO FBC 302.IF HEIGHT OR AREA |
| MODIFICATIONS HAVE BEEN USED AS PER FBC 503 THROUGH |
| 508, PUT ALL INFORMATION AND CALCULATIONS ON THE PLAN. |
| INFORMATION PROVIDED SHOULD BE CLEAR IN REGARDS TO |
| BUILDING TYPE, BUILDING AREA, AND OCCUPANCY |
| CLASSIFICATION IN REGARDS TO THE EXISTING BUILDINGS |
| (INCLUDING AREAS REFERRED TO AS ?CANOPY? AND |
| ?EQUIP.SHED?, ETC.) AS WELL AS THE NEW IMPROVEMENT. |
| |
| 17.)IT IS NOT CLEAR WHETHER THE EXISTING SERVICE |
| SHOWN ON THE WEST SIDE MSP-1 WILL BE A PART OF THE NEW |
| BUILDING (APPEARS TO BE ATTACHED AT THE NORTHWEST |
| PORTION, THE REST OF THE EXISTING SERVICE IS ALONG THE |
| RAMP) OR IF IT A SEPARATE BUILDING, TO BE SEPARATED |
| WITH AN ASSUMED PROPERTY LINE.IF THIS IS A SEPARATE |
| BUILDING, SHOW COMPLIANCE WITH FBC TABLE 602 BY SHOWING |
| THE BUILDING TYPE AND OCCUPANCY, ASSUMED PROPERTY LINE, |
| DISTANCE OF EACH BUILDING FROM THE ASSUMED PROPERTY |
| LINE.COMPLIANCE FOR EACH BUILDING MUST BE SHOWN, |
| INCLUDING FIRE RESISTANCE RATING FOR THE EXISTING |
| BUILDING. |
| |
| IF THIS IS NOT A SEPARATE BUILDING, INCLUDE THIS |
| BUILDING IN THE CODE SUMMARY, SEE ITEM 3. |
| |
| 18.)SEPARATIONS IF REQUIRED ARE TO COMPLY WITH FBC |
| TABLE 302.3.2.AS NO FIRE SPRINKLER INFORMATION OR FBC |
| TABLE 503 COMPLIANCE WAS PROVIDED, IT IS NOT CLEAR IF |
| THE 2 HOUR SHOWN BETWEEN B AND S1 IS CORRECT. |
| |
| 19.)NO HORIZONTAL SEPARATIONS WERE SHOWN.SEE |
| PREVIOUS COMMENT, NOT CLEAR AT THIS TIME IF IT IS |
| REQUIRED. |
| |
| 20.)PROVIDE DISTANCE OF ADJACENT BUILDINGS TO THE |
| PROPOSED RENOVATED BUILDING.FOR INSTANCE, DISTANCE |
| FROM USED CARS TO HUMMER SHOWROOM, USED CARS TO |
| EXISTING SERVICE.CONNECTING MULTIPLE BUILDINGS MAY |
| AFFECT BUILDING TYPE FBC5, WHICH MAY AFFECT CODE |
| COMPLIANCE WITH FBC TABLE 602.PROVIDE INFORMATION IN |
| REGARDS TO OCCUPANCY CLASSIFICATION AND BUILDING TYPE |
| FOR OTHER STRUCTURES. |
| |
| 21.)MSP-1, BUILDING/LOT COVERAGE ZONING INFORMATION |
| REFERS TO AN EXISTING LEVITZ BUILDING BUT THAT BUILDING |
| IS NOT REFERENCED ON THE SITE PLAN. |
| |
| 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND |
| EXISTING VW SERVICE/VW SHOWROOM? |
| |
| 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A203, |
| A303,SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED |
| DOORS IN A SERIES. |
| |
| 24.)A111E, DOOR TO MENS LOCKER, SHOW MANEUVERING |
| SPACE, PULL SIDE, FBC11 FIGURE 25. |
| |
| 25.)MSP-1 SHOWS A PROPOSED PHASE 2 OF PARKING |
| STRUCTURE.NOTE THAT ONLY THE CURRENT IMPROVEMENT IS |
| UNDER REVIEW FOR CODE COMPLIANCE. |
| |
| 26.)S4, THERE IS A NOTE FOR 6IN CONCRETE SLAB AT THE |
| ELEVATOR AREA.IS THIS SUPPOSED TO BE FOR THE |
| MEZZANINE?6IN CONCRETE SLAB SHOWN FOR VESTIBULE. |
| |
| 27.)MSP-1, ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS |
| SHOWN FBC11-4.1.2(1), SHOW MAXIMUM SLOPE ON THE PLAN. |
| |
| 28.)PROVIDE A LIFE SAFETY PLAN FOR THE PROPOSED |
| SERVICE/PARKING GARAGE BUILDING, ALL FLOORS SHOWING |
| TRAVEL DISTANCE AND EXITS, EGRESS COMPONENT WIDTHS, |
| OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, DISTANCE APART |
| OF REQUIRED EXITS, ANY OTHER PERTINENT INFORMATION TO |
| DETERMINE CODE COMPLIANCE.THE EXIT DISCHARGE IS TO |
| BE TO THE OUTSIDE OF THE BUILDING, INCLUDING OUTSIDE OF |
| THE CANOPY COVERED AREAS, AND TRAVEL DISTANCE IS TO |
| INCLUDE TRAVEL THROUGH THESE AREAS IF THIS. |
| |
| 29.)IT APPEARS THAT THE BUILDING AREA BETWEEN THE |
| IMPROVEMENT AND VW AREAS IS AN OPEN CANOPY, SO EGRESS |
| ON THAT SIDE FOR THE OTHER BUILDING IS NOT AFFECTED. IS |
| THIS CORRECT?IF NOT, PROVIDE A LIFE SAFETY PLAN FOR |
| THAT AREA. |
| |
| 30.)THERE APPEARS TO BE AN EXISTING SERVICE BUILDING |
| ON THE WEST SIDE.INCLUDE A LIFE SAFETY PLAN SHOWING |
| HOW EGRESS WILL BE AFFECTED. |
| |
| 31.)PROVIDE A LIFE SAFETY PLAN FOR THE EXISTING |
| HUMMER BUILDING, FIRST FLOOR AND SECOND FLOOR (2 HOUR |
| WALL SHOWN ON 2ND FLOOR) IF APPLICABLE. |
| |
| 32.)A FOLDING PARTITION IS SHOWN ON THE PLAN IN THE |
| MEZZANINE/TRAINING AREA.DOES THIS PARTITION CLOSE? IT |
| DOES NOT COMPLY WITH EGRESS DOOR REQUIREMENTS, |
| FBC1008.1.2, PLEASE ADDRESS.IF IT DOES NOT CLOSE, PUT |
| THAT REQUIREMENT ON THE PLAN. |
| |
| 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN |
| PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE |
| CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON |
| PLAN. |
| |
| 34.)PROVIDE DESIGN SPECIFICATIONS FOR THE GUARD, |
| FBC1607.7, FBC1012. |
| |
| 35.)A101, MEZZANINE PLAN SHOWS A PLYWOOD DECK, |
| CEILING OVER JANITOR?S CLOSET.AS NO BUILDING TYPE WAS |
| DECLARED, IT IS NOT CLEAR IF THIS IS PERMITTED |
| (COMBUSTIBLE).PLEASE CONFIRM PRIOR TO RESUBMITTAL. |
| |
| 36.)WHAT IS THE 3FT4IN DIMENSION SHOWN AT THE STAIR, |
| #303 AND 203?IT APPEARS TO BE AN OPENING, NOT ALLOWED |
| IN A VERTICAL EXIT.PLEASE CLARIFY. |
| |
| 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN |
| WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS |
| TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM |
| NORMALLY OCCUPIED SPACES. |
| |
| 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM |
| THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS |
| REQUIRED.GG-A108. |
| |
| 39.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE |
| 803.5. |
| |
| 40.)THE LOUNGE/TRAINING AREA SHOWS A 2 HOUR |
| SEPARATION, NO HORIZONTAL SEPARATION.IF THE OCCUPANCY |
| SEPARATION IS REQUIRED, HORIZONTAL SEPARATION ALSO |
| REQUIRED, PROVIDE CALCULATED FIRE RESISTANCE FBC7 OR |
| TESTED ASSEMBLY, FLOOR AND CEILING. |
| |
| 41.)THE NOTE A106 STATES THAT THE FUSIBLE LINK IS TO |
| BE MANUALLY OPERATED.CLARIFY. |
| |
| 42.)PROVIDE DESIGN CRITERIA, LIVE LOADS, FOR |
| MEZZANINE AS PER FBC TABLE 1607.1.NOT INCLUDED ON |
| S1. |
| |
| 43.)NO EXIT LIGHTS SHOWN ON FIRST FLOOR OR ROOF, |
| FBC1006.3. |
| |
| 44.)MEZZANINE IS TO BE OPEN TO THE ROOM IT IS LOCATED |
| IN, SEE FBC505.4. |
| |
| 45.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, |
| FBC13. |
| |
| 46.)PRODUCT APPROVAL FOR OVERHEAD DOOR HAS A PRODUCT |
| LIMITATION OF -53, S10 SPECIFIES EITHER -61 FOR D1 OR |
| -73 FOR D1A. |
| |
| 47.)PROVIDE FLORIDA STATE PRODUCT APPROVAL FOR ALL |
| PRODUCTS, INCLUDING ONES WITH A NOA.IF IT IS NOT |
| AVAILABLE, A LOCAL PRODUCT APPROVAL WILL BE ISSUED. |
| |
| 48.)SPEC SHEETS PROVIDED FOR THE FLEMING DOOR. |
| PRODUCT APPROVALS REQUIRED.THE DOOR DOES NOT MEET |
| DESIGN PRESSURE FOR D1A. |
| |
| 49.)UNITED ENERTECH LOUVERS APPEAR CODE COMPLIANT. |
| SEE ITEM 47 AND 10. |
| |
| 50.)A200, NOTES FOR HC BAR BACKING REFER TO PT WOOD. |
| NOTE THAT THAT IS A COMBUSTIBLE.BUILDING TYPE HAS NOT |
| BEEN DECLARED, SO CODE COMPLIANCE CANNOT BE |
| DETERMINED. |
| |
| 51.)A200, ACCESSIBLE SINK IS TO BE A MAX OF 6 1/2 IN |
| DEEP, FBC11-4.24. |
| |
| |