2006-10-13 13:06:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)PROVIDE A SURVEY FOR THIS PROPERTY, FBC*106.3.4,
 SHOWING PROPERTY LINE AND ALL EXISTING IMPROVEMENTS.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4.)RADON FEES DUE, FS*553.721.SEE ATTACHED.
  
 5.)DUE TO VALUATION ADJUSTMENT, FEES HAVE BEEN
 INCREASED.SEE ATTACHED.
  
 6.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 7.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 8.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.1,
 1802.2.3.THREE SETS REQUIRED.
  
 9.)THE SEAL IS ILLEGIBLE (ARCHITECT).PLEASE
 ADDRESS, FS481.221.
  
 10.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 11.)INCLUDE FBC EB IN GOVERNING CODE.THIS PROPOSED
 IMPROVEMENT IS TO COMPLY WITH FBC EB CHAPTER 9; SEE
 ALSO FBC EB 901.2.SOME COMMENTS AND REQUEST FOR
 ADDITIONAL INFORMATION RELATE TO THIS CODE SECTION.
  
 12.)INCLUDE A CODE SUMMARY. DECLARE BUILDING TYPE
 FBC6 (INCLUDE A OR B), BUILDING HEIGHT AND AREA FBC5,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY,
 FIRE SPRINKLER INFORMATION.NOTE THAT CANOPIES AND
 EQUIPMENT SHEDS ARE TO BE INCLUDED, SEE FBC 502,
 DEFINITION OF AREA, BUILDING.BUILDING TYPE WILL BE
 BASED ON WORST CASE UNLESS A FIRE WALL SEPARATES THE
 BUILDING AREAS.DETAILS OF EXISTING CONDITIONS SHOWING
 FIRE RESISTANCE MAY BE REQUIRED.PLEASE CONTACT ME IF
 YOU ARE UNSURE OF WHICH DETAILS TO INCLUDE.
  
 13.)REGARDING OCCUPANCY CLASSIFICATIONS, PLEASE SEE
 FBC304, FBC311.2, FBC311.3.OTHER CODE SECTIONS MAY
 APPLY.
  
 14.)WHAT HAZARDOUS MATERIALS WILL BE STORED AND IN
 WHAT QUANTITIES?SEE FBC TABLE 307.7(1), FBC 406.6.
  
 15.)DECLARE AN OCCUPANCY CLASSIFICATION FOR THE OIL
 STORAGE, SEE FBC TABLE 307.7(1), FBC406.6.NOTE
 QUANTITIES.
  
 16.)SHOW HOW COMPLIANCE WITH FBC TABLE 503 HAS BEEN
 ACCOMPLISHED; SEE ALSO FBC 302.IF HEIGHT OR AREA
 MODIFICATIONS HAVE BEEN USED AS PER FBC 503 THROUGH
 508, PUT ALL INFORMATION AND CALCULATIONS ON THE PLAN.
 INFORMATION PROVIDED SHOULD BE CLEAR IN REGARDS TO
 BUILDING TYPE, BUILDING AREA, AND OCCUPANCY
 CLASSIFICATION IN REGARDS TO THE EXISTING BUILDINGS
 (INCLUDING AREAS REFERRED TO AS ?CANOPY? AND
 ?EQUIP.SHED?, ETC.) AS WELL AS THE NEW IMPROVEMENT.
  
 17.)IT IS NOT CLEAR WHETHER THE EXISTING SERVICE
 SHOWN ON THE WEST SIDE MSP-1 WILL BE A PART OF THE NEW
 BUILDING (APPEARS TO BE ATTACHED AT THE NORTHWEST
 PORTION, THE REST OF THE EXISTING SERVICE IS ALONG THE
 RAMP) OR IF IT A SEPARATE BUILDING, TO BE SEPARATED
 WITH AN ASSUMED PROPERTY LINE.IF THIS IS A SEPARATE
 BUILDING, SHOW COMPLIANCE WITH FBC TABLE 602 BY SHOWING
 THE BUILDING TYPE AND OCCUPANCY, ASSUMED PROPERTY LINE,
 DISTANCE OF EACH BUILDING FROM THE ASSUMED PROPERTY
 LINE.COMPLIANCE FOR EACH BUILDING MUST BE SHOWN,
 INCLUDING FIRE RESISTANCE RATING FOR THE EXISTING
 BUILDING.
  
 IF THIS IS NOT A SEPARATE BUILDING, INCLUDE THIS
 BUILDING IN THE CODE SUMMARY, SEE ITEM 3.
  
 18.)SEPARATIONS IF REQUIRED ARE TO COMPLY WITH FBC
 TABLE 302.3.2.AS NO FIRE SPRINKLER INFORMATION OR FBC
 TABLE 503 COMPLIANCE WAS PROVIDED, IT IS NOT CLEAR IF
 THE 2 HOUR SHOWN BETWEEN B AND S1 IS CORRECT.
  
 19.)NO HORIZONTAL SEPARATIONS WERE SHOWN.SEE
 PREVIOUS COMMENT, NOT CLEAR AT THIS TIME IF IT IS
 REQUIRED.
  
 20.)PROVIDE DISTANCE OF ADJACENT BUILDINGS TO THE
 PROPOSED RENOVATED BUILDING.FOR INSTANCE, DISTANCE
 FROM USED CARS TO HUMMER SHOWROOM, USED CARS TO
 EXISTING SERVICE.CONNECTING MULTIPLE BUILDINGS MAY
 AFFECT BUILDING TYPE FBC5, WHICH MAY AFFECT CODE
 COMPLIANCE WITH FBC TABLE 602.PROVIDE INFORMATION IN
 REGARDS TO OCCUPANCY CLASSIFICATION AND BUILDING TYPE
 FOR OTHER STRUCTURES.
  
 21.)MSP-1, BUILDING/LOT COVERAGE ZONING INFORMATION
 REFERS TO AN EXISTING LEVITZ BUILDING BUT THAT BUILDING
 IS NOT REFERENCED ON THE SITE PLAN.
  
 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND
 EXISTING VW SERVICE/VW SHOWROOM?
  
 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A203,
 A303,SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED
 DOORS IN A SERIES.
  
 24.)A111E, DOOR TO MENS LOCKER, SHOW MANEUVERING
 SPACE, PULL SIDE, FBC11 FIGURE 25.
  
 25.)MSP-1 SHOWS A PROPOSED PHASE 2 OF PARKING
 STRUCTURE.NOTE THAT ONLY THE CURRENT IMPROVEMENT IS
 UNDER REVIEW FOR CODE COMPLIANCE.
  
 26.)S4, THERE IS A NOTE FOR 6IN CONCRETE SLAB AT THE
 ELEVATOR AREA.IS THIS SUPPOSED TO BE FOR THE
 MEZZANINE?6IN CONCRETE SLAB SHOWN FOR VESTIBULE.
  
 27.)MSP-1, ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS
 SHOWN FBC11-4.1.2(1), SHOW MAXIMUM SLOPE ON THE PLAN.
  
 28.)PROVIDE A LIFE SAFETY PLAN FOR THE PROPOSED
 SERVICE/PARKING GARAGE BUILDING, ALL FLOORS SHOWING
 TRAVEL DISTANCE AND EXITS, EGRESS COMPONENT WIDTHS,
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, DISTANCE APART
 OF REQUIRED EXITS, ANY OTHER PERTINENT INFORMATION TO
 DETERMINE CODE COMPLIANCE.THE EXIT DISCHARGE IS TO
 BE TO THE OUTSIDE OF THE BUILDING, INCLUDING OUTSIDE OF
 THE CANOPY COVERED AREAS, AND TRAVEL DISTANCE IS TO
 INCLUDE TRAVEL THROUGH THESE AREAS IF THIS.
  
 29.)IT APPEARS THAT THE BUILDING AREA BETWEEN THE
 IMPROVEMENT AND VW AREAS IS AN OPEN CANOPY, SO EGRESS
 ON THAT SIDE FOR THE OTHER BUILDING IS NOT AFFECTED. IS
 THIS CORRECT?IF NOT, PROVIDE A LIFE SAFETY PLAN FOR
 THAT AREA.
  
 30.)THERE APPEARS TO BE AN EXISTING SERVICE BUILDING
 ON THE WEST SIDE.INCLUDE A LIFE SAFETY PLAN SHOWING
 HOW EGRESS WILL BE AFFECTED.
  
 31.)PROVIDE A LIFE SAFETY PLAN FOR THE EXISTING
 HUMMER BUILDING, FIRST FLOOR AND SECOND FLOOR (2 HOUR
 WALL SHOWN ON 2ND FLOOR) IF APPLICABLE.
  
 32.)A FOLDING PARTITION IS SHOWN ON THE PLAN IN THE
 MEZZANINE/TRAINING AREA.DOES THIS PARTITION CLOSE? IT
 DOES NOT COMPLY WITH EGRESS DOOR REQUIREMENTS,
 FBC1008.1.2, PLEASE ADDRESS.IF IT DOES NOT CLOSE, PUT
 THAT REQUIREMENT ON THE PLAN.
  
 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN
 PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE
 CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON
 PLAN.
  
 34.)PROVIDE DESIGN SPECIFICATIONS FOR THE GUARD,
 FBC1607.7, FBC1012.
  
 35.)A101, MEZZANINE PLAN SHOWS A PLYWOOD DECK,
 CEILING OVER JANITOR?S CLOSET.AS NO BUILDING TYPE WAS
 DECLARED, IT IS NOT CLEAR IF THIS IS PERMITTED
 (COMBUSTIBLE).PLEASE CONFIRM PRIOR TO RESUBMITTAL.
  
 36.)WHAT IS THE 3FT4IN DIMENSION SHOWN AT THE STAIR,
 #303 AND 203?IT APPEARS TO BE AN OPENING, NOT ALLOWED
 IN A VERTICAL EXIT.PLEASE CLARIFY.
  
 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN
 WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS
 TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM
 NORMALLY OCCUPIED SPACES.
  
 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM
 THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS
 REQUIRED.GG-A108.
  
 39.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 40.)THE LOUNGE/TRAINING AREA SHOWS A 2 HOUR
 SEPARATION, NO HORIZONTAL SEPARATION.IF THE OCCUPANCY
 SEPARATION IS REQUIRED, HORIZONTAL SEPARATION ALSO
 REQUIRED, PROVIDE CALCULATED FIRE RESISTANCE FBC7 OR
 TESTED ASSEMBLY, FLOOR AND CEILING.
  
 41.)THE NOTE A106 STATES THAT THE FUSIBLE LINK IS TO
 BE MANUALLY OPERATED.CLARIFY.
  
 42.)PROVIDE DESIGN CRITERIA, LIVE LOADS, FOR
 MEZZANINE AS PER FBC TABLE 1607.1.NOT INCLUDED ON
 S1.
  
 43.)NO EXIT LIGHTS SHOWN ON FIRST FLOOR OR ROOF,
 FBC1006.3.
  
 44.)MEZZANINE IS TO BE OPEN TO THE ROOM IT IS LOCATED
 IN, SEE FBC505.4.
  
 45.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13.
  
 46.)PRODUCT APPROVAL FOR OVERHEAD DOOR HAS A PRODUCT
 LIMITATION OF -53, S10 SPECIFIES EITHER -61 FOR D1 OR
 -73 FOR D1A.
  
 47.)PROVIDE FLORIDA STATE PRODUCT APPROVAL FOR ALL
 PRODUCTS, INCLUDING ONES WITH A NOA.IF IT IS NOT
 AVAILABLE, A LOCAL PRODUCT APPROVAL WILL BE ISSUED.
  
 48.)SPEC SHEETS PROVIDED FOR THE FLEMING DOOR.
 PRODUCT APPROVALS REQUIRED.THE DOOR DOES NOT MEET
 DESIGN PRESSURE FOR D1A.
  
 49.)UNITED ENERTECH LOUVERS APPEAR CODE COMPLIANT.
 SEE ITEM 47 AND 10.
  
 50.)A200, NOTES FOR HC BAR BACKING REFER TO PT WOOD.
 NOTE THAT THAT IS A COMBUSTIBLE.BUILDING TYPE HAS NOT
 BEEN DECLARED, SO CODE COMPLIANCE CANNOT BE
 DETERMINED.
  
 51.)A200, ACCESSIBLE SINK IS TO BE A MAX OF 6 1/2 IN
 DEEP, FBC11-4.24.
  
  