2006-11-15 14:23:29** MECHANICAL REVISION **
 *** DENIED ***
 1) THE RETURN AIR TRANSFER DUCTS TO THE BEDROOMS ARE
 UNDER-SIZED, SEE NOTE #2.
  
 2) BALANCED RETURN AIR.
 MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 3) ENGINEER LUIS A. LOPEZ NEEDS TO SIGN AND SEAL THE
 PLANS AS HIS NAME IS THE TITLE BLOCK, PER FAC
 61G1-16.003.
  
 4) A MECHANICAL PERMIT WILL BE REQUIRED FOR THE A/C
 WORK. PLEASE RESUBMIT MECHANICAL PLANS WITH APPLICATION
 FOR MECHANICAL PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.