2006-09-27 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED ON |
| THE ISOMETRIC DRAWING FOR GAS PLAN |
| REVIEW: |
| |
| 1. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: THIS INCLUDES THE EXISTING GAS |
| SYSTEM PLEASE SEE THE ATTACHED PERMIT |
| INFORMATION INDICATING GAS AT SAID |
| ADDRESS. |
| |
| 2. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: REFERENCE NOTE ON COMMENT 1 |
| |
| 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT AND INSTALLATION INSTRUCTIONS |
| TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND THE FBC-2004 FUEL GAS |
| CODE SEC 402.2 |
| NOTE: NEED SHEETS ON REGULATORS AND |
| GENERATOR. |
| |
| 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |