Plan Review Notes
Plan Review Notes For Permit 06090369
Permit Number 06090369
Review Stop G
Sequence Number 1
Notes
Date Text
2006-09-27 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED ON
 THE ISOMETRIC DRAWING FOR GAS PLAN
 REVIEW:
  
 1. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS
 SYSTEM PLEASE SEE THE ATTACHED PERMIT
 INFORMATION INDICATING GAS AT SAID
 ADDRESS.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE NOTE ON COMMENT 1
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT AND INSTALLATION INSTRUCTIONS
 TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND THE FBC-2004 FUEL GAS
 CODE SEC 402.2
 NOTE: NEED SHEETS ON REGULATORS AND
 GENERATOR.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  