2007-02-14 15:47:35 | |
| **** UNSAT **** |
| |
| 1) NOTE:PLEASE SEE THAT THE PANEL SCHEDULE NEEDS TO |
| BE REVISED TO CORRELATE TO ALL AREAS AND ROOMS WHICH |
| CIRCUITS FEED. |
| PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM |
| 408.4 COMMENTARY OF THE NEC. |
| |
| *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| |
| PLEASE KNOW AS THE DRYWALL IS ALREADY INSTALLED, THESE |
| PLANS WILL BE FOR FINAL AND THE ABOVE IS REQUIRED TO |
| SPECIFIC AT THIS TIME. THIS IS FOR BOTH PANELS P AND |
| P2. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| |