2006-12-24 14:05:03 | **UNSAT 3RD REVIEW ** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS |
| STILL IN NEED OF ADDRESSING. |
| PLEASE SEE NOTE # 1 FROM PREVIOUS REVIEW. |
| |
| 1) NOTE: PLEASE BE SURE TO REMOVE ANY OLD |
| NON-APPLICABLE SHEETS FROM ENERGY CALCULATIONS WHICH DO |
| NOT APPLY. PLEASE SEE OLD SHEETS WERE LEFT IN ALONG |
| WITH NEW. |
| PLEASE CORRELATE ENERGY CALCULATIONS WITH THE FIXTURES |
| AND WATTAGE OF EACH FIXTURE ON PLAN. PLEASE SEE THE |
| WATTAGE DOES NOT CORRELATE. |
| THE EXCEPTION AS PERMITTED AS NOTED IS OK, HOWEVER |
| PLEASE SEE NOT ALL AREAS ARE BEING INCLUDED IN ENERGY |
| CALCULATIONS. |
| PLEASE ALSO SEE THERE ARE ROOMS WHICH ARE NOT BEING |
| INCLUDED FOR CONTROLS. DUE TO THE REMODEL/BUILD OUT |
| TAKING PLACE, THESE AREAS SHALL ALSO BE INCLUDED AS |
| STATED IN THE PREVIOUS REVIEW FOR ALL SEPARATE SPACES |
| CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS. |
| PLEASE SEE ROOMS, 107,108,109,117, 118, 119 AND ROOM |
| WHICH IS NOTED AS CONFERENCE ROOM IN CENTER OF PLANS. |
| AT LAST CONVERSATION, IT WAS UNDERSTOOD THAT ALL AREAS |
| WOULD BE INCLUDED. |
| |
| 13-415.1.ABC.1.1, .1.2, AND .1.3, 13-415.1AB.1, |
| 13-415.2.ABC.1 |
| |
| ** PLEASE KNOW THIS IS NOT SOMETHING THAT CANNOT BE |
| REDLINED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |