Plan Review Notes
Plan Review Notes For Permit 06090338
Permit Number 06090338
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-28 19:57:37**** UNSAT ***
  
 1) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WHICH
 INDICATE MANUAL ON/OFF CONTROL CHOSEN FOR THE METHOD OF
 CONTROLLING LIGHTING. PLEASE CHOOSE AUTO OPTION.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 MISSING OVER RIDE DEVICES LOCATED IN ALL SPACES
 CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS.
 PLEASE SEE MISSING THE MAX TIMES PERMITTED FOR TYPE OF
 OVER RIDES WHICH ARE NOT SHOWN AT THIS TIME. (30 MINS
 MAX FOR OCCUPANT SENSOR TYPE DEVICES, 4HRS MAX FOR
 TIMER TYPE.)
 PLEASE SEE MISSING OVER RIDE CONTROLS AS THEY ARE
 REQUIRED AT THE LOCATIONS OF INGRESS/EGRESS SO THE
 OCCUPANT MAY BE ABLE TO CONTROL THE LIGHTS WHICH ARE IN
 SIGHT.
 PLEASE INDICATE DEVICES AND CORRELATE WITH THE SYMBOL
 LEGEND.
 PLEASE EXPLAIN NOTE NUMBER #6 ON DRAWING KEY NOTES AS
 IT MENTIONS RELAY FOR NOT BEING ABLE TO OPERATE SOME
 RECESSED LIGHTING AT THE SAME TIME WITH OTHERS??
  
 2) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4).
 PLEASE KNOW, ANY NEW FA DEVICES INSTALLED MUST MEET
 THESE MINIMUM LEVELS. THIS WAS NOT IN PREVIOUS REVIEW
 AS THIS WAS NOT IN THE SCOPE OF WORK OF ELECTRICAL
 REVIEW, HOWEVER IT NOW IS.THE PRIMARY ISSUE IS ITEM
 11-4.28.3(4) WHICH REQUIRES A MIN OF 75 CANDELAS FOR
 ANY NEW STROBE DEVICES.
 PLEASE INDICATE ON LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, COMMENTS OR IF ANY PART OF
 NOTES ABOVE ARE NOT UNDERSTOOD OR TYPED IN A MANNER
 WHICH IS NOT CLEAR, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE OR REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  