2006-11-28 19:57:37 | **** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WHICH |
| INDICATE MANUAL ON/OFF CONTROL CHOSEN FOR THE METHOD OF |
| CONTROLLING LIGHTING. PLEASE CHOOSE AUTO OPTION. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE |
| MISSING OVER RIDE DEVICES LOCATED IN ALL SPACES |
| CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS. |
| PLEASE SEE MISSING THE MAX TIMES PERMITTED FOR TYPE OF |
| OVER RIDES WHICH ARE NOT SHOWN AT THIS TIME. (30 MINS |
| MAX FOR OCCUPANT SENSOR TYPE DEVICES, 4HRS MAX FOR |
| TIMER TYPE.) |
| PLEASE SEE MISSING OVER RIDE CONTROLS AS THEY ARE |
| REQUIRED AT THE LOCATIONS OF INGRESS/EGRESS SO THE |
| OCCUPANT MAY BE ABLE TO CONTROL THE LIGHTS WHICH ARE IN |
| SIGHT. |
| PLEASE INDICATE DEVICES AND CORRELATE WITH THE SYMBOL |
| LEGEND. |
| PLEASE EXPLAIN NOTE NUMBER #6 ON DRAWING KEY NOTES AS |
| IT MENTIONS RELAY FOR NOT BEING ABLE TO OPERATE SOME |
| RECESSED LIGHTING AT THE SAME TIME WITH OTHERS?? |
| |
| 2) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4). |
| PLEASE KNOW, ANY NEW FA DEVICES INSTALLED MUST MEET |
| THESE MINIMUM LEVELS. THIS WAS NOT IN PREVIOUS REVIEW |
| AS THIS WAS NOT IN THE SCOPE OF WORK OF ELECTRICAL |
| REVIEW, HOWEVER IT NOW IS.THE PRIMARY ISSUE IS ITEM |
| 11-4.28.3(4) WHICH REQUIRES A MIN OF 75 CANDELAS FOR |
| ANY NEW STROBE DEVICES. |
| PLEASE INDICATE ON LEGEND. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS, COMMENTS OR IF ANY PART OF |
| NOTES ABOVE ARE NOT UNDERSTOOD OR TYPED IN A MANNER |
| WHICH IS NOT CLEAR, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE OR REVIEWER. |
| |