Plan Review Notes For Permit 06090338
Permit Number 06090338
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-29 00:00:00** UNSAT **
  
 1) NOTE: PLEASE STATE THE FOLLOWING
 RELEVANT CODES (WHICH ARE ON PLANS)
 HOWEVER PLEASE GIVE YEAR EDITIONS
 CURRENTLY INEFFECT FOR THE DESIGN.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101.
  
  
 2) NOTE: PLEASE EXPLAIN SERVICE
 SCENARIO, IT IS UNCLEAR AT THIS TIME. IT
 SEEMS LIGHTING ETC IS BEING NOTED AND
 SHOWNFROM A SERVICE WHICH ALSO
 FEEDS THE REST OF THE FLOOR??
 IS THIS NOT A SEPARATE TENANT? PLANS
 INDICATE ADJACENT TENANT SPACES, HOWEVER
 MAY NOT HAVE A SERVICE WHICH FEEDS ONE
 TEANT FEED ANOTHER. PLEASE VERIFY AND
 SHOW THE LOCATION OF THE OTHER
 ELECTRICAL EQUIPMENT/SERVICE. NOT ABLE
 TO DETERMINE SOME ITEMS AT THIS TIME.
 110.26,240.24,210.25 ETC.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13 FOR
 NEW BUILD OUTS OF TENANT SPACES AND
 LIGHTING CONTROLS REQUIRED.
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SEE CALCULAITONS FOR 13-415.2, 13-415.2.ABC.1,
 TABLES 415.2.C.1, AND
 415.2.B.1.
 DEPENDING ON WHAT WORK IS BEING DONE, IT
 SEEMS THESE REQUIREMENTS FOR LIGHTING
 CONTROLS ARE REQUIRED AND LPD'S ARE
 REQUIRED ALSO.
  
 4) NOTE: PLEASE SEE A COUPLE OF OUTSIDE
 OFFICES IN TENANT SPACE WHICH DO NOT
 INDICATE ANY LIGHTING??
  
 5) NOTE: PLEASE SEE BLDG AND POSSIBLE
 FIRE REVIEW COMMENTS AS THE SEEMS TO
 SHOW AN EGRESS DOOR ON THE EXIT STAIR
 TOWERS WHICH OPENS IN. ?? IT IS KNOWN
 THAT THIS MAY NOT BE A PART OF THIS BLD
 OUT HOWEVER IF THIS IS SHOWN ON
 ARCHITECURAL AND MEP PLANS, DOOR SWING
 SHOULD BE VERIFIED. THIS WAS
 HIGH-LIGHTED ON PLANS.
  
  
 ** PLEASE SEE ANY COMMENTS WHICH MAY
 AFFECT THE ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]