Date |
Text |
2006-09-29 00:00:00 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE STATE THE FOLLOWING |
| RELEVANT CODES (WHICH ARE ON PLANS) |
| HOWEVER PLEASE GIVE YEAR EDITIONS |
| CURRENTLY INEFFECT FOR THE DESIGN. |
| 2002 NFPA-70, 2002 NFPA-72, 2003 |
| NFPA-101. |
| |
| |
| 2) NOTE: PLEASE EXPLAIN SERVICE |
| SCENARIO, IT IS UNCLEAR AT THIS TIME. IT |
| SEEMS LIGHTING ETC IS BEING NOTED AND |
| SHOWNFROM A SERVICE WHICH ALSO |
| FEEDS THE REST OF THE FLOOR?? |
| IS THIS NOT A SEPARATE TENANT? PLANS |
| INDICATE ADJACENT TENANT SPACES, HOWEVER |
| MAY NOT HAVE A SERVICE WHICH FEEDS ONE |
| TEANT FEED ANOTHER. PLEASE VERIFY AND |
| SHOW THE LOCATION OF THE OTHER |
| ELECTRICAL EQUIPMENT/SERVICE. NOT ABLE |
| TO DETERMINE SOME ITEMS AT THIS TIME. |
| 110.26,240.24,210.25 ETC. |
| |
| 3) NOTE: PLEASE SEE FBC CHAPTER 13 FOR |
| NEW BUILD OUTS OF TENANT SPACES AND |
| LIGHTING CONTROLS REQUIRED. |
| 13-415.1.ABC.1.1,.1.2,.1.3. |
| PLEASE SEE CALCULAITONS FOR 13-415.2, 13-415.2.ABC.1, |
| TABLES 415.2.C.1, AND |
| 415.2.B.1. |
| DEPENDING ON WHAT WORK IS BEING DONE, IT |
| SEEMS THESE REQUIREMENTS FOR LIGHTING |
| CONTROLS ARE REQUIRED AND LPD'S ARE |
| REQUIRED ALSO. |
| |
| 4) NOTE: PLEASE SEE A COUPLE OF OUTSIDE |
| OFFICES IN TENANT SPACE WHICH DO NOT |
| INDICATE ANY LIGHTING?? |
| |
| 5) NOTE: PLEASE SEE BLDG AND POSSIBLE |
| FIRE REVIEW COMMENTS AS THE SEEMS TO |
| SHOW AN EGRESS DOOR ON THE EXIT STAIR |
| TOWERS WHICH OPENS IN. ?? IT IS KNOWN |
| THAT THIS MAY NOT BE A PART OF THIS BLD |
| OUT HOWEVER IF THIS IS SHOWN ON |
| ARCHITECURAL AND MEP PLANS, DOOR SWING |
| SHOULD BE VERIFIED. THIS WAS |
| HIGH-LIGHTED ON PLANS. |
| |
| |
| ** PLEASE SEE ANY COMMENTS WHICH MAY |
| AFFECT THE ELECTRICAL PLANS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |