Plan Review Notes For Permit 06090301 |
Permit Number |
06090301 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-18 07:22:04 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE | | PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE | | SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO | | RESUBMITTING. | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, GENERATOR, TRANSFER SWITCH, | | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH | | ARTICLES 225 AND 230 CAN BE REVIEWED. DO THIS ON A SITE | | PLAN, NOT ON THE SURVEY, 106.1.3FBC. | | | | 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH. | | THERE IS A DOUBLE THROW DISCONNECT SUBMITTED, BUT THE | | RISER INDICATES A ATS. IF THIS IS TO BE A MANUAL | | TRANSFER PLEASE MODIFY DRAWINGS TO INDICATE SAME. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|