Plan Review Notes
Plan Review Notes For Permit 06090246
Permit Number 06090246
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-11 00:00:00DENIED
  
 1) THE DESIGN PRESSURES FOR THE FLAT
 ROOF SYSTEM ARE TOO LOW FOR ROOF ZONES 2
 AND 3. THE MAXIMUM DESIGN PRESSURE FOR
 THE PRODUCT APPROVAL SUBMITTED FOR THE
 MODIFIED BITUMEN SYSTEM OVER A WOOD DECK
 IS -52.5 PSF. THE PRODUCT APPROVAL DOES
 NOT ALLOW THE DESIGN PRESSURE TO BE
 INCREASED FOR BONDED SYSTEMS. SEE PAGES
 1 AND 2 OF 17.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714