Date |
Text |
2008-02-05 15:35:06 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| FBC-2004 EXISTING BLDG CODE |
| |
| ****FROM PREVIOUS REVIEW: |
| COMMENT NUMBERS TO STAY THE SAME. |
| |
| ******FROM PREVIOUS REVIEWS: 3RD REVIEW*** |
| |
| ********FROM PREVIOUS REVIEWS: 4TH REVIEW*** |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| |
| 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES |
| PER TABLES 1004.2 AND 403.1. |
| ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3 |
| OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR |
| THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE |
| THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE |
| TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. ******RESPONSE |
| NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. IS THE |
| TOTAL AREA OF THE BUILDING TO BE A-3 OCCUPANCY |
| INCLUDING ALL THE OFFICES ON THE SECOND FLOOR? THE |
| TOTAL SQUARE FOOTAGE IS 10411SF @ 7NET THE TOTAL |
| OCCUPANCY IS 1488. THIS NUMBER DIVIDED BY 2, (MEN & |
| WOMEN), COMES TO 744 EACH. 744 DIVIDED BY 150 EQUALS 5 |
| WATER CLOSETS FOR MEN AND 744 DIVIDED BY 75 EQUALS 10 |
| WATER CLOSETS FOR WOMEN TO ACHIEVE POTTY PARITY |
| REQUIRED BY SECTION 403.1.1. THAT SAID, IF THERE IS |
| OTHER OCCUPANCIES BESIDES ASSEMBLY PLEASE INDICATE BY |
| SUBMITTING CALCULATIONS FOR MINIMUM PLUMBING |
| FACILITIES. |
| ********RESPONSE NOTED, BUT THE CALCULATIONS ONLY |
| ACCOUNT FOR 3233SF, BUT THE TOTAL AREA IS INDICATED AS |
| 10,411SF. INDICATE WHERE THE OTHER 7178SF REQUIRED IN |
| THE CALCULATION IS INDICATED. |
| |
| 5. OK |
| 6. OK |
| 7. OK |
| 8. OK |
| 9. OK |
| 10. OK |
| 11. OK |
| 12. OK |
| 13. OK |
| 14. OK |
| |
| **********NEW COMMENTS********** |
| |
| 1B. OK |
| 2B. OK |
| |
| **********NEW COMMENT********** |
| |
| 1C. IN RELATIONSHIP TO THE CHANGE OF OCCUPANCY, SECTION |
| 806.1 OF THE FLORIDA BUILDING CODE EXISTING BUILDING |
| INDICATES "ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| BUILDING. IS THE SECOND FLOOR CONSIDERED ASSEMBLY |
| OCCUPANCY, AND WHAT WAS THE OCCUPANCY PREVIOUSLY. |
| PLEASE CLARIFY. |
| ********RESPONSE NOTED, BUT THE TOILET ROOMS ON THE |
| SECOND FLOOR SHALL BE ACCESSIBLE PER SECTION 806.1 OF |
| THE EXISTING BUILDING CODE |
| |