Plan Review Notes
Plan Review Notes For Permit 06090243
Permit Number 06090243
Review Stop P
Sequence Number 4
Notes
Date Text
2008-02-05 15:35:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 EXISTING BLDG CODE
  
 ****FROM PREVIOUS REVIEW:
 COMMENT NUMBERS TO STAY THE SAME.
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW***
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW***
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES
 PER TABLES 1004.2 AND 403.1.
 ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3
 OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR
 THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE
 THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE
 TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. ******RESPONSE
 NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. IS THE
 TOTAL AREA OF THE BUILDING TO BE A-3 OCCUPANCY
 INCLUDING ALL THE OFFICES ON THE SECOND FLOOR? THE
 TOTAL SQUARE FOOTAGE IS 10411SF @ 7NET THE TOTAL
 OCCUPANCY IS 1488. THIS NUMBER DIVIDED BY 2, (MEN &
 WOMEN), COMES TO 744 EACH. 744 DIVIDED BY 150 EQUALS 5
 WATER CLOSETS FOR MEN AND 744 DIVIDED BY 75 EQUALS 10
 WATER CLOSETS FOR WOMEN TO ACHIEVE POTTY PARITY
 REQUIRED BY SECTION 403.1.1. THAT SAID, IF THERE IS
 OTHER OCCUPANCIES BESIDES ASSEMBLY PLEASE INDICATE BY
 SUBMITTING CALCULATIONS FOR MINIMUM PLUMBING
 FACILITIES.
 ********RESPONSE NOTED, BUT THE CALCULATIONS ONLY
 ACCOUNT FOR 3233SF, BUT THE TOTAL AREA IS INDICATED AS
 10,411SF. INDICATE WHERE THE OTHER 7178SF REQUIRED IN
 THE CALCULATION IS INDICATED.
  
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 **********NEW COMMENT**********
  
 1C. IN RELATIONSHIP TO THE CHANGE OF OCCUPANCY, SECTION
 806.1 OF THE FLORIDA BUILDING CODE EXISTING BUILDING
 INDICATES "ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING. IS THE SECOND FLOOR CONSIDERED ASSEMBLY
 OCCUPANCY, AND WHAT WAS THE OCCUPANCY PREVIOUSLY.
 PLEASE CLARIFY.
 ********RESPONSE NOTED, BUT THE TOILET ROOMS ON THE
 SECOND FLOOR SHALL BE ACCESSIBLE PER SECTION 806.1 OF
 THE EXISTING BUILDING CODE
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]