2007-11-24 17:23:29 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| COMMENT NUMBERS TO STAY THE SAME. |
| |
| ******FROM PREVIOUS REVIEWS: 3RD REVIEW*** |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| |
| 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES |
| PER TABLES 1004.2 AND 403.1. |
| ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3 |
| OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR |
| THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE |
| THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE |
| TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. ******RESPONSE |
| NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. IS THE |
| TOTAL AREA OF THE BUILDING TO BE A-3 OCCUPANCY |
| INCLUDING ALL THE OFFICES ON THE SECOND FLOOR? THE |
| TOTAL SQUARE FOOTAGE IS 10411SF @ 7NET THE TOTAL |
| OCCUPANCY IS 1488. THIS NUMBER DIVIDED BY 2, (MEN & |
| WOMEN), COMES TO 744 EACH. 744 DIVIDED BY 150 EQUALS 5 |
| WATER CLOSETS FOR MEN AND 744 DIVIDED BY 75 EQUALS 10 |
| WATER CLOSETS FOR WOMEN TO ACHIEVE POTTY PARITY |
| REQUIRED BY SECTION 403.1.1. THAT SAID, IF THERE IS |
| OTHER OCCUPANCIES BESIDES ASSEMBLY PLEASE INDICATE BY |
| SUBMITTING CALCULATIONS FOR MINIMUM PLUMBING |
| FACILITIES. |
| |
| 5. OK |
| |
| 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS |
| IS NOT INDICATED ON PLANS. |
| ****NOT ADDRESSED |
| ******RESPONSE NOTED, BUT SECTION 403.1.1 IS NOT |
| COMPLIED WITH. THE CODE SECTION STATES "IN ASSEMBLY |
| OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO THE PUBLIC |
| MUST HAVE A RATIO OF 3:2 WATER CLOSETS PROVIDED FOR |
| WOMEN AS THE TOTAL OF WATER CLOSETS AND URINALS |
| PROVIDED FOR MEN". POTTY PARITY CALCULATIONS SUBMITTED |
| HAVE 4 WATER CLOSETS FOR MEN TO 3 WATER CLOSETS FOR |
| WOMEN. |
| |
| 7. OK |
| 8. OK |
| |
| 9. SHT 3/5 NEW MEN'S TOILET ROOM STALL DOES NOT COMPLY |
| WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3 |
| EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE |
| TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION |
| 11-4.22.3. |
| ****RESPONSE NOTED, BUT THE TURNING AREA IS NOT SHOWN |
| IN THE TOILET ROOMS AS REQUIRED. (NOT REQUIRED IN THE |
| ACCESSIBLE STALL). |
| ******RESPONSE NOTED, BUT THE STALL STILL DOES NOT |
| COMPLY WITH FIGURE 30E. THE LAV IS NOT ALLOWED IN THE |
| CLEAR FLOOR SPACE OF THE WATER CLOSET. FIVE FEET OF |
| CLEAR FLOOR SPACE FROM THE WALL ADJACENT TO THE WATER |
| CLOSET TO THE SIDE OF THE LAV. THE LAV CAN NOT BE IN |
| THE CLEAR FLOOR SPACE OF THE WATER CLOSET. |
| |
| 10. OK |
| |
| 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE |
| WITH 11-4.18 AND ALL SUBSECTIONS. |
| ****RESPONSE NOTED, BUT THE FOLLOWING SECTIONS WERE NOT |
| ADDRESSED: |
| A. OK |
| B. 11-4.18.4 FLUSH CONTROLS |
| ******RESPONSE NOTED, BUT THE CONTROL HEIGHT IS |
| REQUIRED. |
| |
| 12. OK |
| 13. OK |
| 14. OK |
| |
| **********NEW COMMENTS********** |
| |
| 1B. OK |
| |
| 2B. SHT 3/5 MEN'S TOILET ROOM ACCESSIBLE STALL. THE |
| ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER, DIAGONAL |
| TO THE DOOR. SECTION 11-4.17.3 EXCEPTION (2). |
| ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| |
| **********NEW COMMENT********** |
| |
| 1C. IN RELATIONSHIP TO THE CHANGE OF OCCUPANCY, SECTION |
| 806.1 OF THE FLORIDA BUILDING CODE EXISTING BUILDING |
| INDICATES "ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| BUILDING. IS THE SECOND FLOOR CONSIDERED ASSEMBLY |
| OCCUPANCY, AND WHAT WAS THE OCCUPANCY PREVIOUSLY. |
| PLEASE CLARIFY. |
| |