Plan Review Notes
Plan Review Notes For Permit 06090243
Permit Number 06090243
Review Stop M
Sequence Number 3
Notes
Date Text
2007-11-06 13:33:12REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 *PLEASE NOTE* A FINE OF FOUR TIMES THE PERMIT FEE WAS
 ISSUED FOR MECHANICAL, ELECTRICAL AND PLUMBING FOR WORK
 DONE WITHOUT A PERMIT. PLEASE PROVIDE DETAILED
 INFORMATION REGARDING WORK DONE WITHOUT PERMITS AS WELL
 AS ALL WORK TO BE DONE UNDER THIS PERMIT. THERE HAS
 BEEN A CHANGE OF OCCUPANCY UNDERTAKEN WITHOUT PERMITS.
 THEREFORE THE NOTES ON THE PLANS REGARDING THE EXISTING
 CHURCH ARE NOT ACCURATE. THERE IS NO ASSEMBLY OCCUPANCY
 AT THIS LOCATION EXISTING OR OTHERWISE PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY BY THE BUILDING
 OFFICIAL. THE ISSUANCE OF PERMITS AND THE SUCCESSFUL
 COMPLETION OF ALL REQUIRED INSPECTIONS ARE REQUIRED
 BEFORE A CERTIFICATE OF OCCUPANCY CAN BE ISSUED.
  
 NOTE: ALL A/C SYSTEMS IN THIS PROPOSED BUILDING WERE
 INSTALLED WITHOUT A PERMIT. UNTIL THEY HAVE BEEN
 PERMITTED, INSPECTED AND PASSED, THEY ARE NOT TO BE
 CONSIDERED EXISTING. REMOVE NOTATIONS FROM PLANS
 CLAIMING THE MECHANICAL SYSTEMS ARE EXISTING. PLEASE
 PROVIDE THE REQUIRED DETAILS AND DOCUMENTATION FOR
 NEWLY INSTALLED A/C SYSTEMS. INCLUDE EQUIPMENT
 SCHEDULES, DUCT SIZES, CFMS AT ALL DIFFUSERS AND
 REGISTERS. SEE FBC,M 106.3.5.1.4.
  
 NOTE: ALL A/C SYSTEMS WILL BE REVIEWED AS NEW. HOWEVER,
 THE REVIEW WILL BE LIMITED BASED ON THE SMALL AMOUNT OF
 INFORMATION PROVIDED. ADDITIONAL COMMENTS ARE LIKELY
 ONCE ALL REQUIRED INFORMATION IS PROVIDED.
  
 1. PG M.1: BATHROOM EXHAUST, HVAC NOTE # 6 INDICATES
 THAT BATH EXHAUST FANS ARE 100 CFM. THE WOMEN?S
 BATHROOM HAS 3 WATER CLOSETS AND THE MEN?S BATHROOM HAS
 2 WATER CLOSETS AND 2 URINALS. THESE SPACES ARE
 REQUIRED TO HAVE EXHAUST RATES OF 50 CFM PER WATER
 CLOSET OR URINAL IN ACCORDANCE WITH FBC,M TABLE 403.3.
 THE WOMEN?S RESTROOM REQUIRES MIN. 150 CFM AND THE
 MEN?S RESTROOM REQUIRES MIN. 200 CFM. SHOW HOW THESE
 FANS ARE TO BE CONTROLLED, THE SIZE AND LOCATION OF
 EXHAUST DUCTS AND THE DISCHARGE LOCATION. SHOW
 COMPLIANCE WITH FBC,M 401.3, 401.5, 401.6, 403.2.1(3).
  
 2. PG M.1: OUTDOOR AIR CALCULATIONS SCHEDULE SHOWN ON
 PLANS DOES NOT ACTUALLY CONTAIN ANY CALCULATIONS. IT IS
 MERELY A LISTING OF THE REQUIREMENTS OF FBC,M TABLE
 403.3. IT PROVIDES NO INFORMATION REGARDING THE AMOUNT
 OF OUTSIDE AIR REQUIRED FOR EACH LOCATION OR THE AMOUNT
 OF OUTSIDE AIR BEING PROVIDED FOR EACH AREA. SHOW THE
 CALCULATIONS BASED ON THE ACTUAL OCCUPANT LOAD OF THESE
 SPACES AND THE AMOUNT OF OUTSIDE AIR PROVIDED. ALSO,
 PROVIDE AN AIR BALANCE SCHEDULE SHOWING WHETHER OR NOT
 THE BUILDING IS PRESSURIZED WITH RESPECT TO THE
 OUTDOORS IN ACCORDANCE WITH FBC 13-409.1.ABC.2.
  
 3. PG M.1: AHU?S IN CLOSET #2 ARE BOTH SHOWN SHARING A
 RETURN PLENUM CLOSET. WHERE MULTIPLE AIR-HANDLING
 SYSTEMS SHARE COMMON RETURN AIR PLENUMS WITH A COMBINED
 DESIGN CAPACITY GREATER THAN 2,000 CFM, THE RETURN AIR
 AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH SMOKE
 DETECTORS IN ACCORDANCE WITH FBC,M 606.2.1. SEE FBC,M
 606.2.2.
 ANY OF THE OTHER SMOKE DETECTORS SHALL BE INSTALLED IN
 ANY OF THE OTHER SUPPLY AIR SYSTEMS IN THE BUILDING
 WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM IN THE
 SUPPLY AIR DUCT. FBC,M 606.2.1.
 4. WHAT TYPE OF DOORS ARE TO BE USED ON THE A/C CLOSETS
 WHICH ARE BEING USED AS PLENUMS? MATERIALS EXPOSED
 WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84. FBC,M 602.2.1. SHOW A
 DOOR SCHEDULE OR PROVIDE SOME INDICATION ON PLANS THAT
 DOORS USED AS PART OF PLENUM ENCLOSURES ARE IN
 COMPLIANCE WITH THIS SECTION.
  
 5. PG M.2: FLOOR PLAN SHOWS TWO SEPARATE TOILET ROOMS.
 PROVIDE VENTILATION IN THESE AREAS IN ACCORDANCE WITH
 FBC,M TABLE 403.3. SEE COMMENT #1 FOR ADDITIONAL
 REQUIREMENTS.
  
 6. LOCATIONS AND METHODS OF INSTALLATION FOR OUTDOOR
 MECHANICAL EQUIPMENT ARE NOT SHOWN ON PLANS. SHOW THE
 LOCATION OF ALL OUTDOOR EQUIPMENT ALONG WITH MEANS OF
 INSTALLATION WHICH IS IN COMPLIANCE WITH FBC,M 301.13
 AND FBC SEC.1609.
  
 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2, INCLUDING MEANS OF
 AUXILIARY OR SECONDARY DRAIN PROTECTION IN ACCORDANCE
 WITH FBC,M 307.2.3. NOTE: ALL CONDENSATE DRAIN
 MATERIALS USED IN THE PLENUM CLOSETS SHALL BE
 NON-COMBUSTIBLE IN COMPLIANCE WITH FBC,M 602.2.1.
  
 8. CHANGE OF OCUPANCY: BUILDINGS HAVING A CHANGE OF
 OCCUPANCY THAT WERE PERMITTED AFTER MARCH 15, 1979,
 SHALL COMPLY WITH THE REQUIREMENTS OF SUBCHAPTER 13-4
 FOR COMMERCIAL APPLICATIONS. WHERE THE EFFICIENCY OF A
 BUILDING COMPONENT IS UNKNOWN, IT SHALL BE DETERMINED
 IN ACCORDANCE WITH THE CRITERIA SPECIFIED IN SECTION
 101.4.2.1. SEE FBC 13-101.3. PROVIDE AN ENERGY CODE
 COMPLIANCE FORM IN ACCORDANCE WITH FBC 13-400.0.ABC.
 SEE ALSO FBC 13-400.3.ABC.1.
  