Plan Review Notes For Permit 06090243 |
Permit Number |
06090243 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-04-03 16:38:51 | *****DENIED***** | | | | PLEASE ACKNOWLEDGE THE FOLLOWING COMMENTS TAKEN FROM | | 10/24/2006 FIRE PLAN REVIEW: | | | | | | 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE | | PREVENTION CODE, 2004 EDITION SHALL BE REFERENCED. ADD | | TO CODE SUMMARY NOTES, SHEET 1/5 | | | | 02.)STRUCTURES UNDERGOING CONSTRUTION, ALTERATION, | | AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | ADD TO SHEET 1 | | | | 03.)AN ADDRESS IS REQUIRED ON THE BUILDING OF NO LESS | | THAN 6" IN HEIGHT AND 1" IN WIDTH.PLEASE INDICATE | | LOCATION OF THE ADDRESS ON THE APPROPIATE ELEVATION | | FRONTING BROADWAY AVENUE.PLEASE DISPLAY ON THE | | APPROPIATE EXTERIOR ELEVETION | | | | | | 08.)PANIC HARDWARE IS REQUIRED ON EXIT DOORS SERVING | | AN OCCUPANT LOAD GREATER THAN ONE HUNDRED.PLEASE | | ACKNOWLEDGE | | | | 09.)PLEASE INDICATE THE MINIMUM INTERIOR FINISH | | CLASSIFICATIONFOR WALLS AND CEILING IN TERMS OF CLASS | | A, B, OR C IN ACCORDANCE WITH NFPA 101, 10.2.PLEASE | | ACKNOWLEDGE | | | | 10.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). | | ADD TO SHEET 1 | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM EAS ADDRESSED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|