Date |
Text |
2007-03-18 14:09:15 | ** UNSAT ** |
| |
| ** PLEASE KNOW THAT THIS IS A CHANGE IN OCCUPANCY AND |
| ALL ELECTRICAL WILL BE REQUIRED TO MEET THE CURRENT |
| CODES ADOPTED WHEN PERMIT WAS APPLIED. |
| THE PERMIT DESCRIPTION ON COMPUTER NOW INDICATES BUILD |
| OUT FOR NEW CHURCH. |
| |
| *********************************** |
| ** PLEASE SEE PLANS ARE STAMPED FROM PALM BEACH COUNTY |
| FOR IMPACT FEES WHICH INDICATE *EXISTING* USEAND |
| PLANS SUBMITTED TO PALM BEACH COUNTY ALSO INDICATE |
| EXISTING USE AS A CHURCH. PLEASE KNOW THIS WILL BE |
| FORWARD TO PALM BEACH COUNTY FOR THIS USE AS NEW AS IT |
| IS NOT EXISTING. |
| *************************************** |
| |
| 1) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS |
| ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS |
| FOLLOWS. |
| 2004 FBC |
| 2002 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND |
| OTHER CODES WILL BE REQUIRED FOR OTHER TRADES. |
| |
| 2) NOTE: PLEASE SEE MISSING CERTIFICATE OF |
| AUTHORIZATION NUMBER ON TITLE BLOCKS FOR THE COMPANY |
| LISTED AS MCR PROFESSIONAL ENGINEERING INC. PLEASE SEE |
| SHEET IS ATTACHED FROM THE DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION WITH THE LICENSE INFORMATION AS |
| NEED. PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.002 AND FLORIDA STATUTES 471.023. |
| |
| 3) NOTE: PLEASE SEE FBC CHAPTER 13. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE |
| SOME AREAS WHICH DO NOT INDICATE ANY LIGHTING CONTROLS. |
| PLEASE SEE AREAS OF STAIRS WHICH WILL ALSO BE NOTED IN |
| ANOTHER NOTE FOR LIFE SAFETY AND EGRESS WHICH WILL BE |
| REQUIRED TO CONTAIN A AUTOMATED DEVICE FOR OCCUPANTS |
| WHERE SWITCHED. |
| PLEASE VERIFY THE COVERAGE ON THE DEVICES AS NOTED AS |
| THE COVERAGE IN LARGER BATHROOMS WHICH CONTAIN MULTIPLE |
| STALLS AND ALSO HALLWAY AREAS WHICH INDICATE WALL |
| MOUNTED DEVICES. PLEASE VERIFY IF THESE DEVICES AS |
| SHOWN WILL PROVIDE THE COVERAGE AS NEEDED. |
| PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. |
| PLEASE SEE 13-415.1.AB.1, PLEASE SEE MISSING ENERGY |
| CALCULATIONS FOR BUILD OUT OF NEW CHURCH. |
| PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT |
| INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE |
| THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE |
| SUBMITTED. |
| * PLEASE SEE ALL OF CHAPTER 13. |
| 13-103.1.1.1 |
| |
| 4) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| WORK NEEDS TO BE DECLARED. UNABLE TO VERIFY AT THIS |
| TIME. BASED ON THE SCOPE OF ELECTRICAL WORK AND OTHER |
| TRADES THE APPLIED VALUE IS LOW. PLEASE SEE FBC 108.3 |
| ADMIN SECTION. |
| |
| 5) NOTE: PLEASE CORRELATE ELECTRICAL PLANS AND RISER |
| FOR THE ELECTRICAL SERVICE AS SHOWN AND NOTED. PLEASE |
| KNOW THERE ARE MANY NOTES ON PLANS TO VERIFY SERVICE, |
| CONDUCTORS, AND FEEDERS ETC. PLEASE KNOW THAT ALL THE |
| VERIFICATION IS REQUIRED BEFORE PERMIT ISSUANCE AND |
| SHALL BE STATED ON PLANS AS REQUIRED FOR NEW BUILD |
| OUT. |
| PLEASE SEE RISER MENTIONS NEW PANELS, YET MDP MENTIONS |
| PANELS AS EXISTING? |
| THESE ARE PANELS WHICH WERE INSTALLED WITHOUT PERMITS, |
| THEY SHALL BE INCLUDED AS *NEW* ON THESE RECORD SETS OF |
| PLANS. |
| PLEASE SEE MDP AND PLANS DO NOT MATCH AND PROVIDE |
| ENOUGH INFORMATION FOR THE PANELS SHOWN FOR AIR |
| HANDLING UNITS 1,2 AND 3. |
| (PLEASE ALSO SEE THE NEXT COMMENT #6.) |
| PLEASE CLARIFY SEVERAL PANELS ON PLANS WHICH MENTIONS |
| *EXIST PANEL, NOT USED*? PLEASE SEE NO INFORMATION IS |
| PROVIDED FOR THESE AND WHETHER OR NOT THESE PANELS ARE |
| BEING REMOVED? PLEASE INDICATE IF THEY. PLEASE INDICATE |
| IF THEY ARE BEING REMOVED, IF NOT THEN PLEASE INCLUDE |
| ON PANEL SCHEDULES, PLANS, RISER ETC. |
| |
| 6) NOTE: PLEASE CORRELATE ALL LOADS FOR AIR |
| CONDITIONING EQUIPMENT. PLEASE SEE THE LOAD |
| CALCULATIONS INDICATE A TOTAL OF 27KVA, YET THE PANEL |
| SCHEDULE FOR PANEL *B* ALONE SHOWS 30KVA FOR A/C |
| EQUIPMENT. PLEASE SEE THE LOAD ON CIRCUIT 1 ON THE MDP |
| INDICATES 18KVA WHICH EXCEEDS THE RATING OF THE OVER |
| CURRENT PROTECTION DEVICE AS SHOWN FEEDING AHU 1, 2 AND |
| 3? |
| PLEASE SEE NOTE ABOVE AS INFORMATION FOR THE FEEDERS |
| ETC TO THE AHU PANELS NEEDS TO BE SUBMITTED FOR REVIEW. |
| NOT ENOUGH INFORMATION IS SUBMITTED FOR FULL REVIEW OF |
| CODE COMPLIANCE. |
| NEC 220, 424.3, 215.5, ETC. |
| FBC 106.3.5.1.2, 106.1.2 |
| ** PLEASE ALSO VERIFY THE CONDENSING UNITS WHICH ARE |
| SHOWN AS 3-PHASE AND AIR HANDLING UNITS AS SINGLE PHASE |
| AND CONDENSING UNITS BEING SHOWN AS 3-PHASE WITH AIR |
| HANDLING UNITS TO A SINGLE PHASE PANEL?? |
| |
| 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PANEL |
| SCHEDULES FOR ALL ROOMS AND AREAS WHICH THE CIRCUIT |
| FEEDS. PLEASE SEE 408.4 AND COMMENTARY WHICH IS TAKEN |
| FROM THE CODE. |
| * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 8) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| EGRESS PATHS MEETING NFPA-101 7.8 AND 7.9. |
| PLEASE SEE 7.8.1.3 AND 7.9.2.2 FOR STAIR AREAS. |
| PLEASE SHOW LIGHTING LEVELS UNDER NORMAL AND EMERGENCY |
| CONDITIONS. |
| PLEASE ALSO SEE NOTE ABOVE WITH RESPECT TO CONTROLS FOR |
| LIGHTING WHICH SHALL NOT LEAVE ANY ONE AREA IN TOTAL |
| DARKNESS BASED ON THE SWITCHING OF A DEVICE, TRIPPING |
| OF A BREAKER ETC. |
| PLEASE SEE BUILDING COMMENTS FOR POSSIBLE 2ND MEANS OF |
| EGRESS WHICH MAY BE REQUIRED. PLEASE KNOW ANY OTHER |
| EGRESS PATH FROM SECOND FLOOR WHICH MAY APPEARS TO |
| PLACE OCCUPANTS OVER A ROOF AREA AND THEN TO STAIRS ON |
| THE OUTSIDE OF A BUILDING LEADING TO THE PUBLIC RIGHT |
| OF WAY BELOW. |
| PLEASE PROVIDE LIGHTING AS REQUIRED FOR THESE AREAS. |
| PLEASE INDICATE NORMAL AND EMERGENCY FOR STAGE AREA AND |
| STAIRS FROM THIS AREA. |
| |
| 9) NOTE: PLEASE SEE 620.23, 620.24 WHICH REQUIRES |
| DEDICATED CIRCUITS FOR ELEVATOR LIGHTS/RECEPTACLES AND |
| ELEVATOR EQUIPMENT ROOMS. PLEASE SEE THAT SOME OF THIS |
| IS DONE; HOWEVER PLEASE SEE THAT THESE CIRCUITS MAY NOT |
| FEED ANY OTHER AREAS. |
| PLEASE ALSO INDICATE AN EMERGENCY LIGHT FIXTURE OF SOME |
| KIND IN ELEVATOR EQUIPMENT ROOM. 700.12E, 700.16, LS |
| 7.8, 7.9 AND STATE ELEVATOR CODE. |
| |
| 10) NOTE: PLEASE INDICATE HOW LIGHTING AND RECEPTACLE |
| LOADS ARE DERIVED. PLEASE SEE 220.3, 220.10, 220.11, |
| 220.13 ETC. |
| |
| 11) NOTE: PLEASE PLACE INFORMATION ON SYMBOL LEGEND FOR |
| HORN AND STROBE DEVICES FOR FBC 2004 ADA LEVELS. |
| 11-4.28.1, .2 AND .3(4). |
| PLEASE SEE THERE ARE SEVERAL DIFFERENCES IN THE POWER |
| PLANS COMPARED TO THE LIGHTING PLANS FOR DEVICE |
| LOCATIONS. |
| PLEASE ALSO SEE 11-4.28.1 AS THERE IS MANY LOCATIONS |
| /ROOMS/AREAS WHICH DO NOT INDICATE ANY DEVICES. |
| |
| 12) NOTE: PLEASE CORRELATE ALL ARCHITECTURAL SHEETS |
| WITH THE ELECTRICAL PLANS AS THERE ARE PANELS NOTED ON |
| OTHER SHEETS WHICH DO NOT CORRELATE WITH ELECTRICAL FOR |
| SIZES ETC. |
| FBC 106.1.2, 106.3.5.1.2. |
| |
| 13) NOTE: PLEASE SEE TITLE BLOCKS WHICH CONTAINS |
| *WHITE-OUT* OVER THE DRAFTING FIRM, PLEASE DO NOT USE |
| WHITE OUT ON PLANS AND REMOVE THE TITLE BLOCKS WHEN |
| REVISING PLANS. |
| FS 471/481 |
| |
| ** PLEASE COMPLETE, CORRELATE AND SUBMIT PLANS FOR |
| REVIEW. |
| ** PLEASE KNOW AT THIS TIME, BASED ON MANY ITEMS WHICH |
| CAN NOT BE REVIEWED FOR CODE COMPLIANCE, THERE MAY VERY |
| WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH ARE |
| NOT ON THIS REVIEW AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |