Plan Review Notes
Plan Review Notes For Permit 06090243
Permit Number 06090243
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-18 14:09:15** UNSAT **
  
 ** PLEASE KNOW THAT THIS IS A CHANGE IN OCCUPANCY AND
 ALL ELECTRICAL WILL BE REQUIRED TO MEET THE CURRENT
 CODES ADOPTED WHEN PERMIT WAS APPLIED.
 THE PERMIT DESCRIPTION ON COMPUTER NOW INDICATES BUILD
 OUT FOR NEW CHURCH.
  
 ***********************************
 ** PLEASE SEE PLANS ARE STAMPED FROM PALM BEACH COUNTY
 FOR IMPACT FEES WHICH INDICATE *EXISTING* USEAND
 PLANS SUBMITTED TO PALM BEACH COUNTY ALSO INDICATE
 EXISTING USE AS A CHURCH. PLEASE KNOW THIS WILL BE
 FORWARD TO PALM BEACH COUNTY FOR THIS USE AS NEW AS IT
 IS NOT EXISTING.
 ***************************************
  
 1) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS.
 2004 FBC
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCKS FOR THE COMPANY
 LISTED AS MCR PROFESSIONAL ENGINEERING INC. PLEASE SEE
 SHEET IS ATTACHED FROM THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION WITH THE LICENSE INFORMATION AS
 NEED. PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FLORIDA STATUTES 471.023.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 SOME AREAS WHICH DO NOT INDICATE ANY LIGHTING CONTROLS.
 PLEASE SEE AREAS OF STAIRS WHICH WILL ALSO BE NOTED IN
 ANOTHER NOTE FOR LIFE SAFETY AND EGRESS WHICH WILL BE
 REQUIRED TO CONTAIN A AUTOMATED DEVICE FOR OCCUPANTS
 WHERE SWITCHED.
 PLEASE VERIFY THE COVERAGE ON THE DEVICES AS NOTED AS
 THE COVERAGE IN LARGER BATHROOMS WHICH CONTAIN MULTIPLE
 STALLS AND ALSO HALLWAY AREAS WHICH INDICATE WALL
 MOUNTED DEVICES. PLEASE VERIFY IF THESE DEVICES AS
 SHOWN WILL PROVIDE THE COVERAGE AS NEEDED.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING.
 PLEASE SEE 13-415.1.AB.1, PLEASE SEE MISSING ENERGY
 CALCULATIONS FOR BUILD OUT OF NEW CHURCH.
 PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT
 INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE
 THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE
 SUBMITTED.
 * PLEASE SEE ALL OF CHAPTER 13.
 13-103.1.1.1
  
 4) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK NEEDS TO BE DECLARED. UNABLE TO VERIFY AT THIS
 TIME. BASED ON THE SCOPE OF ELECTRICAL WORK AND OTHER
 TRADES THE APPLIED VALUE IS LOW. PLEASE SEE FBC 108.3
 ADMIN SECTION.
  
 5) NOTE: PLEASE CORRELATE ELECTRICAL PLANS AND RISER
 FOR THE ELECTRICAL SERVICE AS SHOWN AND NOTED. PLEASE
 KNOW THERE ARE MANY NOTES ON PLANS TO VERIFY SERVICE,
 CONDUCTORS, AND FEEDERS ETC. PLEASE KNOW THAT ALL THE
 VERIFICATION IS REQUIRED BEFORE PERMIT ISSUANCE AND
 SHALL BE STATED ON PLANS AS REQUIRED FOR NEW BUILD
 OUT.
 PLEASE SEE RISER MENTIONS NEW PANELS, YET MDP MENTIONS
 PANELS AS EXISTING?
 THESE ARE PANELS WHICH WERE INSTALLED WITHOUT PERMITS,
 THEY SHALL BE INCLUDED AS *NEW* ON THESE RECORD SETS OF
 PLANS.
 PLEASE SEE MDP AND PLANS DO NOT MATCH AND PROVIDE
 ENOUGH INFORMATION FOR THE PANELS SHOWN FOR AIR
 HANDLING UNITS 1,2 AND 3.
 (PLEASE ALSO SEE THE NEXT COMMENT #6.)
 PLEASE CLARIFY SEVERAL PANELS ON PLANS WHICH MENTIONS
 *EXIST PANEL, NOT USED*? PLEASE SEE NO INFORMATION IS
 PROVIDED FOR THESE AND WHETHER OR NOT THESE PANELS ARE
 BEING REMOVED? PLEASE INDICATE IF THEY. PLEASE INDICATE
 IF THEY ARE BEING REMOVED, IF NOT THEN PLEASE INCLUDE
 ON PANEL SCHEDULES, PLANS, RISER ETC.
  
 6) NOTE: PLEASE CORRELATE ALL LOADS FOR AIR
 CONDITIONING EQUIPMENT. PLEASE SEE THE LOAD
 CALCULATIONS INDICATE A TOTAL OF 27KVA, YET THE PANEL
 SCHEDULE FOR PANEL *B* ALONE SHOWS 30KVA FOR A/C
 EQUIPMENT. PLEASE SEE THE LOAD ON CIRCUIT 1 ON THE MDP
 INDICATES 18KVA WHICH EXCEEDS THE RATING OF THE OVER
 CURRENT PROTECTION DEVICE AS SHOWN FEEDING AHU 1, 2 AND
 3?
 PLEASE SEE NOTE ABOVE AS INFORMATION FOR THE FEEDERS
 ETC TO THE AHU PANELS NEEDS TO BE SUBMITTED FOR REVIEW.
 NOT ENOUGH INFORMATION IS SUBMITTED FOR FULL REVIEW OF
 CODE COMPLIANCE.
 NEC 220, 424.3, 215.5, ETC.
 FBC 106.3.5.1.2, 106.1.2
 ** PLEASE ALSO VERIFY THE CONDENSING UNITS WHICH ARE
 SHOWN AS 3-PHASE AND AIR HANDLING UNITS AS SINGLE PHASE
 AND CONDENSING UNITS BEING SHOWN AS 3-PHASE WITH AIR
 HANDLING UNITS TO A SINGLE PHASE PANEL??
  
 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PANEL
 SCHEDULES FOR ALL ROOMS AND AREAS WHICH THE CIRCUIT
 FEEDS. PLEASE SEE 408.4 AND COMMENTARY WHICH IS TAKEN
 FROM THE CODE.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS MEETING NFPA-101 7.8 AND 7.9.
 PLEASE SEE 7.8.1.3 AND 7.9.2.2 FOR STAIR AREAS.
 PLEASE SHOW LIGHTING LEVELS UNDER NORMAL AND EMERGENCY
 CONDITIONS.
 PLEASE ALSO SEE NOTE ABOVE WITH RESPECT TO CONTROLS FOR
 LIGHTING WHICH SHALL NOT LEAVE ANY ONE AREA IN TOTAL
 DARKNESS BASED ON THE SWITCHING OF A DEVICE, TRIPPING
 OF A BREAKER ETC.
 PLEASE SEE BUILDING COMMENTS FOR POSSIBLE 2ND MEANS OF
 EGRESS WHICH MAY BE REQUIRED. PLEASE KNOW ANY OTHER
 EGRESS PATH FROM SECOND FLOOR WHICH MAY APPEARS TO
 PLACE OCCUPANTS OVER A ROOF AREA AND THEN TO STAIRS ON
 THE OUTSIDE OF A BUILDING LEADING TO THE PUBLIC RIGHT
 OF WAY BELOW.
 PLEASE PROVIDE LIGHTING AS REQUIRED FOR THESE AREAS.
 PLEASE INDICATE NORMAL AND EMERGENCY FOR STAGE AREA AND
 STAIRS FROM THIS AREA.
  
 9) NOTE: PLEASE SEE 620.23, 620.24 WHICH REQUIRES
 DEDICATED CIRCUITS FOR ELEVATOR LIGHTS/RECEPTACLES AND
 ELEVATOR EQUIPMENT ROOMS. PLEASE SEE THAT SOME OF THIS
 IS DONE; HOWEVER PLEASE SEE THAT THESE CIRCUITS MAY NOT
 FEED ANY OTHER AREAS.
 PLEASE ALSO INDICATE AN EMERGENCY LIGHT FIXTURE OF SOME
 KIND IN ELEVATOR EQUIPMENT ROOM. 700.12E, 700.16, LS
 7.8, 7.9 AND STATE ELEVATOR CODE.
  
 10) NOTE: PLEASE INDICATE HOW LIGHTING AND RECEPTACLE
 LOADS ARE DERIVED. PLEASE SEE 220.3, 220.10, 220.11,
 220.13 ETC.
  
 11) NOTE: PLEASE PLACE INFORMATION ON SYMBOL LEGEND FOR
 HORN AND STROBE DEVICES FOR FBC 2004 ADA LEVELS.
 11-4.28.1, .2 AND .3(4).
 PLEASE SEE THERE ARE SEVERAL DIFFERENCES IN THE POWER
 PLANS COMPARED TO THE LIGHTING PLANS FOR DEVICE
 LOCATIONS.
 PLEASE ALSO SEE 11-4.28.1 AS THERE IS MANY LOCATIONS
 /ROOMS/AREAS WHICH DO NOT INDICATE ANY DEVICES.
  
 12) NOTE: PLEASE CORRELATE ALL ARCHITECTURAL SHEETS
 WITH THE ELECTRICAL PLANS AS THERE ARE PANELS NOTED ON
 OTHER SHEETS WHICH DO NOT CORRELATE WITH ELECTRICAL FOR
 SIZES ETC.
 FBC 106.1.2, 106.3.5.1.2.
  
 13) NOTE: PLEASE SEE TITLE BLOCKS WHICH CONTAINS
 *WHITE-OUT* OVER THE DRAFTING FIRM, PLEASE DO NOT USE
 WHITE OUT ON PLANS AND REMOVE THE TITLE BLOCKS WHEN
 REVISING PLANS.
 FS 471/481
  
 ** PLEASE COMPLETE, CORRELATE AND SUBMIT PLANS FOR
 REVIEW.
 ** PLEASE KNOW AT THIS TIME, BASED ON MANY ITEMS WHICH
 CAN NOT BE REVIEWED FOR CODE COMPLIANCE, THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH ARE
 NOT ON THIS REVIEW AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  