Plan Review Notes
Plan Review Notes For Permit 06090243
Permit Number 06090243
Review Stop P
Sequence Number 1
Notes
Date Text
2006-10-11 08:02:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. AN ARCHITECT OR ENGINEER IS REQUIRED TO DESIGN THE
 PLANS PER FS 481.229
  
 2. HOLD DATED 2-9-05 INDICATES THAT COMPLETE PLANS ARE
 REQUIRED. THIS IS A CHANGE OF OCCUPANCY, AND WORK WAS
 DONE WITH PERMITS. PLEASE SUBMIT FLOOR PLANS FOR BOTH
 FLOORS SHOWING FLOOR PLANS PRIOR TO CHANGES MADE WITH
 OUT PERMITS. SECTION 106.1.1.
  
 3. PER FBC-2004 EXISTING BUILDING CODE, INDICATE LEVEL
 OF ALTERATION. CHAPTER 3.
  
 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES
 PER TABLES 1004.2 AND 403.1.
  
 5. SEPARATE FACILITIES ARE REQUIRED FOR MEN AND WOMEN.
 NO WOMEN'S TOILET ROOM INDICATED. SECTION 403.2.
  
 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS
 IS NOT INDICATED ON PLANS.
  
 7. PER TABLE 403.1 AT LEAST ONE DRINKING FOUNTAIN IS
 REQUIRED.
  
 8. SHT 3/5 HAS A NOTE THAT STATES, "PLUMBING PERMIT ON
 RECORD". SEE ATTACHED SHEET. NO PLUMBING PERMIT IS
 INDICATED ON RECORD.
  
 9. SHT 3/5 MEW MEN'S TOILET ROOM STALL DOES NOT COMPLY
 WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3
 EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE
 TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION
 11-4.22.3.
  
 10. SHT 3/5 ELEVATIONS FOR WATER CLOSETS AND LAVS. SHOW
 THE FOLLOWING INFORMATION:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT (SHOWN AS 20")
 C. 11-4.16.4 GRAB BARS (SHOW LENGTHS)
 D. 11-4.16.5 FLUSH CONTROLS
 FOR LAV'S
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
  
 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE
 WITH 11-4.18 AND ALL SUBSECTIONS.
  
 12. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS, AS WELL AS
 11-4.1.3(10)(B) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING IF THE DRINKING FOUNTAIN
 IS NOT A HIGH/LOW UNIT.
  
 13. SHT 3/5 PLUMBING SANITARY RISER DIAGRAM. URINALS
 ARE NOT VENTED. SECTION 901.2.1.
  
 14. SUBMIT A WATER RISER DIAGRAM ISOMETRIC. SHOW ALL
 PIPE SIZES, VALVES, AND WATER HAMMER ARRESTORS AS
 REQUIRED BY SECTION 604.9. IF WATER HAMMER ARRESTORS
 ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]