Date |
Text |
2006-10-11 08:02:08 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. AN ARCHITECT OR ENGINEER IS REQUIRED TO DESIGN THE |
| PLANS PER FS 481.229 |
| |
| 2. HOLD DATED 2-9-05 INDICATES THAT COMPLETE PLANS ARE |
| REQUIRED. THIS IS A CHANGE OF OCCUPANCY, AND WORK WAS |
| DONE WITH PERMITS. PLEASE SUBMIT FLOOR PLANS FOR BOTH |
| FLOORS SHOWING FLOOR PLANS PRIOR TO CHANGES MADE WITH |
| OUT PERMITS. SECTION 106.1.1. |
| |
| 3. PER FBC-2004 EXISTING BUILDING CODE, INDICATE LEVEL |
| OF ALTERATION. CHAPTER 3. |
| |
| 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES |
| PER TABLES 1004.2 AND 403.1. |
| |
| 5. SEPARATE FACILITIES ARE REQUIRED FOR MEN AND WOMEN. |
| NO WOMEN'S TOILET ROOM INDICATED. SECTION 403.2. |
| |
| 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS |
| IS NOT INDICATED ON PLANS. |
| |
| 7. PER TABLE 403.1 AT LEAST ONE DRINKING FOUNTAIN IS |
| REQUIRED. |
| |
| 8. SHT 3/5 HAS A NOTE THAT STATES, "PLUMBING PERMIT ON |
| RECORD". SEE ATTACHED SHEET. NO PLUMBING PERMIT IS |
| INDICATED ON RECORD. |
| |
| 9. SHT 3/5 MEW MEN'S TOILET ROOM STALL DOES NOT COMPLY |
| WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3 |
| EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE |
| TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION |
| 11-4.22.3. |
| |
| 10. SHT 3/5 ELEVATIONS FOR WATER CLOSETS AND LAVS. SHOW |
| THE FOLLOWING INFORMATION: |
| FOR W/C'S |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT (SHOWN AS 20") |
| C. 11-4.16.4 GRAB BARS (SHOW LENGTHS) |
| D. 11-4.16.5 FLUSH CONTROLS |
| FOR LAV'S |
| A. 11-4.19.3 CLEAR FLOOR SPACE |
| B. 11-4.19.5 FAUCETS |
| |
| 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE |
| WITH 11-4.18 AND ALL SUBSECTIONS. |
| |
| 12. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS, AS WELL AS |
| 11-4.1.3(10)(B) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING IF THE DRINKING FOUNTAIN |
| IS NOT A HIGH/LOW UNIT. |
| |
| 13. SHT 3/5 PLUMBING SANITARY RISER DIAGRAM. URINALS |
| ARE NOT VENTED. SECTION 901.2.1. |
| |
| 14. SUBMIT A WATER RISER DIAGRAM ISOMETRIC. SHOW ALL |
| PIPE SIZES, VALVES, AND WATER HAMMER ARRESTORS AS |
| REQUIRED BY SECTION 604.9. IF WATER HAMMER ARRESTORS |
| ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE FIXTURE |
| IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 |
| AND MANUF. INSTALLATION INSTRUCTIONS. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |