Plan Review Notes
Plan Review Notes For Permit 06090243
Permit Number 06090243
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-24 11:03:23*****DENIED*****
  
  
  
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION SHALL BE REFERENCED.
  
 02.)STRUCTURES UNDERGOING CONSTRUTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.)AN ADDRESS IS REQUIRED ON THE BUILDING OF NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.PLEASE INDICATE
 LOCATION OF THE ADDRESS ON THE APPROPIATE ELEVATION
 FRONTING BROADWAY AVENUE.
  
 04.)WHAT IS THE OCCUPANCY CLASSIFICATION (I.E.
 ASEMBLY, BUSINESS, EDUCATIONAL) FOR THIS BUILDING?
  
 05.)IS THE BUILDING PROTECTED BY FIRE PROTECTION
 SYSTEMS SUCH AS A FIRE SPRINKLER AND/OR FIRE ALARM
 SYSTEM?
  
 06.)IN REFERENCE TO #5, IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE FIRE FIRE
 PROTECTION SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE
 SUBMITTED FOR REVIEW.
  
 07.)IN ADDITION TO THE FIRE EXTINGUISHERS SHOWN ON
 THE LIFE SAFETY SHEETS, PLEASE INDICATE THE LOCATION OF
 EXIT LIGHTS, EMERGENCY LIGHTS, AND COMMON PATH TRAVEL
 DISTANCES TO THE EXITS.
  
 08.)PANIC HARDWARE IS REQUIRED ON EXIT DOORS SERVING
 AN OCCUPANT LOAD GREATER THAN ONE HUNDRED.
  
 09.)PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATIONFOR WALLS AND CEILING IN TERMS OF CLASS
 A, B, OR C IN ACCORDANCE WITH NFPA 101, 10.2.
  
 10.)CONSTRUTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722