2006-09-17 00:00:00 | ********UNSAT ************ |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETE |
| ELECTRICAL PLANS FOR THIS BUILDING AS |
| THIS WAS A CHANGE IN OCCUPANCY WHICH WAS |
| NEVER PERMITTED. PLEASE SEE PERMIT |
| APPLICATIONS WHICH WERE PLACED ON "HOLD" |
| AND/VOIDED IN 2005. |
| PLEASE SEE PLANS MENTIONS PANELS SHOWN |
| AS EXISTING, HOWEVER THESE WERE NEVER |
| PERMITTED. |
| |
| ** PLEASE SEE 2004 FBC , 2002 NFPA-70, |
| NFPA-72 2002, NFPA-101 2003. |
| |
| 2) NOTE: PLEASE KNOW AS VALUE FOR SCOPE |
| OF WORK WILL EXCEED $25K, THE SCOPE OF |
| MUST BE DONE BY AN ARCHITECT OR ENGINEER |
| AND A "DRAFTING FIRM" MAY NOT DO |
| COMMERICAL PLANS OVER $25K. |
| PLEASE CONTACT THE FLORIDA BOARD OF |
| ARCHITECTS AND/OR LEGAL COUNSEL TO THE |
| BOARD. |
| FS 481.229. |
| |
| 3) NOTE: PLEASE SEE PERMIT APPLICATION |
| SHOWN MENTIONS ONLY REPLACING AN |
| EXTERIOR DOORS, HOWEVER PLANS INDICATES |
| BATH RMS ETC . PLEASE SEE NOTE ABOVE |
| WHICH WILL ALSO REQUIRE COMPLETE PLANS |
| FOR CHANGE. |
| PLEASE SEE FBC AND NFPA-70, 101 ETC FOR |
| ASSEMBLY OCCUPANCIES. |
| |
| ONE SET OF PLANS IS BEING RETAINED BY |
| THIS OFFICE. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |