Plan Review Notes
Plan Review Notes For Permit 06090238
Permit Number 06090238
Review Stop E
Sequence Number 3
Notes
Date Text
2006-12-08 19:58:53***UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
  
  
 1) NOTE:PLEASE SEE STILL MISSING REQUIRED DEDICATED
 CIRCUITS AND EQUIPMENT AS REQUIRED PER 620.22A, 620.23,
 AND 620.24 ETC.
 PLEASE COMPLETE PLANS THIS IS THE THIRD TIME FOR
 REQUEST OF THE ABOVE.
 PLEASE SEE THE FOLLOWING SECTIONS WHICH ARE BEING
 EXTRACTED FROM THE CODE IN ORDER TO HELP IN WHAT THE
 CODE REQUIRES.
  
 620.22 THE REQUIREMENTS IN 620.22(A) AND 620.22(B)
 SPECIFY THAT THE OVER-CURRENT DEVICES PROTECTING THE
 BRANCH CIRCUITS FOR ELEVATOR CAR LIGHTING AND
 HEATING/AIR CONDITIONING ARE TO BE LOCATED IN THE
 ELEVATOR MACHINE ROOM OR CONTROL ROOM OR IN THE
 ELEVATOR MACHINERY OR CONTROL SPACE. THIS REQUIREMENT
 FACILITATES EASE OF MAINTENANCE AND TROUBLESHOOTING AND
 CORRELATES WITH OTHER NORTH AMERICAN CODE REQUIREMENTS.
 SEE EXHIBIT 620.1.
  
 620.23 BRANCH CIRCUITS FOR MACHINE ROOM OR CONTROL
 ROOM/MACHINERY SPACE OR CONTROL SPACE LIGHTING AND
 RECEPTACLE(S).
 (A) SEPARATE BRANCH CIRCUIT. A SEPARATE BRANCH CIRCUIT
 SHALL SUPPLY THE MACHINE ROOM OR CONTROL ROOM/MACHINERY
 SPACE OR CONTROL SPACE LIGHTING AND RECEPTACLE(S).
 REQUIRED LIGHTING SHALL NOT BE CONNECTED TO THE LOAD
 SIDE OF A GROUND-FAULT CIRCUIT INTERRUPTER.
 LUMINAIRES ARE NOT PERMITTED TO BE CONNECTED TO THE
 LOAD SIDE OF A GFCI DEVICE OF ANY KIND, BECAUSE THE
 MACHINE ROOM LIGHTING COULD BE DE-ENERGIZED DURING
 CERTAIN FAULT CONDITIONS.
 (B) LIGHTING SWITCH. THE MACHINE ROOM OR CONTROL
 ROOM/MACHINERY SPACE OR CONTROL SPACE LIGHTING SWITCH
 SHALL BE LOCATED AT THE POINT OF ENTRY.
 (C) DUPLEX RECEPTACLE. AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, DUPLEX RECEPTACLE SHALL BE PROVIDED IN
 EACH MACHINE ROOM OR CONTROL ROOM AND MACHINERY SPACE
 OR CONTROL SPACE.
 FPN:SEE ANSI/ASME A17.1-1996, SAFETY CODE FOR ELEVATORS
 AND ESCALATORS, FOR ILLUMINATION LEVELS.
 620.24 BRANCH CIRCUIT FOR HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
 (A) SEPARATE BRANCH CIRCUIT. A SEPARATE BRANCH CIRCUIT
 SHALL SUPPLY THE HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
 REQUIRED LIGHTING SHALL NOT BE CONNECTED TO THE LOAD
 SIDE OF A GROUND-FAULT CIRCUIT INTERRUPTER.
 (B) LIGHTING SWITCH. THE LIGHTING SWITCH SHALL BE
 LOCATED SO AS TO BE READILY ACCESSIBLE FROM THE PIT
 ACCESS DOOR.
 (C) DUPLEX RECEPTACLE. AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, DUPLEX RECEPTACLE SHALL BE PROVIDED IN
 THE HOISTWAY PIT.
  
 THE RECEPTACLES REQUIRED BY 620.23 AND 620.24 ARE ALSO
 REQUIRED TO BE PROVIDED WITH GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL (SEE
 620.85). LUMINAIRES ARE NOT PERMITTED TO BE CONNECTED
 TO THE LOAD SIDE OF GFCI DEVICES. SEE ALSO THE
 COMMENTARY FOLLOWING 620.23(A).
 ANSI/ASME A17.1-1996, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
 LUMINAIRES IN PITS SHOULD BE MOUNTED SO THAT THE CAR OR
 COUNTERWEIGHT DOES NOT STRIKE THEM WHEN ON FULLY
 COMPRESSED BUFFERS. IT IS RECOMMENDED THAT LUMINAIRES
 BE MOUNTED IN THE CORNERS OF THE PIT.
  
 2) NOTE: PLEASE SEE NEW EMERGENCY AND EXIT LIGHTS NOW
 BEING SHOWN IN THIS SCOPE OF WORK SHALL INDICATE
 CIRCUITING AND MEET 700.12E. THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES
  
 3) NOTE: PLEASE SEE THAT THE ELEVATOR EQUIPMENT ROOM
 WILL BE REQUIRED TO CONTAIN AN EMERGENCY BATTERY BACK
 UP LIGHT OF SOME SORT. PLEASE SEE THIS ILLUMINATION OF
 THE ELEVATOR EQUIPMENT AND CONTROLS IN IMPERATIVE IN
 THE EVENT OF A POWER FAILURE. PLEASE SEE 700.16 AS THE
 FIXTURE SHOWN IS NOT CLEAR.
 LS 101 7.8,7.9
  
 4) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WHICH
 REQUESTED THE APPROPRIATE VALUE BE APPLIED ON THE
 PERMIT APPLICATION. PLEASE KNOW A VALUE WILL BE
 ASSESSED FOR SCOPE OF WORK AS SHOWN OF ONE IS NOT
 SHOWN. THE VALUE AS SHOWN IS LOW FOR SCOPE OF WORK AS
 SHOWN ON PLANS.
 FBC 108.3.
  
 5) NOTE: PLEASE KNOW AS A NEW DESIGNER HAS NOW TAKEN
 OVER PROJECT, PLEASE SEE FS 553.80(2)(B).
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]