2006-12-08 19:58:53 | ***UNSAT 3RD REVIEW *** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEWS WHICH |
| STILL NEED TO BE ADDRESSED. |
| |
| |
| 1) NOTE:PLEASE SEE STILL MISSING REQUIRED DEDICATED |
| CIRCUITS AND EQUIPMENT AS REQUIRED PER 620.22A, 620.23, |
| AND 620.24 ETC. |
| PLEASE COMPLETE PLANS THIS IS THE THIRD TIME FOR |
| REQUEST OF THE ABOVE. |
| PLEASE SEE THE FOLLOWING SECTIONS WHICH ARE BEING |
| EXTRACTED FROM THE CODE IN ORDER TO HELP IN WHAT THE |
| CODE REQUIRES. |
| |
| 620.22 THE REQUIREMENTS IN 620.22(A) AND 620.22(B) |
| SPECIFY THAT THE OVER-CURRENT DEVICES PROTECTING THE |
| BRANCH CIRCUITS FOR ELEVATOR CAR LIGHTING AND |
| HEATING/AIR CONDITIONING ARE TO BE LOCATED IN THE |
| ELEVATOR MACHINE ROOM OR CONTROL ROOM OR IN THE |
| ELEVATOR MACHINERY OR CONTROL SPACE. THIS REQUIREMENT |
| FACILITATES EASE OF MAINTENANCE AND TROUBLESHOOTING AND |
| CORRELATES WITH OTHER NORTH AMERICAN CODE REQUIREMENTS. |
| SEE EXHIBIT 620.1. |
| |
| 620.23 BRANCH CIRCUITS FOR MACHINE ROOM OR CONTROL |
| ROOM/MACHINERY SPACE OR CONTROL SPACE LIGHTING AND |
| RECEPTACLE(S). |
| (A) SEPARATE BRANCH CIRCUIT. A SEPARATE BRANCH CIRCUIT |
| SHALL SUPPLY THE MACHINE ROOM OR CONTROL ROOM/MACHINERY |
| SPACE OR CONTROL SPACE LIGHTING AND RECEPTACLE(S). |
| REQUIRED LIGHTING SHALL NOT BE CONNECTED TO THE LOAD |
| SIDE OF A GROUND-FAULT CIRCUIT INTERRUPTER. |
| LUMINAIRES ARE NOT PERMITTED TO BE CONNECTED TO THE |
| LOAD SIDE OF A GFCI DEVICE OF ANY KIND, BECAUSE THE |
| MACHINE ROOM LIGHTING COULD BE DE-ENERGIZED DURING |
| CERTAIN FAULT CONDITIONS. |
| (B) LIGHTING SWITCH. THE MACHINE ROOM OR CONTROL |
| ROOM/MACHINERY SPACE OR CONTROL SPACE LIGHTING SWITCH |
| SHALL BE LOCATED AT THE POINT OF ENTRY. |
| (C) DUPLEX RECEPTACLE. AT LEAST ONE 125-VOLT, |
| SINGLE-PHASE, DUPLEX RECEPTACLE SHALL BE PROVIDED IN |
| EACH MACHINE ROOM OR CONTROL ROOM AND MACHINERY SPACE |
| OR CONTROL SPACE. |
| FPN:SEE ANSI/ASME A17.1-1996, SAFETY CODE FOR ELEVATORS |
| AND ESCALATORS, FOR ILLUMINATION LEVELS. |
| 620.24 BRANCH CIRCUIT FOR HOISTWAY PIT LIGHTING AND |
| RECEPTACLE(S). |
| (A) SEPARATE BRANCH CIRCUIT. A SEPARATE BRANCH CIRCUIT |
| SHALL SUPPLY THE HOISTWAY PIT LIGHTING AND |
| RECEPTACLE(S). |
| REQUIRED LIGHTING SHALL NOT BE CONNECTED TO THE LOAD |
| SIDE OF A GROUND-FAULT CIRCUIT INTERRUPTER. |
| (B) LIGHTING SWITCH. THE LIGHTING SWITCH SHALL BE |
| LOCATED SO AS TO BE READILY ACCESSIBLE FROM THE PIT |
| ACCESS DOOR. |
| (C) DUPLEX RECEPTACLE. AT LEAST ONE 125-VOLT, |
| SINGLE-PHASE, DUPLEX RECEPTACLE SHALL BE PROVIDED IN |
| THE HOISTWAY PIT. |
| |
| THE RECEPTACLES REQUIRED BY 620.23 AND 620.24 ARE ALSO |
| REQUIRED TO BE PROVIDED WITH GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL (SEE |
| 620.85). LUMINAIRES ARE NOT PERMITTED TO BE CONNECTED |
| TO THE LOAD SIDE OF GFCI DEVICES. SEE ALSO THE |
| COMMENTARY FOLLOWING 620.23(A). |
| ANSI/ASME A17.1-1996, SAFETY CODE FOR ELEVATORS AND |
| ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) |
| AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE |
| EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE. |
| LUMINAIRES IN PITS SHOULD BE MOUNTED SO THAT THE CAR OR |
| COUNTERWEIGHT DOES NOT STRIKE THEM WHEN ON FULLY |
| COMPRESSED BUFFERS. IT IS RECOMMENDED THAT LUMINAIRES |
| BE MOUNTED IN THE CORNERS OF THE PIT. |
| |
| 2) NOTE: PLEASE SEE NEW EMERGENCY AND EXIT LIGHTS NOW |
| BEING SHOWN IN THIS SCOPE OF WORK SHALL INDICATE |
| CIRCUITING AND MEET 700.12E. THE BRANCH CIRCUIT FEEDING |
| THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS |
| THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| CONNECTED AHEAD OF ANY LOCAL SWITCHES |
| |
| 3) NOTE: PLEASE SEE THAT THE ELEVATOR EQUIPMENT ROOM |
| WILL BE REQUIRED TO CONTAIN AN EMERGENCY BATTERY BACK |
| UP LIGHT OF SOME SORT. PLEASE SEE THIS ILLUMINATION OF |
| THE ELEVATOR EQUIPMENT AND CONTROLS IN IMPERATIVE IN |
| THE EVENT OF A POWER FAILURE. PLEASE SEE 700.16 AS THE |
| FIXTURE SHOWN IS NOT CLEAR. |
| LS 101 7.8,7.9 |
| |
| 4) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WHICH |
| REQUESTED THE APPROPRIATE VALUE BE APPLIED ON THE |
| PERMIT APPLICATION. PLEASE KNOW A VALUE WILL BE |
| ASSESSED FOR SCOPE OF WORK AS SHOWN OF ONE IS NOT |
| SHOWN. THE VALUE AS SHOWN IS LOW FOR SCOPE OF WORK AS |
| SHOWN ON PLANS. |
| FBC 108.3. |
| |
| 5) NOTE: PLEASE KNOW AS A NEW DESIGNER HAS NOW TAKEN |
| OVER PROJECT, PLEASE SEE FS 553.80(2)(B). |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |