Date |
Text |
2006-09-24 00:00:00 | *** UNSAT 2ND REVIEW*** |
| |
| ** PLEASE SEE SAME COMMENTS FROM |
| PREVIOUS REVIEW AND NEW COMMENTS. |
| |
| 1) NOTE:NO, SAME NOTE. |
| PLEASE KNOW THIS ELECTRICAL SCOPE IS |
| REQUIRED. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SUBMIT AND SHOW ALL |
| ELECTRICAL REQUIRED FOR THE NEW PROPOSED |
| ELEVATOR AND ELEVATOR MACHINE ROOM. |
| NFPA-70 620., 620.23,620.24 ETC |
| STATE ELEVATOR CODE. NFPA-101 ETC. |
| |
| ** PLEASE SEE NOTE ON PLANS MENTIONS |
| SEPARATE ELECTRICAL PERMIT ALREADY |
| APPLIED FOR, HOWEVER THE ELECTRICAL |
| PERMIT DONE WAS FOR "DEMO ONLY " OF SOME |
| EXISTING ELECTRICAL. |
| |
| ALL ELECTRICAL PLANS FOR THIS SCOPE |
| SHALL BE SUBMITTED UNDER THIS PERMIT. |
| |
| 2) NOTE: NO, SAME NOTE, NO CHANGE MADE |
| TO VALUE. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SEE VALUE SHALL BE BASED |
| ON ALL LABOUR AND MATERIALS EVEN OF ANY |
| EQUIPMENT IS BEING OWNER SUPPLIED PER |
| FBC108.3. |
| PLEASEKNOW A VALUE MAY ALSO BE ASSESSEDD |
| PER MARSHALL'S & SWIFT GUIDE AS ADOPTED |
| BY THE FBC AND THIS OFFICE. |
| |
| 3) NOTE:NO, PLEASE SEE FS 481.223(1)(A) |
| WHICH DEFINES WHO CAN PROVIDE |
| ARCHITECTURAL DOCUMENTATION. |
| COULD NOT LOCATE AN LICENSEURE |
| INFORMATION FOR SAID COMPANY AS SHOWN ON |
| PLANS. |
| PLEASE SEE 481.203, 481.229 (1)(C), AS |
| THIS SCOPE MUST BE DONE BY AN ARCHITECT |
| OR ENGINEER AND A "DESIGN" OR "DRAFTING" |
| FIRM MAY NOT DO PLANS AS SHOWN AND |
| SUBMITTED. PLEASE KNOW, THIS WAS |
| CONFIRMED WITH THE STATE'S LEGAL COUNSEL |
| TO THE FLORIDA BOARD OF ARCHITECTS ON |
| 9/22/06. |
| PLEASE MAKE ADJUSTMENTS AND PLEASE KNOW, |
| ONE SET OF PLANS ARE BEING RETAINED BY |
| THIS OFFICE AT THE REQUEST OF THE |
| BOARD'S LEGAL COUNSEL. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE ANY DOCUMENTATION |
| SIGNED,DATED AND SEALED BY THE ENGINEER |
| SHALL CONTAIN MIN TITLE BLOCKS AS |
| REQUIRED UNDER FAC 61G15-23.002. PLEASE |
| SEE THE ARCHITECTURAL TITLE BLOCK IS NOT |
| RELEVANT FOR THE ENGINEER. |
| |
| ** NEW NOTE ** |
| |
| 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| RESPECT TO REPEAT COMMENTS FOR CODE |
| COMPLIANCE WITH REPSECT TO DESIGN |
| PROFESSIONALS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |