Plan Review Notes
Plan Review Notes For Permit 06090238
Permit Number 06090238
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-24 00:00:00*** UNSAT 2ND REVIEW***
  
 ** PLEASE SEE SAME COMMENTS FROM
 PREVIOUS REVIEW AND NEW COMMENTS.
  
 1) NOTE:NO, SAME NOTE.
 PLEASE KNOW THIS ELECTRICAL SCOPE IS
 REQUIRED.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT AND SHOW ALL
 ELECTRICAL REQUIRED FOR THE NEW PROPOSED
 ELEVATOR AND ELEVATOR MACHINE ROOM.
 NFPA-70 620., 620.23,620.24 ETC
 STATE ELEVATOR CODE. NFPA-101 ETC.
  
 ** PLEASE SEE NOTE ON PLANS MENTIONS
 SEPARATE ELECTRICAL PERMIT ALREADY
 APPLIED FOR, HOWEVER THE ELECTRICAL
 PERMIT DONE WAS FOR "DEMO ONLY " OF SOME
 EXISTING ELECTRICAL.
  
 ALL ELECTRICAL PLANS FOR THIS SCOPE
 SHALL BE SUBMITTED UNDER THIS PERMIT.
  
 2) NOTE: NO, SAME NOTE, NO CHANGE MADE
 TO VALUE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE VALUE SHALL BE BASED
 ON ALL LABOUR AND MATERIALS EVEN OF ANY
 EQUIPMENT IS BEING OWNER SUPPLIED PER
 FBC108.3.
 PLEASEKNOW A VALUE MAY ALSO BE ASSESSEDD
 PER MARSHALL'S & SWIFT GUIDE AS ADOPTED
 BY THE FBC AND THIS OFFICE.
  
 3) NOTE:NO, PLEASE SEE FS 481.223(1)(A)
 WHICH DEFINES WHO CAN PROVIDE
 ARCHITECTURAL DOCUMENTATION.
 COULD NOT LOCATE AN LICENSEURE
 INFORMATION FOR SAID COMPANY AS SHOWN ON
 PLANS.
 PLEASE SEE 481.203, 481.229 (1)(C), AS
 THIS SCOPE MUST BE DONE BY AN ARCHITECT
 OR ENGINEER AND A "DESIGN" OR "DRAFTING"
 FIRM MAY NOT DO PLANS AS SHOWN AND
 SUBMITTED. PLEASE KNOW, THIS WAS
 CONFIRMED WITH THE STATE'S LEGAL COUNSEL
 TO THE FLORIDA BOARD OF ARCHITECTS ON
 9/22/06.
 PLEASE MAKE ADJUSTMENTS AND PLEASE KNOW,
 ONE SET OF PLANS ARE BEING RETAINED BY
 THIS OFFICE AT THE REQUEST OF THE
 BOARD'S LEGAL COUNSEL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ANY DOCUMENTATION
 SIGNED,DATED AND SEALED BY THE ENGINEER
 SHALL CONTAIN MIN TITLE BLOCKS AS
 REQUIRED UNDER FAC 61G15-23.002. PLEASE
 SEE THE ARCHITECTURAL TITLE BLOCK IS NOT
 RELEVANT FOR THE ENGINEER.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE WITH REPSECT TO DESIGN
 PROFESSIONALS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]