2006-09-17 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SUBMIT AND SHOW ALL |
| ELECTRICAL REQUIRED FOR THE NEW PROPOSED |
| ELEVATOR AND ELEVATOR MACHINE ROOM. |
| NFPA-70 620., 620.23,620.24 ETC |
| STATE ELEVATOR CODE. NFPA-101 ETC. |
| |
| ** PLEASE SEE NOTE ON PLANS MENTIONS |
| SEPARATE ELECTRICAL PERMIT ALREADY |
| APPLIED FOR, HOWEVER THE ELECTRICAL |
| PERMIT DONE WAS FOR "DEMO ONLY " OF SOME |
| EXISTING ELECTRICAL. |
| |
| ALL ELECTRICAL PLANS FOR THIS SCOPE |
| SHALL BE SUBMITTED UNDER THIS PERMIT. |
| |
| 2) NOTE: PLEASE SEE VALUE SAHLL BE BASED |
| ON ALL LABOUR AND MATERIALS EVEN OF ANY |
| EQUIPMENT IS BEING OWNER SUPPLIED PER |
| FBC108.3. |
| PLEASEKNOW A VALUE MAY ALOS BE ASSESSD |
| PER MARSHALL'S & SWIFT GUIDE AS ADOPTED |
| BY THE FBC AND THIS OFFICE. |
| |
| 3) NOTE: PLEASE SEE ANY DOCUMENTATION |
| SIGNED,DATED AND SEALED BY THE ENGINEER |
| SHALL CONTAIN MIN TITLE BLOCKS AS |
| REQUIRED UNDER FAC 61G15-23.002. PLEASE |
| SEE THE ARCHITECTURAL TITLE BLOCK IS NOT |
| RELEVANT FOR THE ENGINEER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |