Plan Review Notes
Plan Review Notes For Permit 06090238
Permit Number 06090238
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-14 00:00:00DENIED BY BUILDING
  
 1) PROVIDE BUILDING INFORMATION. SPECIFY
 THE TYPE OF CONSTRUCTION, BUILDING
 HEIGHT, NUMBER OF STORIES, WHETHER
 SPRINKLERED OR NOT.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) ENGINEER IS REQUIRED TO LEGIBLY
 INDICATE THEIR LICENSE NUMBER IN
 ADDITION TO NAME AND ADDRESS ON EACH
 SHEET OF THE PLANS. THIS INFORMATION IS
 ALSO REQUIRED ON SIGNED AND SEALED
 LETTERS. SEE FAC 61G15-23.002.
  
 4) OVERHEAD DOOR WILL NOT COMPLY WITH
 ENERGY CODE REQUIREMENTS IF THE LOBBY IS CONDITIONED
 SPACE OR IS NOT SEPARATED
 FROM CONDITIONED SPACE. SEE FBC 13-403
 AND 13-406.
  
 5) THE PLANS MUST BE REVISED TO SHOW THE
 TYPE OF DOORS. A LETTER IS NOT
 SUFFICIENT.
  
 6) SUBMIT PLANS THAT INDICATE THE
 EXISTING BUILDING WALL LOCATIONS PRIOR
 TO ANY DEMOLITION OR REMODELING.
  
 7) SPECIFY HOW TERMITE PROTECTION WILL
 BE PROVIDED ON THE PLANS. FBC 1816.1
  
 8) EACH ENCLOSED ELEVATOR LOBBY AND EACH
 ELEVATOR MACHINE ROOM SHALL BE PROVIDED
 WITH AN APPROVED SMOKE DETECTOR LOCATED
 IN THE LOBBY CEILING IN ACCORDANCE WITH
 NFPA 72. SMOKE DETECTORS MAY BE
 INSTALLED IN ANY HOISTWAY, AND SHALL BE
 INSTALLED IN HOISTWAYS WHICH ARE
 SPRINKLERED. WHEN THE SMOKE DETECTOR IS
 ACTIVATED, ALL AFFECTED ELEVATORS SHALL
 OPERATE IN CONFORMANCE WITH NFPA 72,
 SECTION 3?9.3. FBC 3002.8
  
 9) THE ELEVATOR MUST COMPLY WITH
 ACCESSIBILITY REQUIREMENTS OF FBC 2007.
  
 10) ELEVATOR MACHINE ROOMS AND MACHINERY
 SPACES SHALL BE ENCLOSED WITH
 CONSTRUCTION HAVING A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED RATING
 OF THE HOISTWAY ENCLOSURE SERVED BY THE
 MACHINERY. OPENINGS SHALL BE PROTECTED
 WITH ASSEMBLIES HAVING A FIRE-RESISTANCE
 RATING NOT LESS THAN THAT REQUIRED FOR
 THE HOISTWAY ENCLOSURE DOORS. FBC 3006.4
  
 11) PROVIDE DETAILS AND THE TESTED FIRE
 ASSEMBLY TYPES AND FILE NUMBERS FOR ALL
 FIRE RATED ASSEMBLIES.
  
 12)INDICATE ON THE PLANS THAT THE
 WALLS ADJACENT TO THE EGRESS STAIRS ARE
 FIRE RATED WALLS. THE DASHED LINE
 INDICATING RATED WALLS SHOULD CONTINUE
 AROUND THE STAIR SHAFT.
  
 13) FBC 3202.2 ENCROACHMENTS INTO THE
 PUBLIC RIGHT-OF-WAY ABOVE GRADE AND
 BELOW 8 FEET (2438 MM) IN HEIGHT SHALL
 BE PROHIBITED EXCEPT AS PROVIDED FOR IN
 SECTIONS 3202.2.1 THROUGH 3202.2.3 .
 DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
 SUBMIT A SITE PLAN SHOWING THE LOCATION
 OF THE PROPERTY LINES.
  
 14) SUBMIT PRODUCT APPROVALS FOR
 EXISTING STOREFRONT DOORS THAT ARE TO BE RELOCATED.
 THEY MUST COMPLY WITH IMPACT
 AND WINDLOAD REQUIREMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  