2006-09-14 00:00:00 | DENIED BY BUILDING |
| |
| 1) PROVIDE BUILDING INFORMATION. SPECIFY |
| THE TYPE OF CONSTRUCTION, BUILDING |
| HEIGHT, NUMBER OF STORIES, WHETHER |
| SPRINKLERED OR NOT. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) ENGINEER IS REQUIRED TO LEGIBLY |
| INDICATE THEIR LICENSE NUMBER IN |
| ADDITION TO NAME AND ADDRESS ON EACH |
| SHEET OF THE PLANS. THIS INFORMATION IS |
| ALSO REQUIRED ON SIGNED AND SEALED |
| LETTERS. SEE FAC 61G15-23.002. |
| |
| 4) OVERHEAD DOOR WILL NOT COMPLY WITH |
| ENERGY CODE REQUIREMENTS IF THE LOBBY IS CONDITIONED |
| SPACE OR IS NOT SEPARATED |
| FROM CONDITIONED SPACE. SEE FBC 13-403 |
| AND 13-406. |
| |
| 5) THE PLANS MUST BE REVISED TO SHOW THE |
| TYPE OF DOORS. A LETTER IS NOT |
| SUFFICIENT. |
| |
| 6) SUBMIT PLANS THAT INDICATE THE |
| EXISTING BUILDING WALL LOCATIONS PRIOR |
| TO ANY DEMOLITION OR REMODELING. |
| |
| 7) SPECIFY HOW TERMITE PROTECTION WILL |
| BE PROVIDED ON THE PLANS. FBC 1816.1 |
| |
| 8) EACH ENCLOSED ELEVATOR LOBBY AND EACH |
| ELEVATOR MACHINE ROOM SHALL BE PROVIDED |
| WITH AN APPROVED SMOKE DETECTOR LOCATED |
| IN THE LOBBY CEILING IN ACCORDANCE WITH |
| NFPA 72. SMOKE DETECTORS MAY BE |
| INSTALLED IN ANY HOISTWAY, AND SHALL BE |
| INSTALLED IN HOISTWAYS WHICH ARE |
| SPRINKLERED. WHEN THE SMOKE DETECTOR IS |
| ACTIVATED, ALL AFFECTED ELEVATORS SHALL |
| OPERATE IN CONFORMANCE WITH NFPA 72, |
| SECTION 3?9.3. FBC 3002.8 |
| |
| 9) THE ELEVATOR MUST COMPLY WITH |
| ACCESSIBILITY REQUIREMENTS OF FBC 2007. |
| |
| 10) ELEVATOR MACHINE ROOMS AND MACHINERY |
| SPACES SHALL BE ENCLOSED WITH |
| CONSTRUCTION HAVING A FIRE-RESISTANCE |
| RATING NOT LESS THAN THE REQUIRED RATING |
| OF THE HOISTWAY ENCLOSURE SERVED BY THE |
| MACHINERY. OPENINGS SHALL BE PROTECTED |
| WITH ASSEMBLIES HAVING A FIRE-RESISTANCE |
| RATING NOT LESS THAN THAT REQUIRED FOR |
| THE HOISTWAY ENCLOSURE DOORS. FBC 3006.4 |
| |
| 11) PROVIDE DETAILS AND THE TESTED FIRE |
| ASSEMBLY TYPES AND FILE NUMBERS FOR ALL |
| FIRE RATED ASSEMBLIES. |
| |
| 12)INDICATE ON THE PLANS THAT THE |
| WALLS ADJACENT TO THE EGRESS STAIRS ARE |
| FIRE RATED WALLS. THE DASHED LINE |
| INDICATING RATED WALLS SHOULD CONTINUE |
| AROUND THE STAIR SHAFT. |
| |
| 13) FBC 3202.2 ENCROACHMENTS INTO THE |
| PUBLIC RIGHT-OF-WAY ABOVE GRADE AND |
| BELOW 8 FEET (2438 MM) IN HEIGHT SHALL |
| BE PROHIBITED EXCEPT AS PROVIDED FOR IN |
| SECTIONS 3202.2.1 THROUGH 3202.2.3 . |
| DOORS AND WINDOWS SHALL NOT OPEN OR |
| PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| SUBMIT A SITE PLAN SHOWING THE LOCATION |
| OF THE PROPERTY LINES. |
| |
| 14) SUBMIT PRODUCT APPROVALS FOR |
| EXISTING STOREFRONT DOORS THAT ARE TO BE RELOCATED. |
| THEY MUST COMPLY WITH IMPACT |
| AND WINDLOAD REQUIREMENTS. |
| |