Plan Review Notes For Permit 06090190 |
Permit Number |
06090190 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-21 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 SEC. 424.2 SWIMMING | | POOLS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR PLUMBING PLAN REVIEW: | | | | 1. PLEASE CORRELATE THE PRINTS FOR | | RESUBMITTAL. THE POOL SPECIFICATIONS | | INDICATE A GAS POOL HEATER AND THE | | ELECTRICAL SCHEMATIC INDICATES AN | | ELECTRIC POOL HEATER. | | 2. FBC-2004 SEC. 424.2.14.1, OR | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | SHEETS REQUIRED, PLEASE SUBMIT) | | 3. FBC-2004 SEC. 424.2.14.2, OR | | FBCR-2004 SEC. R4101.14.2 WATER | | RETENTION, PROVIDE A POSITIVE MEANS OF | | RETAINING WATER IN THE HEATER WHEN PUMP | | IS SHUT OFF.(MANUFACTURE SHEETS | | REQUIRED, PLEASE SUBMIT) | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED PROVIDE ONE COPY OF | | ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | IN RED INK FOR REFERENCE FOR | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | | | | | |
|