Plan Review Notes For Permit 06090171
Permit Number 06090171
Review Stop E
Sequence Number 3
Notes
Date Text
2007-02-04 09:49:48*** PROVSIO/ REDLINED NOTES ***
  
 ** IMPORATANT**
  
 THE FOLLOWING MUST BE REVISED, SUBMITTED, REVIEWED AND
 STAMPED FOR JOB-SITE INSPECTION BEFORE ANY ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
  
 1) NOTE: PLEASE SEE NO TIMES ARE STATED ON PLANS FOR
 OVER RIDE CONTROLS AS PREVIOUSLY REQUESTED. PLEASE SEE
 THE RESPONSE LETTER MENTIONS THIS WILL BE SET PER THE
 OWNERS? REQUEST: HOWEVER THE MAXIMUM TIMES ARE
 DETERMINED BY THE FLORIDA BUILDING CODE
 13-415.1.ABC.1.1 AND .1.2. THIS IS NOT AN OPTION OF THE
 OWNER.
 PLEASE SEE MAXIMUM TIMES FOR ALL OCCUPANCY TYPE DEVICES
 ARE 30 MINUTES MAX.
  
  
 2) NOTE: ALL EM/EXT LTS WIRED PER 700.12E. AHEAD OF ANY
 SWITCH OR OC DEVICE.
  
 ** RISER WAS REVISED TO SHOW CORRECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW AND
 STAMPING BEFORE ANY ELECTRICLA INSPECTION. IF THERE ARE
 ANY QUESTIONS, PLEASE DO NOT HESIATE ON CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-03 19:23:42 
 IN ELEC FOR REIVEW