Plan Review Notes For Permit 06090171 |
Permit Number |
06090171 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-02-04 09:49:48 | *** PROVSIO/ REDLINED NOTES *** | | | | ** IMPORATANT** | | | | THE FOLLOWING MUST BE REVISED, SUBMITTED, REVIEWED AND | | STAMPED FOR JOB-SITE INSPECTION BEFORE ANY ROUGH | | ELECTRICAL INSPECTION IS CALLED IN. | | | | 1) NOTE: PLEASE SEE NO TIMES ARE STATED ON PLANS FOR | | OVER RIDE CONTROLS AS PREVIOUSLY REQUESTED. PLEASE SEE | | THE RESPONSE LETTER MENTIONS THIS WILL BE SET PER THE | | OWNERS? REQUEST: HOWEVER THE MAXIMUM TIMES ARE | | DETERMINED BY THE FLORIDA BUILDING CODE | | 13-415.1.ABC.1.1 AND .1.2. THIS IS NOT AN OPTION OF THE | | OWNER. | | PLEASE SEE MAXIMUM TIMES FOR ALL OCCUPANCY TYPE DEVICES | | ARE 30 MINUTES MAX. | | | | | | 2) NOTE: ALL EM/EXT LTS WIRED PER 700.12E. AHEAD OF ANY | | SWITCH OR OC DEVICE. | | | | ** RISER WAS REVISED TO SHOW CORRECTIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW AND | | STAMPING BEFORE ANY ELECTRICLA INSPECTION. IF THERE ARE | | ANY QUESTIONS, PLEASE DO NOT HESIATE ON CONTACTING THIS | | OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-02-03 19:23:42 | | | IN ELEC FOR REIVEW |
|