Date |
Text |
2006-12-03 20:42:20 | *** UNSAT 2ND REVIEW**** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND NEW |
| NOTES DUE TO THE PLANS SUBMITTED. |
| THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW |
| AND INDICATE A "NO OR OK". IF A "NO" IS SHOWN, FURTHER |
| EXPLANATION/NOTES MAY BE PRESENT. |
| ** PLEASE SEE ANY NEW NOTES ARE BEING ADDED TO THE |
| BOTTOM OF FIRST REVIEW NOTES. |
| |
| 1) NOTE: OK |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE: NO, LIGHTING CONTROLS ONLY SEEM TO BE SHOWN |
| FOR SOME LOCATIONS. PLEASE SEE 13-415.1.ABC.1.2, WHICH |
| REQUIRES CONTROL IN ALL AREAS WITH FLOOR TO CEILING |
| HEIGHT PARTITIONS. |
| PLEASE SEE RESPONSE LETTER MENTIONS LIGHTING DENSITIES |
| SHOWN ON E5.1, HOWEVER RISER AND LOAD SUMMARY WERE THE |
| ONLY ITEMS LOCATED ON 5.1. |
| PLEASE SUBMIT AND SHOW IN DETAIL THE PROPOSED LIGHTING |
| CONTROL SYSTEM. PLEASE INDICATE THE NORMAL TIME |
| SCHEDULE(S), THE TIMES ON THE TYPES OF OVER RIDE |
| DEVICES ETC. |
| PLEASE SEE PREVIOUS REVIEW COMMENTS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2, AND |
| .1.3. |
| PLEASE SEE SOME NOTES ARE MENTIONED FOR SOME SORT OF |
| LIGHTING CONTROL, HOWEVER ONLY IT SEEMS FOR COMMON |
| AREAS? |
| PLEASE SEE .1.3, FOR ALL SEPARATE AREAS, WITH FLR TO |
| CEILING HEIGHT PARTITIONS. |
| PLEASE SUBMIT AND SHOW THE ENTIRE SYSTEM BEING |
| INSTALLED AND PROPOSED. PLEASE INCLUDE ALL LOCATIONS |
| FOR OVER-RIDE DEVICES AS REQUIRED INCLUDING INGRESS/ |
| EGRESS INTO SPACE, SO THE OCCUPANT MAY VISUALLY SEE |
| LIGHTING BEING CONTROLLED. |
| PLEASE SUBMIT THE SCHEDULING TO TIME OF OPERATION. |
| PLEASE INDICATE THE MAXIMUM OF THE TIMES ALLOWED FOR |
| EACH TYPE OF OVER-RIDE DEVICE WHICH MAY BE CHOSEN. |
| (TIMER TYPE, 4HRS MAX, SENSOR TYPE 30 MINS MAX) |
| PLEASE BE SURE TO UPDATE THE SYMBOL LEGEND FOR DEVICES |
| CHOSEN. |
| PLEASE PROVIDE LIGHTING POWER DENSITIES, PER |
| 13-415.1.AB.1, 415.2.C.1, 415.2.B.1 ETC. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE: OK. |
| |
| |
| *** NEW NOTES 2ND REVIEW*** |
| |
| 1) NOTE: PLEASE SEE PANEL "LA" HAS NOW BEEN CHANGED TO |
| A 225A MLO, WITH 300A OVER CURRENT PROTECTION FEEDING |
| THIS PANEL?? |
| PLEASE SEE PREVIOUS PLANS INDICATED THIS PANEL AS A 400 |
| MLO. |
| PLEASE SEE RISER SHOWS "LA" FEEDING "LC", WHICH IS OK, |
| HOWEVER SEE "LB" INDICATES THIS PANEL AS THE PANEL |
| CONTAINING THE "FEED-THRU" LUGS? |
| PLEASE SEE RISER AND CORRELATE ALL OF THE ABOVE. |
| ADJUST PANEL SIZES AND/OR OVER CURRENT PROTECTION AS |
| NEEDED. |
| THIS IS A NEW COMMENT AS PLANS WERE CHANGED. |
| 240.4, 310.16, 408 ETC. |
| |
| 2) NOTE: PLEASE SEE ATTACHED SHEET WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. |
| FLORIDA STATUTES 553.80(2)(B). THIS IS ONLY GIVEN AS A |
| NOTICE AT THIS TIME. |
| |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |