Plan Review Notes For Permit 06090171 |
Permit Number |
06090171 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-12-19 10:40:19 | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) ON SHEET A1.0 EXIT CORRIDOR 105THAT LEADS TO THE | | EXISTING EXIT DOOR IS SPECIFIED AS FILE ROOM. FBC | | 1013.2 PROHIBITS EGRESS THROUGH STORAGE ROOMS OR SPACES | | USED FOR SIMILAR PURPOSES. PLEASE CORRECT AND INDICATE | | THAT 105 IS A CORRIDOR AND THE FILES ARE LOCATED IN THE | | CLOSET. | | | | 3) THE EXIT LIGHT LAYOUT ON A2.0 DOES NOT INDICATE THAT | | THE EXIT AT CORRIDOR 105 IS A REQUIRED EXIT ( DUE TO | | REQUIRED EXIT SEPARATION) . PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|