Plan Review Notes
Plan Review Notes For Permit 06090171
Permit Number 06090171
Review Stop P
Sequence Number 1
Notes
Date Text
2006-10-04 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A3.1 ROOMS 136, & 138. INTERIOR
 FINISH SCHEDULE INDICATES THE WALLS TO
 BE EPOXY PAINT. SECTION 1210.2 STATES
 WALLS WITHIN 2' OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET ABOVE THE FLOOR. PLEASE INDICATE
 HOW "PAINT" MEETS THE REQUIREMENT FOR A
 HARD SURFACE.
  
 2. SHTS PO.1 & P2.1. ENGINEERS SIGNATURE
 IS REQUIRED ON THE SEAL. INITIALS ARE
 NOT ACCEPTABLE. FAC 61G15-23.002(1) AND
 FS 471.025.
  
 3. SHT P5.1 DOMESTIC WATER ISOMETRIC.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLLATION INSTRUCTIONS.
  
 4. SHT P5.1 DOMESTIC WATER ISOMETRIC.
 MOP SINK HOT WATER IS PIPED TO THE RIGHT
 SIDE OF THE FIXTURE, NOT TO THE LEFT
 SIDE AS REQUIRED IN SECTION 607.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 8O5-6731
 E-MAIL [email protected]