Plan Review Notes For Permit 06090171 |
Permit Number |
06090171 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-04 00:00:00 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. SHT A3.1 ROOMS 136, & 138. INTERIOR | | FINISH SCHEDULE INDICATES THE WALLS TO | | BE EPOXY PAINT. SECTION 1210.2 STATES | | WALLS WITHIN 2' OF URINALS AND WATER | | CLOSETS SHALL HAVE A SMOOTH, HARD, | | NONABSORBENT SURFACE, TO A HEIGHT OF 4 | | FEET ABOVE THE FLOOR. PLEASE INDICATE | | HOW "PAINT" MEETS THE REQUIREMENT FOR A | | HARD SURFACE. | | | | 2. SHTS PO.1 & P2.1. ENGINEERS SIGNATURE | | IS REQUIRED ON THE SEAL. INITIALS ARE | | NOT ACCEPTABLE. FAC 61G15-23.002(1) AND | | FS 471.025. | | | | 3. SHT P5.1 DOMESTIC WATER ISOMETRIC. | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | AND MANUF. INSTALLLATION INSTRUCTIONS. | | | | 4. SHT P5.1 DOMESTIC WATER ISOMETRIC. | | MOP SINK HOT WATER IS PIPED TO THE RIGHT | | SIDE OF THE FIXTURE, NOT TO THE LEFT | | SIDE AS REQUIRED IN SECTION 607.4. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 8O5-6731 | | E-MAIL [email protected] |
|