Plan Review Notes For Permit 06090171 |
Permit Number |
06090171 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-14 10:48:53 | ---------------------DENIED----------------------- | | | | 1. PLEASE SHOW MEANS OF CONDENSATE DISPOSAL IN | | COMPLIANCE WITH FBC,M 307.2.1 AND FBC 1503.6. AUXILIARY | | DRAIN PROTECTION IS ALSO REQUIRED PER FBC,M 307.2.3. | | | | 2. ALL R/A GRILL CONNECTIONS ARE SHOWN ON PLAN TO BE | | RIGID RECTANGULAR DUCT EXCEPT ROOM 129. NO SIZES ARE | | GIVEN AS THERE IS ONLY A DUCT SIZE SCHEDULE FOR | | FLEXIBLE DUCT. IF THE INTENT IS TO USE FLEX, PLEASE | | INDICATE SO ON PLAN. IF THE INTENT IS TO USE | | RECTANGULAR RIGID DUCT, PLEASE PROVIDE SIZES FOR EACH | | R/A DROP. NOTE: IN THIS CASE, A RECTANGULAR VOLUME | | DAMPER WILL BE REQUIRED AT EACH DROP. | | | | 3. PAGE M7.1 ROOF CURB DETAIL NOTE #9 STATES THAT A | | STRUCTURAL ENGINEER WILL PROVIDE THE NUMBER AND SIZE OF | | ANCHORS TO BE USED FOR CURB ATTACHMENT. NO SUCH | | INFORMATION WAS PROVIDED. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|