Plan Review Notes For Permit 06090171
Permit Number 06090171
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-14 10:48:53---------------------DENIED-----------------------
  
 1. PLEASE SHOW MEANS OF CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2.1 AND FBC 1503.6. AUXILIARY
 DRAIN PROTECTION IS ALSO REQUIRED PER FBC,M 307.2.3.
  
 2. ALL R/A GRILL CONNECTIONS ARE SHOWN ON PLAN TO BE
 RIGID RECTANGULAR DUCT EXCEPT ROOM 129. NO SIZES ARE
 GIVEN AS THERE IS ONLY A DUCT SIZE SCHEDULE FOR
 FLEXIBLE DUCT. IF THE INTENT IS TO USE FLEX, PLEASE
 INDICATE SO ON PLAN. IF THE INTENT IS TO USE
 RECTANGULAR RIGID DUCT, PLEASE PROVIDE SIZES FOR EACH
 R/A DROP. NOTE: IN THIS CASE, A RECTANGULAR VOLUME
 DAMPER WILL BE REQUIRED AT EACH DROP.
  
 3. PAGE M7.1 ROOF CURB DETAIL NOTE #9 STATES THAT A
 STRUCTURAL ENGINEER WILL PROVIDE THE NUMBER AND SIZE OF
 ANCHORS TO BE USED FOR CURB ATTACHMENT. NO SUCH
 INFORMATION WAS PROVIDED.
  