2006-09-18 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE PROIVDE THE YEARS FOR |
| THE CODE BEING REFERENCED WHICH ARE |
| CURRENTLY IN EFFECT AND RELEVANT TO |
| DESIGN. |
| NFPA-70 (NEC) 2002, NFPA-72 2002, |
| NFPA-101 2003 AND THE 2004 FBC ON |
| ELECTRICAL PLANS. |
| FBC 106.1.2 ADMIN SECT. |
| |
| 2) NOTE: PLEASE VERIFY THE LOCATIONS OF |
| THE EM LTS AND NIGHT LTS. |
| PLEASE SEE THE SYMBOL BEING USED FOR THE |
| NL'S APPEAR TO BE ON SOME FIXTURES WHICH |
| ARE NOT THE EM LTS/W/ BATTERY BACK UP. |
| IF THE EM LTS ARE NOT ON THE NL CIRCUIT, |
| WIRED AHEAD OF ANY SWITCHABLE MEANS, |
| THIS WOULD CAUSE EACH OF THESE TO BE RUN |
| DOWN EACH NIGHT. PLEASE SEE THAT IT |
| APPEARS IT MAY BE A MISPRINT FOR THE |
| LOCATION OF THESE ON PLANS.?? |
| 700.12E. |
| |
| 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| .1.2, AND .1.3. |
| PLEASE SEE SOME NOTES ARE MENTIONED FOR |
| SOME SORT OF LIGHTING CONTROL, HOWEVER |
| ONLY IT SEEMS FOR COMMON AREAS? |
| PLEASE SEE .1.3, FOR ALL SEPARATE AREAS, |
| WITH FLR TO CEILING HEIGHT PARTITIONS. |
| PLEASE SUBMIT AND SHOW THE ENTIRE SYSTEM |
| BEING INSTALLED AND PROPOSED. PLEASE |
| INCLUDE ALL LOCATIONS FOR OVER-RIDE |
| DEVICES AS REQUIRED INCLUDING INGRESS/ |
| EGRESS INTO SPACE, SO THE OCCUPANT MAY |
| VISUALLY SEE LIGHTING BEING CONTROLLED. |
| PLEASE SUBMIT THE SCHEDULING TO TIME OF OPERATION. |
| PLEASE INDICATE TH MAXIMUM OF THE TIMES |
| ALLOWED FOR EACH TYPE OF OVER-RIDE |
| DEVICE WHICH MAY BE CHOOSEN. (TIMER |
| TYPE, 4HRS MAX, SENSOR TYPE 30 MINS MAX) |
| PLEASE BE SURE TO UPDATE THE SYMBOL |
| LEGEND FOR DEVICES CHOSEN. |
| PLEASE PROVIDE LIGHTING POWER DENSITIES, |
| PER 13-415.1.AB.1, 415.2.C.1, 415.2.B.1 |
| ETC. |
| |
| 4) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| LOADS AT 125%. |
| 215.3,230.42 |
| |
| 5) NOTE: PLEASE SEE PANEL SCHEDULE |
| MENTIONS THE FACP IS GOING TO HAVEA |
| RECEPT AT THIS LOCATION.PLEASE VERIFY |
| THE RECEPT AND WHERE IT WILL BE LCOATED. |
| PLEASE SEE ELECTRICAL PLANS INDICATE THE |
| CIRCUIT LOCATION, HOWEVER THE FACP IS |
| NOT SHOWN. PLEASE SEE THE FOLLOWING TEXT |
| FROM NFPA-72 |
| 4.4.1.4.2.1THE DEDICATED BRANCH |
| CIRCUIT(S) AND CONNECTIONS SHALL BE |
| MECHANICALLY PROTECTED. |
| 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS |
| SHALL HAVE A RED MARKING, SHALL BE |
| ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, |
| AND SHALL BE IDENTIFIED AS "FIRE ALARM |
| CIRCUIT." |
| 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING |
| MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM |
| CONTROL |
| UNIT. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |