Plan Review Notes
Plan Review Notes For Permit 06090171
Permit Number 06090171
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-18 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROIVDE THE YEARS FOR
 THE CODE BEING REFERENCED WHICH ARE
 CURRENTLY IN EFFECT AND RELEVANT TO
 DESIGN.
 NFPA-70 (NEC) 2002, NFPA-72 2002,
 NFPA-101 2003 AND THE 2004 FBC ON
 ELECTRICAL PLANS.
 FBC 106.1.2 ADMIN SECT.
  
 2) NOTE: PLEASE VERIFY THE LOCATIONS OF
 THE EM LTS AND NIGHT LTS.
 PLEASE SEE THE SYMBOL BEING USED FOR THE
 NL'S APPEAR TO BE ON SOME FIXTURES WHICH
 ARE NOT THE EM LTS/W/ BATTERY BACK UP.
 IF THE EM LTS ARE NOT ON THE NL CIRCUIT,
 WIRED AHEAD OF ANY SWITCHABLE MEANS,
 THIS WOULD CAUSE EACH OF THESE TO BE RUN
 DOWN EACH NIGHT. PLEASE SEE THAT IT
 APPEARS IT MAY BE A MISPRINT FOR THE
 LOCATION OF THESE ON PLANS.??
 700.12E.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2, AND .1.3.
 PLEASE SEE SOME NOTES ARE MENTIONED FOR
 SOME SORT OF LIGHTING CONTROL, HOWEVER
 ONLY IT SEEMS FOR COMMON AREAS?
 PLEASE SEE .1.3, FOR ALL SEPARATE AREAS,
 WITH FLR TO CEILING HEIGHT PARTITIONS.
 PLEASE SUBMIT AND SHOW THE ENTIRE SYSTEM
 BEING INSTALLED AND PROPOSED. PLEASE
 INCLUDE ALL LOCATIONS FOR OVER-RIDE
 DEVICES AS REQUIRED INCLUDING INGRESS/
 EGRESS INTO SPACE, SO THE OCCUPANT MAY
 VISUALLY SEE LIGHTING BEING CONTROLLED.
 PLEASE SUBMIT THE SCHEDULING TO TIME OF OPERATION.
 PLEASE INDICATE TH MAXIMUM OF THE TIMES
 ALLOWED FOR EACH TYPE OF OVER-RIDE
 DEVICE WHICH MAY BE CHOOSEN. (TIMER
 TYPE, 4HRS MAX, SENSOR TYPE 30 MINS MAX)
 PLEASE BE SURE TO UPDATE THE SYMBOL
 LEGEND FOR DEVICES CHOSEN.
 PLEASE PROVIDE LIGHTING POWER DENSITIES,
 PER 13-415.1.AB.1, 415.2.C.1, 415.2.B.1
 ETC.
  
 4) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%.
 215.3,230.42
  
 5) NOTE: PLEASE SEE PANEL SCHEDULE
 MENTIONS THE FACP IS GOING TO HAVEA
 RECEPT AT THIS LOCATION.PLEASE VERIFY
 THE RECEPT AND WHERE IT WILL BE LCOATED.
 PLEASE SEE ELECTRICAL PLANS INDICATE THE
 CIRCUIT LOCATION, HOWEVER THE FACP IS
 NOT SHOWN. PLEASE SEE THE FOLLOWING TEXT
 FROM NFPA-72
 4.4.1.4.2.1THE DEDICATED BRANCH
 CIRCUIT(S) AND CONNECTIONS SHALL BE
 MECHANICALLY PROTECTED.
 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS
 SHALL HAVE A RED MARKING, SHALL BE
 ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL,
 AND SHALL BE IDENTIFIED AS "FIRE ALARM
 CIRCUIT."
 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL
 UNIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-09-17 00:00:00IN ELEC FOR REVIEW.