2006-10-05 00:00:00 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SPECIFY THE LEVEL OF ALTERATION AS |
| SPECIFIED IN CHAPTER 3 OF THE 2004 FBC |
| EXISTING BUILDING CODE. |
| |
| 3) SPECIFY THE TYPE OF CONSTRUCTION FOR |
| THE BUILDING. SEE 2004 FBC 602 AND |
| TABLES 601 AND 602. |
| |
| 4) THERE ARE TWO DETAIL ELEVENS ON SHEET |
| A5.0. PLEASE CORRECT. |
| |
| 5) SPECIFY THE INSULATION AND REQUIRED |
| FIRE RESISTANCE RATING FOR THE NEW |
| EXTERIOR MASONRY WALL SHOWN IN DETAIL |
| 11/A5.0 |
| |
| 6) 2004 FBC 1014.2.1 TWO EXITS OR EXIT |
| ACCESS DOORWAYS. |
| WHERE TWO EXITS OR EXIT ACCESS DOORWAYS |
| ARE REQUIRED FROM ANY PORTION OF THE |
| EXIT ACCESS, THE EXIT DOORS OR EXIT |
| ACCESS DOORWAYS SHALL BE PLACED A |
| DISTANCE APART EQUAL TO NOT LESS THAN |
| ONE-HALF OF THE LENGTH OF THE MAXIMUM |
| OVERALL DIAGONAL DIMENSION OF THE |
| BUILDING OR AREA TO BE SERVED MEASURED |
| IN A STRAIGHT LINE BETWEEN EXIT DOORS OR |
| EXIT ACCESS DOORWAYS. INTERLOCKING OR |
| SCISSOR STAIRS SHALL BE COUNTED AS ONE |
| EXIT STAIRWAY. |
| EXCEPTIONS: |
| 1.WHERE EXIT ENCLOSURES ARE |
| PROVIDED AS A PORTION OF THE REQUIRED |
| EXIT AND ARE INTERCONNECTED BY A 1-HOUR |
| FIRE-RESISTANCE-RATED CORRIDOR |
| CONFORMING TO THE REQUIREMENTS OF |
| SECTION 1016 , THE REQUIRED EXIT |
| SEPARATION SHALL BE MEASURED ALONG THE |
| SHORTEST DIRECT LINE OF TRAVEL WITHIN |
| THE CORRIDOR. |
| 2.WHERE A BUILDING IS EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER |
| SYSTEM IN ACCORDANCE WITH SECTION |
| 903.3.1.1 OR 903.3.1.2 , THE SEPARATION |
| DISTANCE OF THE EXIT DOORS OR EXIT |
| ACCESS DOORWAYS SHALL NOT BE LESS THAN |
| ONE-THIRD OF THE LENGTH OF THE MAXIMUM |
| OVERALL DIAGONAL DIMENSION OF THE AREA |
| SERVED. |
| THE EXITS TO THIS SPACE DO NOT COMPLY. |
| PLEASE REVISE. |
| |