Plan Review Notes
Plan Review Notes For Permit 06090106
Permit Number 06090106
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-31 15:09:57*****DENIED*****
  
  
  
 1.THE ADDRESS ON THE SUBMITTED PLANS INDICATE THAT
 THE SCOPE OF WORK WILL DONE AT 2000 NO. FLORIDA MANGO
 ROAD WHEREAS THE SUBMITTED APPLICATION STATES 2100 NO.
 FLORIDA AVENUE.THE SUBMITTED PLANS MUST REFLECT THE
 ACTUAL LOCATION OF THE JOB SITE.
  
 2.WHAT IS THE DISTANCE OF THE GENERATOR FROM THE
 BUILDING?
  
 3.WILL THE GENARATOR BE TIED INTO THE EXIT AND
 EMERGENCY LIGHTS LOCATED IN THE BUILDING?
  
  
  
  
 ****TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER
 INDICATING HOW EACH ITEM WAS ADDRESSED WHEN
 RESUBMITTING.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW