Plan Review Notes
Plan Review Notes For Permit 06090092
Permit Number 06090092
Review Stop M
Sequence Number 2
Notes
Date Text
2006-10-31 15:27:24 
 COMMENTS FROM REVIEW DATED 10-13-06:
  
 COMMENT 1, 2 ,3
  
 COMMENT 4: EF-2 TERMINATION TO THE ROOF IS NOT
 INDICATED ON PLAN SHEET M-1.2.THIS WAS NOT ADDRESSED.
 REFERENCED PLAN SHEET WAS REMOVED FROM THE RESUBMITTED
 PLANS.PLEASE PROVIDE DETAIL OF EQUIPMENT LOCATED ON
 THE ROOF.PROVIDE DETAIL OF REQUIRED CLEARANCES FROM
 ROOF SURFACE, FRESH AIR INTAKE IN RELATION TO EXHAUST
 TERMINATIONS, AS WELL AS CLEARANCES FOR THE GREASE DUCT
 TERMINATION TO PROPERTY LINES, CONTINGUOUS BUILDINGS
 ETC.2004 FMC 506.3.12.3.
  
 COMMENT 5 WAS NOT ADDRESSED.PLAN SHEET M-1 INDICATES
 EF-2 (WHICH THE LOCATION OR TERMINATION IS NOT
 INDICATED ON THE PLAN). IS THIS A GRILLE AT THE
 CEILING?A HOOD IS NOT SHOWN OVER THE OVEN.PLEASE
 INDICATE WHAT TYPE OF "OVEN" THIS IS.PLEASE
 REFERENCE 2004 FMC 507.2.1, TYPE I HOOD SHALL BE
 INSTALLED WHERE COOKING APPLIANCES PRODUCE GREASE OR
 SMOKE, SUCH AS OCCURS WITH GRIDDLES, FRYERS, BOILERS,
 OVENS, RANGES, AND WOK RANGES.A TYPE II HOOD IS SHALL
 BE INSTALLED WHERE COOKING OR DISHWASHING APPLIANCES
 THAT PRODUCE HEAT OR STEAM AND DO NOT PRODUCE GREASE OR
 SMOKE, SUCH AS STEAMERS, KETTLES, PASTA COOKERS &
 DISHWASHING MACHINES.PLEASE CLARIFY.PLEASE PROVIDE
 MANUFACTURER'S SUBMITTAL FOR THE OVEN.
  
 COMMENT6 WAS NOT ADDRESSED.(PLAN SHEET M-1.2 WAS
 REMOVED FROM SUBMITTAL SET)PLAN SHEET M-1.2 APPEARS
 TO HAVE A WALL THAT TERMINATES ABOVE THE ROOF THAT
 SEPARATES RTU-1 & EF-1. PER 2004 FMC 306.5, ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES.PLEASE NOTE, SHOULD ROOF HAVE A SLOPE
 GREATER THAN 4/14 PITCH SHOW COMPLIANCE WITH 306.5
 ITEMS 1 THROUGH 7.
  
 COMMENT 7 WAS NOT ADDRESSED.PLEASE INDICATE ACCESS TO
 ROOF.
  
 COMMENT8 WAS NOT ADDRESSED.PLEASE CLARIFY WHAT
 EQUIPMENTTHE20"X48" RETURN AIR DUCT & 20"X32"
 SUPPLY DUCT TERMINATING ON THE ROOF GO TO (RTU-1?)
  
 COMMENT 9 WAS NOT ADDRESSED.ADDITIONAL PERMITS
 REQUIRED FOR HOOD, FIRE SUPPRESSION, & WALK-IN COOLER.
 PLEASE PROVIDE PLANS AND MANUFACTURER'S SUBMITTAL DATA
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  
  
 PLEASE NOTE, FAN SCHEDULE ON PLAN SHEET M-1 SHOWS EF-1
 AS A COOKING LINE HOOD FAN BUT THE PLAN INDICATES EF-1
 IN THE RESTROOM
  
 PLEASE NOTE, GREASE DUCT ENCLOSURE OR SHAFT SHALL NOT
 ENCLOSE ANY OTHER DUCT SYSTEMS PER NFPA 96-01 SECTION
 7.7.5.2.