Plan Review Notes
Plan Review Notes For Permit 06090092
Permit Number 06090092
Review Stop G
Sequence Number 2
Notes
Date Text
2006-11-27 17:44:01DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PREVIOUS REVIEW
  
 1. SHTS A-6 & P-1. SHT A-6 INDICATES A
 NEW OVEN, AND SHT P-1 INDICATES A FRYER
 AND THE OVEN AS RECONNECTING (GAS SIZE
 AND CAPACITY SAME EXISTING). A GAS
 PERMIT WILL BE REQUIRED AND THE
 FOLLOWING INFORMATION WILL BE REQUIRED
 TO VERIFY COMPLIANCE WITH THE GAS CODE:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B"
 TO "D" IS NOT INDICATED
  
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT.
 ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C",
 AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B"
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES
 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004
 FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5
 PSI, NOT 1 PSI OR LESS.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (FOR
 ALL NEW EQUIPMENT).
 ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE
 REQUIRED FOR PLAN REVIEW.
  
 H. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731