2006-11-27 17:44:01 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| FROM PREVIOUS REVIEW |
| |
| 1. SHTS A-6 & P-1. SHT A-6 INDICATES A |
| NEW OVEN, AND SHT P-1 INDICATES A FRYER |
| AND THE OVEN AS RECONNECTING (GAS SIZE |
| AND CAPACITY SAME EXISTING). A GAS |
| PERMIT WILL BE REQUIRED AND THE |
| FOLLOWING INFORMATION WILL BE REQUIRED |
| TO VERIFY COMPLIANCE WITH THE GAS CODE: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B" |
| TO "D" IS NOT INDICATED |
| |
| B. OK |
| C. OK |
| D. OK |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT. |
| ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C", |
| AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B" |
| |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES |
| 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004 |
| FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5 |
| PSI, NOT 1 PSI OR LESS. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. (FOR |
| ALL NEW EQUIPMENT). |
| ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE |
| REQUIRED FOR PLAN REVIEW. |
| |
| H. OK |
| |